8.1.5.Automatic Operation

This mode can be set using remote control and the operation is decided by remote control setting temperature, indoor intake air temperature and outdoor air temperature.

During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to detect the indoor intake and outdoor air temperature. The operation mode is decided based on below chart.

Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2 and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based on the above operation mode chart, every 30 minutes.

Remote Control Setting Temperature (°C)

T1

T2

T3

16 ~ 18

+10

-3

-5

 

 

 

 

19 ~ 22

+8

-3

-7

 

 

 

 

23 ~ 26

+7

-3

-7

27 ~ 30

+6

-3

-8

 

 

 

 

There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or vice verse.

Operation Mode change from

Temperature shifts (°C)

Cooling/Soft Dry Heating

-2

 

 

Heating Cooling/Soft Dry

+2

Example of operation mode chart adjustment:

From the above table, if remote control setting temperature = 25,

T1 = 25 + 7 = 32; T2 = 25 - 3 = 22; T3 = 25 - 7 = 18

The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend on indoor intake air temperature and outdoor air temperature at the time when the judgment is made.

19

Image 19
Contents Contents Environmental Protection FeaturesServiceability Improvement ProductFunctions Remote ControlIndoor Unit Automatic Operation SwitchOutdoor Unit CS-E15DB4EW CU-E15DBE Product SpecificationsFPI CS-E18DB4EW CU-E18DBE CS-E18DB4EW CU-E18DBENet Weight Lb kg CS-E21DB4ES CU-E21DBE CS-E21DB4ES CU-E21DBE108 Indoor Unit & Remote Control DimensionsCS-E15DB4EW CS-E18DB4EW CS-E21DB4ES CU-E15DBE CU-E18DBE CU-E21DBE Refrigeration Cycle Diagram Block Diagram Wiring Diagram Operation Details Temperature Shifting FlowBasic Operation Soft Dry Operation Thermostat control Cooling Operation Thermostat controlHeating Operation Thermostat control Automatic Operation Basic Rotation Speed rpm Indoor Fan Motor OperationIndoor Fan Control Heating Ii. Auto Fan Speed Cooling Fan Motor Control Deodorizing Control Outdoor Fan Motor OperationPurpose Quiet operation Cooling Mode/Cooling area of Dry ModeAirflow Direction Vertical AirflowQuiet operation Heating Control contentsOFF Timer Powerful Mode OperationHour Real Time Timer Control On TimerDrain Pump Control Operation Drain Pump ErrorAuto Restart Control Indication PanelTotal Running Current Control Protection Control FeaturesIPM Power transistor Prevention Control Seconds Forced OperationControl start conditions Compressor Overheating Prevention ControlLow Pressure Prevention Control Gas Leakage Detection Low Frequency Protection ControlCooling Overload Control Anti-Dew Formation Control Anti-Freezing ControlOverload Protection Control Deice Control Operating Instructions Page Page Page Page Page Page Page Outline Installation And Servicing Air Conditioner Using R410AAbout R410A Refrigerant Necessary Tools Tools For Installing/Servicing Refrigerant PipingTorque wrenches 10.2.2. R410A ToolsSensitivity with R410A is about 23 g/year Electronic scale for refrigerant charging 10.2.3. R410A Tools Which Are Usable for R22 ModelsRefrigerant Piping Work Processing and Connecting Piping MaterialsPiping Materials Storing and Managing Piping Materials Precautions Installation, Transferring, ServicingAC Units Replacement Using Existing Refrigerant Piping Transferring Using New Refrigerant PipingRecharging Refrigerant During Servicing PrecautionServicing Tips BrazingBrazing Method for Preventing Oxidation Safety Precautions Installation InstructionsPage Select the best location Attached accessoriesOutdoor Unit Page Installation of Indoor Unit Vacuum drying Indoor Unit Drain PipingWall seal Heat InsulationConnecting the Cable to the Indoor Page Cutting and Flaring the Piping Connecting The Piping To Indoor UnitConnecting The Piping To Outdoor Unit Refer to Select the best location sectionEvacuation of the Equipment Disposal of Outdoor Unit Drain Water Auto Switch OperationHand Over Changing the Remote Control Transmission CodeREMO-CON NO. Change in Remote Control Check ItemsServicing Information TroubleshootingRated Frequency Operation Troubleshooting Air Conditioner Refrigeration cycle system Breakdown Self Diagnosis Function Judgement Error Codes TableSetting Remote Control Transmission Code Remote Control ResetAuto OFF/ON Button Disassembly of Parts Page Remove the top panel and front panel Outdoor Electronic Controller Removal ProcedureOperation Characteristics Technical DataCS-E15DB4EW CU-E15DBE CS-E18DB4EW CU-E18DBE CS-E21DB4ES CU-E21DBE CS-E21DB4ES CU-E21DBE Sensible Capacity ChartCS-E15DB4EW CU-E15DBE CS-E18DB4EW CU-E18DBECS-E15DB4EW CS-E18DB4EW CS-E21DB4ES Exploded View Indoor UnitPage CZ-BT20E Front Grille Complete Replacement Parts List Indoor Unit REF. no Part Description QTY Front Grille Complete CU-E15DBE CU-E18DBE CU-E21DBE Exploded View Outdoor UnitReplacement Parts List Outdoor Unit CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES Schematic Diagram 1/4 Electronic Circuit DiagramR17 Schematic Diagram 2/4SSR02 SSR01 Schematic Diagram 3/4WHT Schematic Diagram 4/4CU-E15DBE CU-E18DBE CU-E21DBE Schematic Diagram 1/4 FUSE2 IC1 Yellow Schematic DiagramTimer Table Indoor How to use electronic circuit diagramTimer Table Outdoor Remote Control Print Pattern Indoor Unit Printed Circuit Board Print Pattern Outdoor Unit Printed Circuit Board View