10.4.2. Transferring (Using New Refrigerant Piping)

1.Removing the unit

a.Collecting the refrigerant into the outdoor unit by pumping down

The refrigerant can be collected into the outdoor unit (pumping down) by pressing the TEST RUN button, even when the temperature of the room is low.

Check to make sure that the valve stems of the 2-way valve and 3-way valve have been opened by turning them counter- clockwise. (Remove the valve stem caps and check to see that the valve stems are fully opened position. Always use a hex wrench (with 4-mm opposing sides) to operate the valve stems.)

Press the TEST RUN button on the indoor unit, and allow preliminary operation for 5-6 minutes. (TEST RUN mode)

After stopping the operation, let the unit sit for about 3 minutes, then close the 2-way valve by turning the valve stem in the clockwise direction.

Press the TEST RUN button on the indoor unit again, and after 2-3 minutes of operation, turn the valve stem of the 3- way valve quickly in the clockwise direction to close it, then stop the operation.

Tighten the caps of the 2-way valve and 3-way valve to the stipulated torque.

Remove the connection pipes (liquid side and gas side). b. Removing the indoor and outdoor units.

Disconnect the pipes and connecting electric cables from between the indoor and outdoor units.

Put capped flare nuts onto all of the pipe connections of the indoor and outdoor units, to make sure no dust or other foreign matter enters.

Remove the indoor and outdoor units.

2.Installing the unit

Install the unit using new refrigerant piping. Follow the instructions in section 4.1 to evacuate the pipes connecting the indoor and outdoor units, and the pipes of the indoor unit, and check for gas leaks.

10.4.3. AC Units Replacement (Using Existing Refrigerant Piping)

When replacing an R410A AC unit with another R410A AC unit, you should re-flare the refrigerant piping. Even though the replacement AC unit uses the R410A, problems occur when, for example, either the AC unit maker or the refrigerating machine oil is different.

When replacing an R22 AC unit with an R410A AC unit, the following checks and cleaning procedures are necessary but are difficult to do because of the chemical characteristics of the refrigerating machine oil (as described in items c) and d) of section About R410A Refrigerant). In this case, you should use new refrigerant piping rather than the existing piping.

1.Piping check

Because of the different pressure characteristics of R22 and R410A, the design pressure for the equipment is 1.6 times different. the wall thickness of the piping must comply with that shown in Table 10, but this is not easy to check. Also, even if the thickness is correct, there may be flattened or bent portions midway through the piping due to sharp curves. Buried sections of the piping also cannot be checked.

2.Pipe cleaning

A large quantity of refrigerating machine oil (mineral oil) adheres to existing pipes due to the refrigeration cycle circulation. If the pipes are used just as they are for the R410A cycle, the capacity will be lowered due to the incompatibility of this oil with the R410A, or irregularities may occur in the refrigeration cycle. For this reason, the piping must be thoroughly cleaned, but this is difficult with the present technology.

10.4.4. Refrigerant Compatibility (Using R410A Refrigerant in R22 ACs and Vice Versa)

Do not operate an existing R22 AC with the new R410A refrigerant. Doing so would result in improper functioning of the equipment or malfunction, and might lead to a major accident such as an explosion in the refrigeration cycle. Similarly, do not operate an R410A AC with R22 refrigerant. The chemical reaction between the refrigerating machine oil used in R410A ACs and the chlorine that is contained in R22 would cause the refrigerating machine oil to degrade and lead to malfunction.

50

Image 50
Contents Contents Product FeaturesServiceability Improvement Environmental ProtectionRemote Control FunctionsAutomatic Operation Switch Indoor UnitOutdoor Unit Product Specifications CS-E15DB4EW CU-E15DBEFPI CS-E18DB4EW CU-E18DBE CS-E18DB4EW CU-E18DBENet Weight Lb kg CS-E21DB4ES CU-E21DBE CS-E21DB4ES CU-E21DBE108 CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES DimensionsIndoor Unit & Remote Control CU-E15DBE CU-E18DBE CU-E21DBE Refrigeration Cycle Diagram Block Diagram Wiring Diagram Basic Operation Temperature Shifting FlowOperation Details Heating Operation Thermostat control Cooling Operation Thermostat controlSoft Dry Operation Thermostat control Automatic Operation Indoor Fan Control Indoor Fan Motor OperationBasic Rotation Speed rpm Heating Ii. Auto Fan Speed Cooling Fan Motor Control Outdoor Fan Motor Operation Deodorizing ControlVertical Airflow Quiet operation Cooling Mode/Cooling area of Dry ModeAirflow Direction PurposeControl contents Quiet operation HeatingOn Timer Powerful Mode OperationHour Real Time Timer Control OFF TimerIndication Panel Drain Pump ErrorAuto Restart Control Drain Pump Control OperationSeconds Forced Operation Protection Control FeaturesIPM Power transistor Prevention Control Total Running Current ControlLow Frequency Protection Control Compressor Overheating Prevention ControlLow Pressure Prevention Control Gas Leakage Detection Control start conditionsCooling Overload Control Anti-Freezing Control Anti-Dew Formation ControlOverload Protection Control Deice Control Operating Instructions Page Page Page Page Page Page Page About R410A Refrigerant Installation And Servicing Air Conditioner Using R410AOutline Tools For Installing/Servicing Refrigerant Piping Necessary Tools10.2.2. R410A Tools Torque wrenchesSensitivity with R410A is about 23 g/year 10.2.3. R410A Tools Which Are Usable for R22 Models Electronic scale for refrigerant charging Piping Materials Processing and Connecting Piping Materials Refrigerant Piping Work Storing and Managing Piping Materials Installation, Transferring, Servicing PrecautionsTransferring Using New Refrigerant Piping AC Units Replacement Using Existing Refrigerant PipingPrecaution Recharging Refrigerant During ServicingBrazing Method for Preventing Oxidation BrazingServicing Tips Installation Instructions Safety PrecautionsPage Outdoor Unit Attached accessoriesSelect the best location Page Installation of Indoor Unit Indoor Unit Drain Piping Vacuum dryingHeat Insulation Wall sealConnecting the Cable to the Indoor Page Refer to Select the best location section Connecting The Piping To Indoor UnitConnecting The Piping To Outdoor Unit Cutting and Flaring the PipingEvacuation of the Equipment Auto Switch Operation Disposal of Outdoor Unit Drain WaterCheck Items Changing the Remote Control Transmission CodeREMO-CON NO. Change in Remote Control Hand OverRated Frequency Operation TroubleshootingServicing Information Troubleshooting Air Conditioner Refrigeration cycle system Breakdown Self Diagnosis Function Error Codes Table JudgementRemote Control Reset Setting Remote Control Transmission CodeAuto OFF/ON Button Disassembly of Parts Page Outdoor Electronic Controller Removal Procedure Remove the top panel and front panelCS-E15DB4EW CU-E15DBE Technical DataOperation Characteristics CS-E18DB4EW CU-E18DBE CS-E21DB4ES CU-E21DBE CS-E18DB4EW CU-E18DBE Sensible Capacity ChartCS-E15DB4EW CU-E15DBE CS-E21DB4ES CU-E21DBEExploded View Indoor Unit CS-E15DB4EW CS-E18DB4EW CS-E21DB4ESPage CZ-BT20E Front Grille Complete Replacement Parts List Indoor Unit REF. no Part Description QTY Front Grille Complete Exploded View Outdoor Unit CU-E15DBE CU-E18DBE CU-E21DBEReplacement Parts List Outdoor Unit Electronic Circuit Diagram CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES Schematic Diagram 1/4Schematic Diagram 2/4 R17Schematic Diagram 3/4 SSR02 SSR01Schematic Diagram 4/4 WHTCU-E15DBE CU-E18DBE CU-E21DBE Schematic Diagram 1/4 FUSE2 IC1 Schematic Diagram YellowTimer Table Outdoor How to use electronic circuit diagramTimer Table Indoor Remote Control Print Pattern Indoor Unit Printed Circuit Board Print Pattern Outdoor Unit Printed Circuit Board View