Page 48

CS-E15DB4EW CU-E15DBE / CS-E18DB4EW CU-E18DBE / CS-E21DB4ES CU-E21DBE

Table 11 R410A flaring dimensions

Nominal

Outside

Wall thickness

 

 

 

A (mm)

 

 

diameter

diameter

(mm)

R410A flaring

 

 

Conventional flaring tool

 

 

(mm)

 

tool, clutch type

 

 

 

 

 

 

Clutch type

Wing-nut type

 

 

 

 

 

 

 

 

 

1/4

6.35

0.8

0 - 0.5

 

1.0

- 1.5

1.5

- 2.0

3/8

9.52

0.8

0 - 0.5

 

1.0

- 1.5

1.5

- 2.0

 

 

 

 

 

 

 

 

 

1/2

12.70

0.8

0 - 0.5

 

1.0

- 1.5

2.0

- 2.5

 

 

Table 12 R22 flaring dimensions

 

 

 

 

Nominal

Outside

Wall thickness

 

 

 

A (mm)

 

 

diameter

diameter

(mm)

 

 

 

 

R410A flaring

 

 

Conventional flaring tool

 

 

(mm)

 

tool, clutch type

 

 

 

 

 

 

Clutch type

Wing-nut type

1/4

6.35

0.8

0 - 0.5

 

0.5

- 1.0

1.0

- 1.5

 

 

 

 

 

 

 

 

 

3/8

9.52

0.8

0 - 0.5

 

0.5

- 1.0

1.0

- 1.5

1/2

12.70

0.8

0 - 0.5

 

0.5

- 1.0

1.5

- 2.0

 

 

 

 

 

 

 

 

 

Table 13 R410A flare and flare nut dimensions Unit: mm

Nominal

Outside

Wall thickness

A +0, -0.4

B

C

D

Flare nut

diameter

diameter (mm)

(mm)

 

dimension

dimension

dimension

width

 

 

 

 

 

 

 

 

1/4

6.35

0.8

9.1

9.2

6.5

13

17

3/8

9.52

0.8

13.2

13.5

9.7

20

22

 

 

 

 

 

 

 

 

1/2

12.70

0.8

16.6

16.0

12.9

23

26

 

 

 

 

 

 

 

 

 

 

Table 14 R22 flare and flare nut dimensions Unit: mm

 

 

Nominal

Outside

Wall thickness

A +0, -0.4

B

C

D

Flare nut

diameter

diameter (mm)

(mm)

 

dimension

dimension

dimension

width

1/4

6.35

0.8

9.0

9.2

6.5

13

17

 

 

 

 

 

 

 

 

3/8

9.52

0.8

13.0

13.5

9.7

20

22

1/2

12.70

0.8

16.2

16.0

12.9

20

24

 

 

 

 

 

 

 

 

2.Procedure and precautions for flare connection

a.Check to make sure there is no scratches, dust, etc., on the flare and union.

b.Align the flared surface with the axial center of the union.

c.Use a torque wrench, and tighten to the specified torque. The tightening torque for R410A is the same as the conventional torque value for R22. Be careful, because if the torque is too weak, it may lead to a gas leak. If it is too strong, it may split the flare nut or make it impossible to remove the flare nut.

Table 15 R410A tightening torque

Nominal

Outside

Tightening torque

Torque wrench tightening torque

diameter

diameter (mm)

N.m (kgf.cm)

N.m (kgf.cm)

1/4

6.35

14 - 18 (140 - 180)

18 (180)

 

 

 

 

3/8

9.52

33 - 42 (330 -420)

42 (420)

1/2

12.70

55 (550)

55 (550)

 

 

 

 

10.3.3. Storing and Managing Piping Materials

1.Types of piping and their storage

The following is a general classification of the refrigerant pipe materials used for ACs.

Because the gas pressure of R410A is approximately 1.6 times as high as that of R22, copper pipes with the thickness shown in Table 10, and with minimal impurities must be used. Care must also be taken during storage to ensure that pipes are not crushed, deformed, or scratched, and that no dust, moisture or other substance enters the pipe interior. When storing sheathed copper pipes or plain copper pipes, seal the openings by pinching or taping them securely.

2.Makings and management

a.Sheathed copper pipes and copper-element pipes

When using these pipes, check to make sure that they are the stipulated thickness. For flare nuts, be sure to used the same nut that is used on the AC unit.

48

Image 48
Contents Contents Features Serviceability ImprovementProduct Environmental ProtectionRemote Control FunctionsAutomatic Operation Switch Indoor UnitOutdoor Unit Product Specifications CS-E15DB4EW CU-E15DBEFPI CS-E18DB4EW CU-E18DBE CS-E18DB4EW CU-E18DBENet Weight Lb kg CS-E21DB4ES CU-E21DBE CS-E21DB4ES CU-E21DBE108 Dimensions Indoor Unit & Remote ControlCS-E15DB4EW CS-E18DB4EW CS-E21DB4ES CU-E15DBE CU-E18DBE CU-E21DBE Refrigeration Cycle Diagram Block Diagram Wiring Diagram Temperature Shifting Flow Operation DetailsBasic Operation Cooling Operation Thermostat control Soft Dry Operation Thermostat controlHeating Operation Thermostat control Automatic Operation Indoor Fan Motor Operation Basic Rotation Speed rpmIndoor Fan Control Heating Ii. Auto Fan Speed Cooling Fan Motor Control Outdoor Fan Motor Operation Deodorizing ControlQuiet operation Cooling Mode/Cooling area of Dry Mode Airflow DirectionVertical Airflow PurposeControl contents Quiet operation HeatingPowerful Mode Operation Hour Real Time Timer ControlOn Timer OFF TimerDrain Pump Error Auto Restart ControlIndication Panel Drain Pump Control OperationProtection Control Features IPM Power transistor Prevention ControlSeconds Forced Operation Total Running Current ControlCompressor Overheating Prevention Control Low Pressure Prevention Control Gas Leakage DetectionLow Frequency Protection Control Control start conditionsCooling Overload Control Anti-Freezing Control Anti-Dew Formation ControlOverload Protection Control Deice Control Operating Instructions Page Page Page Page Page Page Page Installation And Servicing Air Conditioner Using R410A OutlineAbout R410A Refrigerant Tools For Installing/Servicing Refrigerant Piping Necessary Tools10.2.2. R410A Tools Torque wrenchesSensitivity with R410A is about 23 g/year 10.2.3. R410A Tools Which Are Usable for R22 Models Electronic scale for refrigerant chargingProcessing and Connecting Piping Materials Refrigerant Piping WorkPiping Materials Storing and Managing Piping Materials Installation, Transferring, Servicing PrecautionsTransferring Using New Refrigerant Piping AC Units Replacement Using Existing Refrigerant PipingPrecaution Recharging Refrigerant During ServicingBrazing Servicing TipsBrazing Method for Preventing Oxidation Installation Instructions Safety PrecautionsPage Attached accessories Select the best locationOutdoor Unit Page Installation of Indoor Unit Indoor Unit Drain Piping Vacuum dryingHeat Insulation Wall sealConnecting the Cable to the Indoor Page Connecting The Piping To Indoor Unit Connecting The Piping To Outdoor UnitRefer to Select the best location section Cutting and Flaring the PipingEvacuation of the Equipment Auto Switch Operation Disposal of Outdoor Unit Drain WaterChanging the Remote Control Transmission Code REMO-CON NO. Change in Remote ControlCheck Items Hand OverTroubleshooting Servicing InformationRated Frequency Operation Troubleshooting Air Conditioner Refrigeration cycle system Breakdown Self Diagnosis Function Error Codes Table JudgementRemote Control Reset Setting Remote Control Transmission CodeAuto OFF/ON Button Disassembly of Parts Page Outdoor Electronic Controller Removal Procedure Remove the top panel and front panelTechnical Data Operation CharacteristicsCS-E15DB4EW CU-E15DBE CS-E18DB4EW CU-E18DBE CS-E21DB4ES CU-E21DBE Sensible Capacity Chart CS-E15DB4EW CU-E15DBECS-E18DB4EW CU-E18DBE CS-E21DB4ES CU-E21DBEExploded View Indoor Unit CS-E15DB4EW CS-E18DB4EW CS-E21DB4ESPage CZ-BT20E Front Grille Complete Replacement Parts List Indoor Unit REF. no Part Description QTY Front Grille Complete Exploded View Outdoor Unit CU-E15DBE CU-E18DBE CU-E21DBEReplacement Parts List Outdoor Unit Electronic Circuit Diagram CS-E15DB4EW CS-E18DB4EW CS-E21DB4ES Schematic Diagram 1/4Schematic Diagram 2/4 R17Schematic Diagram 3/4 SSR02 SSR01Schematic Diagram 4/4 WHTCU-E15DBE CU-E18DBE CU-E21DBE Schematic Diagram 1/4 FUSE2 IC1 Schematic Diagram YellowHow to use electronic circuit diagram Timer Table IndoorTimer Table Outdoor Remote Control Print Pattern Indoor Unit Printed Circuit Board Print Pattern Outdoor Unit Printed Circuit Board View

CS-E15DB4EW specifications

The Philips CS-E15DB4EW is an exceptional air conditioner that exemplifies modern cooling technology while emphasizing energy efficiency and user comfort. This model is designed to provide reliable performance in various settings, making it suitable for both residential and light commercial applications.

One of the standout features of the Philips CS-E15DB4EW is its powerful cooling capacity. With a cooling power reaching up to 15000 BTUs, this air conditioner is capable of effectively cooling medium to large-sized rooms. This high capacity ensures that users enjoy a refreshingly cool environment, even during the hottest summer months.

Energy efficiency is a prominent characteristic of the CS-E15DB4EW. It features an advanced inverter technology that optimizes power consumption while maintaining the desired temperature. This technology not only results in lower electricity bills but also reduces environmental impact by minimizing energy waste. The air conditioner boasts a high EER (Energy Efficiency Ratio), making it a responsible choice for energy-conscious consumers.

In terms of convenience, the CS-E15DB4EW is equipped with a user-friendly remote control, allowing users to adjust settings from a distance. This includes temperature adjustments, fan speed settings, and timer functions, providing flexibility and comfort at the users' fingertips. Additionally, the air conditioner features various operating modes, including cool, dry, and fan modes, catering to diverse climatic conditions and individual preferences.

Another remarkable characteristic of the Philips CS-E15DB4EW is its quiet operation. With a noise level as low as 30 dB, this unit ensures that users can enjoy a peaceful environment without the disruptive sounds typical of standard air conditioning units. This feature is particularly beneficial for bedrooms or study areas where concentration or relaxation is crucial.

Moreover, the unit is designed with a sleek, modern aesthetic that seamlessly integrates into any interior decor. The easy-to-clean filters and compact design contribute to its practicality, allowing for efficient maintenance and longevity.

In conclusion, the Philips CS-E15DB4EW stands out as a versatile, efficient, and user-friendly air conditioning solution. With its powerful cooling capacity, energy-saving technologies, convenient features, and quiet operation, it effectively addresses the cooling needs of various environments. Whether for residential use or light commercial applications, this model is designed to provide a comfortable atmosphere while being mindful of energy consumption and environmental impact.