Philips AMC 30, AMW, AMC 60, AMC 45, AMC Series Recommended Height and Length, Installation Method

Page 4

RECOMMENDED HEIGHT AND LENGTH

If the refrigerant piping is longer than the recommended length, or if the height difference between the indoor and outdoor unit is greater than recommended, the capacity will drop and the compressor could malfunction. Select an installation location that is within the recommended parameters.

(MAXIMUM PIPING LENGTH & HEIGHT RECOMMENDED)

 

 

Piping length

(feet)

 

50

Notes

 

 

 

 

 

23

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

Installation

Unit

 

 

 

 

 

 

Piping

capacity

Add

 

Not

Needed

 

not

 

 

Diameter

7,500 to

charge

 

needed

(1)

 

recom-

1/4" and

9,000

 

 

 

 

 

 

mended

3/8”

Btuh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended height difference is 23 ft or less *Evacuate refrigerant lines

(1)An installation with a piping length of 23 ft. or less is desirable. If this is not possible, the maximum piping length can be extended to 50 ft. by charging the system with additional refrigerant. However, cooling and heating capacity will be reduced.

INSTALLATION METHOD

HOLE DRILLING: After deciding the method your unit will be installed, a hole to route the connecting tubes and wires to the outdoor unit is to be drilled on the wall. The hole must be lower than the point where the drainpipe attaches to the drain pan of the unit. It should also be slightly declined towards the outside.

Additional charge volume = (piping length - 23 ft.) x 0.2 oz.

 

 

Piping length (feet)

 

 

Notes

 

 

 

33

55

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

Installation

Unit

 

 

 

 

 

 

Piping

capacity

Add

 

Not

 

Needed

 

not

 

 

 

Diameter

18,500 to

charge

 

needed

 

(2)

 

recom-

 

36,000

 

 

 

 

 

 

mended

 

Btuh

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recommended height difference is 23 ft or less *Evacuate refrigerant lines

(2)An installation with a piping length of 33 ft. or less is desirable. If this is not possible, the maximum piping length can be extended to 55 ft. by charging the system with additional refrigerant. However, cooling and heating capacity will be reduced.

Additional charge volume = (piping length - 33 ft.) x 0.2 oz.

Image 4
Contents AMW / AMC Series Safety Considerations Tools and SuppliesIndoor Unit Selection of LocationOutdoor Unit Installation Method Recommended Height and LengthMounting Installation Plate Installation of FAN Coil Mounting Condensing UnitRefrigeration Piping & Drainage Preparation of PipingPiping Insulation Precautions When Bending PipesFlare Fitting CONNECTION. There are 3 piping rules Fan Coil Precautions When Connecting PipesCondensing Units AIR Purging Drain Pipe Connection SlimeElectrical Wiring Wiring ConnectionLocation of Terminal Block External Finishing of PipingOperating Tips Product DescriptionAuxiliary Control Controls and Indicators Remote Control OperationModel AMW 25 Model AMW 45 Operating Instructions Operating Guide Model AMW 25Functions Care and Maintenance END of SeasonAir conditioner does not operate Trouble ShootingCooling is insufficient AMW/AMC AMW/AMC AMW/AMC 45 Service Notes