Page 11

DRAIN PIPE CONNECTION

The fan coil is equipped with a drain hose. It is tied together with the refrigerant piping. During installation, it is important to observe the following instructions to prevent water overflowing from the drain pan.

!Insure that the indoor unit is level and not tilted forwards or backwards.

!Insure that the drain hose does not rise above the drain pan. It should be sloping towards the hole.

!Route the drain hose through the same hole as the refrigerant pipes.

!If the drain pipe extends horizontally a long way, use PVC tubing to provide heat insulation.

!Outside insert the drain hose into a PVC drainpipe and not the other way around and glue them together.

!Run the PVC drainpipe straight down the wall. There should be no traps and avoid putting the end of the pipe into water.

!Ensure that all sections of the PVC pipes are glued securely together.

!Ensure that the entire indoor part of the drain hose is insulated to avoid condensation from dripping.

!Drain pipe may be required for heat pump unit and should be connected if necessary.

SLIME

 

 

 

Downward

 

Down-

Slant

 

 

 

 

ward

 

Drain Pipe

slant

 

 

 

 

 

 

Drain Pipe

 

 

 

• Traps

The lack of a

 

Trap

downward

 

 

slope causes

 

 

water to build

 

 

up and

 

 

 

overflow the

Traps

 

drain pan.

 

 

 

 

 

 

Even if there is a downward slope overall, there must not be any “double traps” formed

• Long Horizontal Extensions

Gap of approximately 50 cm

Good

 

 

Stiff vinyl

Secure in place

chloride (PVC)

with saddles

tubing

No good

Trap effect created

 

Flexible tube

 

Good

 

No good

 

Drain hose

 

Drain water cannot

 

flow freely

Drainage gutter

Drainage gutter

Water leakage due to a clogged drain hose can be caused by accumulated dirt in the drain pan or by a buildup of slime inside the drain hose.

Slime is caused by the following factors:

!Temperature : 25°C (77°F) to 30°C(86°F)

!Accumulated water

!Nutrients (components of perspiration and dust in the air)

!A combination of certain types of mold and bacteria.

To reduce the chance of clogging, it is very important to ensure that the drain hose has a downward slant to prevent water from accumulating and a clean and a well ventilated environment.

Image 11
Contents AMW / AMC Series Tools and Supplies Safety ConsiderationsOutdoor Unit Selection of LocationIndoor Unit Recommended Height and Length Installation MethodMounting Installation Plate Mounting Condensing Unit Installation of FAN CoilPreparation of Piping Refrigeration Piping & DrainageFlare Fitting CONNECTION. There are 3 piping rules Precautions When Bending PipesPiping Insulation Condensing Units Precautions When Connecting PipesFan Coil AIR Purging Slime Drain Pipe ConnectionExternal Finishing of Piping Electrical WiringWiring Connection Location of Terminal BlockProduct Description Operating TipsAuxiliary Control Model AMW 25 Remote Control OperationControls and Indicators Model AMW 45 Operating Guide Model AMW 25 Operating InstructionsFunctions END of Season Care and MaintenanceCooling is insufficient Trouble ShootingAir conditioner does not operate AMW/AMC AMW/AMC AMW/AMC 45 Service Notes