REFRIGERATION PIPING & DRAINAGE

PREPARATION OF PIPING

Fan coil and side discharge condensing units are equipped with flare connections. Improper flaring and brazing may cause refrigerant to leak out of the system. Follow these instructions carefully in preparing the refrigerant piping.

!Ensure that all piping is of the correct size.

!Measure the distance between the indoor and outdoor units' refrigerant connections, together with all the curves necessary. Add a few inches as slack.

!Lay the piping as straight as possible on a flat surface and with a pipe cutter, cut the piping according to the measured length.; Do not tighten the cutter excessively during cutting as this may cause the pipe to deform. Do not use hacksaw or similar tools to cut the pipe, as it results in metal shavings getting inside the pipe. This also makes proper flaring impossible.

!Use a reamer to remove burrs from cut edges. Hold the pipe ends upside down to prevent metal powder from getting into the pipe.

Pipe

Reamer

Note:

As the pipe is round, cutting should be

Pipe cutter

performed on a straight section. Also,

 

do not apply too much force with the

 

blade of the pipe cutter.

 

Keep pipe facing downward when removing burrs.

!For connection to flare settings, the pipe has to be flared. Remove the flare nut from the unit and insert it onto the piping.

!Fit the pipe into the bar of the flare tool, about 0.5 mm higher than the surface of the bar.

!Center the flare punch carefully on the pipe and turn gradually to widen the pipe. Check the finish of the flare to ensure even flaring.

!Cover the flared ends with tape to prevent dust from entering.

 

Handle

 

Flaring tool

 

Flaring bar

 

Length of periphery portion

Flare nut

L should be constant

 

0.635 (1/4”) only

0.952 (3/8”) and larger

Approx. 1 mm

0.5 mm

Image 7
Contents AMW / AMC Series Tools and Supplies Safety ConsiderationsIndoor Unit Selection of LocationOutdoor Unit Recommended Height and Length Installation MethodMounting Installation Plate Mounting Condensing Unit Installation of FAN CoilPreparation of Piping Refrigeration Piping & DrainagePiping Insulation Precautions When Bending PipesFlare Fitting CONNECTION. There are 3 piping rules Fan Coil Precautions When Connecting PipesCondensing Units AIR Purging Slime Drain Pipe ConnectionExternal Finishing of Piping Electrical WiringWiring Connection Location of Terminal BlockProduct Description Operating TipsAuxiliary Control Controls and Indicators Remote Control OperationModel AMW 25 Model AMW 45 Operating Guide Model AMW 25 Operating InstructionsFunctions END of Season Care and MaintenanceAir conditioner does not operate Trouble ShootingCooling is insufficient AMW/AMC AMW/AMC AMW/AMC 45 Service Notes