19 | Turbine Installation |
|
|
|
|
DC Power Wiring
TURBINE POLES
TURBINE TO CONTROLLER WIRE SIZE CHART
TURBINE WIRE | MAX DISTANCE (FT) | EMT CONDUIT (INCH) |
#10 (#6 GND) | 150 | 3/4 |
#8 (#4 GND) | 200 | 1 |
#4 GND
EARTH
GROUND
STAKE
TURBINE JUNCTION BOX
SEE TURBINE TO CONTROLLER SIZE CHART ON SHEET 1
(2) #10 |
¾” CONDUIT |
MAX DISTANCE 3 FEET. |
Figure 2.10 Power Wiring Diagram
Turbine Wiring and Distances
The HONEYWELL™ Wind Turbine and SMARTBOX™ Controller can be installed at a maximum distance of 200 feet apart. The SMARTBOX™ Controller and battery enclosure can be installed at a maximum distance of 10 feet apart.
Turbine Current Rating and Wiring
The turbine input is rated for 20 amps maximum Isc (short circuit). The recommended wire type is #10 AWG
HONEYWELL™ Wind Turbine WT6500 Owner’s Manual - Rev 10