Desa (V)K36EP, (V)K36EN Connecting Fireplace to GAS Supply, Checking GAS Connections

Page 19

FIREPLACE INSTALLATION

Installing Gas Piping to Fireplace Location (Cont.) Connecting Fireplace To Gas Supply Checking Gas Connections

19

FIREPLACE INSTALLATION

Continued

CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in cer- tain areas. Check your local codes. Use pipe of 1/2" inside diameter or greater to allow proper gas volume to fireplace. If pipe is too small, undue loss of volume will occur.

Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from fireplace (see Figure 31).

IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the appliance.

Check your building codes for any special requirements for locating equipment shutoff valve to fireplaces.

Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged fireplace valves.

WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.

We recommend that you install a sediment trap/drip leg in supply line as shown in Figure 31. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping system between fuel supply and fireplace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into fireplace gas con- trols. If sediment trap/drip leg is not installed or is installed wrong, fireplace may not run properly.

CSA Design-Certified

Equipment Shutoff Valve

with 1/8" NPT Tap*

CONNECTING FIREPLACE TO GAS SUPPLY

Installation Items Needed

5/16" hex socket wrench or nut-driver

sealant (resistant to propane/LP gas, not provided)

1.Open lower louver door panel by gently pulling forward.

2.Route flexible gas line (provided by installer) from equipment shutoff valve to fireplace. Route flexible gas supply line through one of the access holes on side of fireplace.

3.Attach flexible gas line from gas supply to control valve (see Figure 32).

4.Check all gas connections for leaks. See Checking Gas Connections.

 

Red Surface Indicates

Equipment

For Propane/LP Use Only

Flexible Gas Line

Shutoff Valve

Do NOT Kink

1/2" NPT Incoming

 

 

Gas Line

Inlet Pressure Tap

Outlet Pressure Tap

 

Note: Wire Connections Not Shown for Clarity

Figure 32 - Connecting Flexible Gas Line to Electronic Valve

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

Approved Flexible

Gas Line

3" Minimum

Natural - From Gas Meter (5.5" W.C. to 10.5"

W.C. Pressure)

Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)

WARNING: Never use an open flame to check for a leak. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1. Disconnect fireplace and its individual equipment shutoff valve

from gas supply piping system. Pressures in excess of 1/2 psig

(3.5 kPa) will damage fireplace gas regulator.

Cap Pipe Nipple Tee Joint

2. Cap off open end of gas pipe where equipment shutoff valve

was connected.

Figure 31 - Gas Connection

Sediment Trap/Drip Leg

3. Pressurize supply piping system by either opening propane/LP

supply tank valve for propane/LP gas fireplace or opening main

*The CSA design-certified equipment shutoff valve may be sup- plied with the appliance or you can purchase it from your retailer.

gas valve located on or near gas meter for natural gas fire-

place, or using compressed air.

For morevisit www..com

111924-01B

Image 19
Contents For Your Safety OWNER’S Operation Installation ManualFor Your Safety What to do if YOU Smell GAS Safety Information Table of ContentsLocal Codes Product IdentificationPRE-INSTALLATION Preparation Product FeaturesLocation and Space Requirements Framing and Finishing ClearancesBalcony with Perpendicular Side Wall Location of Termination CAPInstallation Precautions Venting Installation InstructionsHorizontal Termination Installation Installation PlanningInstalling Siding Standoff Combustible Exterior Vertical V Horizontal H Horizontal Termination ConfigurationsCorner Installation Venting with Two 90 Elbows Horizontal System Installation Using TWO ElbowsFlat Ceiling Installation Installation for Vertical TerminationVenting with One 90 Elbow Vertical Termination ConfigurationsVertical Venting High Altitude Installation Check GAS Type Fireplace Installation Installing Optional Blower Accessory Model BK InstallationAttaching Speed Control to Firebox Model BKT InstallationBlower Wiring Diagram Installing GAS Piping to Fireplace LocationInstallation Items Needed Checking GAS Connections Connecting Fireplace to GAS SupplyInstallation Items Needed Pressure Testing Gas Supply Piping SystemREMOVING/REPLACING Glass Door Pressure Testing Fireplace Gas ConnectionsRemoving Louver Panels Removing Glass Door Cleaning Glass DoorWall Switch Installation Installing LOGS, Lava Rock and Glowing EmbersOptional Remote Control Wiring DiagramTo Turn OFF GAS To Appliance For Your Safety Read Before LightingOperating Fireplace Lighting InstructionsBurner Flame Pattern Operating Optional Blower AccessoryPilot Assembly Inspecting BurnersLogs Cleaning MaintenanceGlass Door Pilot and BurnersObserved Problem Possible Cause Remedy TroubleshootingTop Gas leak. See Warning statement atSpecifications Replacement PartsService Hints Technical ServiceModels Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListBurner Assembly for Models VK36EN, VK36ENH, VK36EP, VK36EPH Parts List Accessories Owners Registration Form Postage Required 111924-01B Warranty Information