Desa CDV37N/P, CDV41N/P installation manual General Venting

Page 6

CDV37N/P(A,B) AND CDV41N/P(A,B)

DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)

GENERAL VENTING Continued

N

N

D

E V

B L

 

C

 

 

Fixed

V

 

Closed

 

 

F

Openable

 

V

 

B

Openable Fixed

Closed

H

V

B

I

G

B

B

V J X

G

A

M

V

K X

V

G V A

V TERMINATION CAP

X AIR SUPPLY INLET

G

GAS METER

 

RESTRICTED AREA (TERMINATION PROHIBITED)

A= clearance above grade, veranda, porch, deck, or balcony [*12 inches (305mm) minimum]

B= clearance to window or door that may be opened

[12 inches (305mm) minimum]

C = clearance to permanently closed window [minimum 12 inches (305mm) recommended to prevent condensation on window]

D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24 inches (610mm) from the center-line of the terminal [18 inches (457mm) minimum]

E= clearance to unventilated soffit [12 inches (305mm) minimum]

F= clearance to outside corner (see below)

G= clearance to inside corner (see below)

H= *not to be installed above a meter/regulator assembly within

36 inches (914mm) horizontally from the center-line of the regulator

I= clearance to service regulator vent outlet [*72 inches (1829mm) minimum]

J= clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [*12 inches (305mm) minimum]

K= clearance to a mechanical air supply inlet [*72 inches (1829mm) minimum]

L= † clearance above paved side-walk or a paved driveway located on public property [*84 inches (2133mm) minimum]

M= clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡]

N= clearance above a roof shall extend a minimum of 24 inches (610mm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 inches (457mm)

† vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings*

‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*

* as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow the current National Fuel Gas Code, ANS Z223.1

Note: Local codes or regulations may require different clearances

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Inside Corner

A

 

A = 6" (152mm)

 

V

Outside Corner

V

B B = 6" (152mm)

Recessed Location

D

C

C

E

V

Balcony with No Side Wall

G

V

G = Combustible 24" (610mm) Noncombustible 18" (457mm)

Balcony with Perpendicular Side Wall

H

V

J

Combustible &

Noncombustible

H = 24" (610mm)

J = 20" (508mm)

C = Maximum depth of 48" (1219mm) for recessed location

D = Minimum width for back wall of recessed location - Combustible - 38" (965mm) Noncombustible - 24" (610mm)

E = Clearance from corner in recessed location- Combustible - 6" (152mm) Noncombustible - 2" (51mm)

Figure 8 - Minimum Clearances for Vent Terminations

6

105541

Image 6
Contents For Your Safety For Your Safety What to do if YOU Smell GASCDV37N/PA,B and CDV41N/PA,B Safety Information DIRECT-VENT Fireplace NATURAL/PROPANE/LPLocal Codes Product FeaturesProduct Identification Glossary TermsLocation and Space Requirements PRE-INSTALLATION PreparationClearances Framing and FinishingPRE-INSTALLATION Preparation General Venting Location of Vent TerminationGeneral Venting Installation Planning Venting InstallationInstallation Precautions Installing Vent System in a ChaseInstallation for Horizontal Termination Snorkel TerminationVent Pipe Connections Horizontal Termination Configurations Horizontal VentingVenting with Two 90 Elbows Installation for Vertical Termination Flat Ceiling InstallationCathedral Ceiling Installation Vertical Termination Configurations Venting with One 90 ElbowVertical Venting Comfort Glow Rigid Venting High Altitude InstallationParts Lists for Venting Kits and Components Comfort Glow Flexible VentingInstalling GA3750/CDA3620T Blowers Fireplace InstallationInstalling Optional Blower Accessory Check GAS TypePlug in blower power cord Installing GAS Piping to Fireplace Location Installation Items NeededConnecting Fireplace to GAS Supply Pressure Testing Gas Supply Piping SystemChecking GAS Connections Pressure Testing Fireplace Gas Connections Close manual shutoff valve see Fig- ureInstalling 9-Volt Battery in Hand- Held Remote Control Unit Wireless HAND-HELD Remote ControlInstalling Battery into Receiver REMOVING/REPLACING Glass DoorInstalling Optional Brick Liner CD8037A/ CD8041 Attaching Magnetic Decorative Brass StripsInstalling LOGS, Lava Rock and Glowing Embers Replace glass door. See Removing/Re- placing Glass Door,Operating Fireplace For Your Safety Read Before LightingManual Lighting Procedure Lighting InstructionsInspecting Burners Operating Optional Blower AccessoryPilot Assembly HAND-HELD Remote OperationPilot and Burners Cleaning and MaintenanceGlass Door LogsTroubleshooting Observed Problem Possible CauseObserved Problem Possible Cause Remedy Gas leak. See Warning statement Service Hints Replacement PartsWiring Diagram Technical ServiceTHERMOSTATICALLY- Controlled Blower KIT CDA3620T SpecificationsAccessories Manual Blower KIT GA3750Illustrated Parts Breakdown CDV41NA,BParts List DIRECT-VENT Fireplace CDV37NA,B CDV41NA,BCDV37PA,B CDV41PA,B DIRECT-VENT Fireplace CDV37PA,B CDV41PA,B Warranty Information