Desa LMFP33PR Installing GAS Piping to Fireplace Location, Installation Items Needed

Page 12

12

INSTALLATION

Built-In Fireplace Installation (Cont.) Installing Gas Piping to Fireplace Location

INSTALLATION

Continued

Mantel Clearances for Built-In Installation

If placing mantel above built-in fireplace, you must meet minimum clearance between mantel shelf and top of fireplace opening.

NOTICE: If your installation does not meet the mini- mum clearances shown, you must do one of the following:

raise the mantel to an acceptable height

remove the mantel

NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.

INSTALLING GAS PIPING TO FIREPLACE LOCATION

WARNING: This appliance requires a 1/2" NPT (National Pipe Thread) inlet connection to the pres- sure regulator.

WARNING: A qualified service person must con- nect fireplace to gas supply. Follow all local codes.

CAUTION: Never connect propane/LP fireplace directly to the propane/LP supply. This fireplace requires an external regulator (not supplied). Install the external regulator between the fireplace and pro- pane/LP supply.

Wall board or facing material (above firebox) may be of

Mantel Shelf

WARNING: Never connect natural gas fireplace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

combustible material, including decorative mantel ornaments or other similar projec- tions off of the facing material.

Framing

Material

Firebox

Wire-mesh

Screen

10"

8"

6"

21/2"

Noncombustible Material May Project Off this Surface above the Firebox Hood

Supplied Firebox

Hood Must Be

Used at All Times

13" 16" 19" 21"

Note: All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf.

These minimum clearances replace any other recommended clearances supplied with your ANSI Z21.11.2 approved gas logs.

Installation Items Needed

Before installing fireplace, make sure you have the items listed below.

external regulator for propane/LP unit only (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

equipment shutoff valve *

test gauge connection *

sediment trap (optional)

tee joint

pipe wrench

approved flexible gas line with gas connector (if allowed by lo- cal codes) (not provided)

*A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 30.

Figure 20 - Minimum Mantel Clearances for Built-In Installation

For propane/LP units, the installer must supply an external regula- tor. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent point- ing down as shown in Figure 21, page 13. Pointing the vent down protects it from freezing rain or sleet.

For..com

111604-01B

Image 12 Contents
OWNER’S Operation and Installation Manual What to do if YOU Smell GASTable of Contents Safety InformationLog Base Assembly Product IdentificationProduct Features Local CodesUnpacking AIR for Combustion and VentilationProviding Adequate Ventilation Determining FRESH-AIR Flow for Heater LocationUnusually Tight Construction Confined and Unconfined SpaceVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Installation Installing HoodCheck GAS Type Electrical Hookup Installation Clearances Included with Mantel Accessory Assembling and Attaching Optional Brass Trim Conventional Fireplace Installation Installing Cabinet MantelBUILT-IN Fireplace Installation Actual Framing Height 32 3 Front Width DepthSupport Bracket Firebox Wrapper Shield Power Screws Cord Installing GAS Piping to Fireplace Location Mantel Clearances for Built-In InstallationInstallation Items Needed Connecting Fireplace to GAS Supply Gas ConnectionPressure Testing gas Supply Piping system Checking GAS ConnectionsPressure Testing Fireplace Gas Connections Check all other internal joints for leaksInstalling Logs Installing Logs 1For Your Safety Read Before Lighting Installing Batteries in ReceiverInstalling Battery into Remote Operating HeaterManual Lighting Procedure To Turn OFF GAS To ApplianceShutting Off Heater Shutting Off Burners Only pilot stays litHAND-HELD Remote Operation Inspecting Burners Pilot Flame PatternBurner Primary AIR Holes Main BurnerCleaning Maintenance Cleaning Burner Injector Holder and Pilot AIR Inlet HoleLogs Troubleshooting Observed Problem Possible Cause RemedyMaintenance, Gas leak. See Warning statement Wiring Diagram SpecificationsTechnical Service Service HintsIllustrated Parts Breakdown Models LMFP33PRParts List KEY Part Number LMFP33PR LMFP33NR Description QTYFirebox LMFP33PR LMFP33NR Firebox LMFP33PR and LMFP33NR KEY Part Number Description QTYAccessories Blower Accessory GA3750A GA3700TA SeriesEquipment Shutoff Valve GA5010 Information VideoOwners Registration Form Postage Required 111604-01B Warranty Information