AIR FOR COMBUSTION AND VENTILATION

Providing Adequate Ventilation Determining Fresh-Air Flow for Heater Location

5

AIR FOR COMBUSTION AND VENTILATION

Continued

PROVIDING ADEQUATE VENTILATION

The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.

All spaces in homes fall into one of the three following ventilation classifications:

1.Unusually Tight Construction

2.Unconfined Space

3.Confined Space

The information on pages 4 through 6 will help you classify your space and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:

a.walls and ceilings exposed to the outside atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10-11kg per pa-sec-m2) or less with openings gasketed or sealed and

b.weather stripping has been added on openable win- dows and doors and

c.caulking or sealants are applied to areas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.

If your home meets all of the three criteria above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 6.

If your home does not meet all of the three criteria above, proceed to Determining Fresh-Air Flow For Heater Loca- tion, column 2.

Confined and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the unconfined space.

*Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height). Length x Width x Height = ___________ cu. ft. (volume of space)

Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or open- ings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maximum Btu/Hr the space

can support)

Example: 2,560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

 

_____________ Btu/Hr

Gas water heater*

 

_____________ Btu/Hr

Gas furnace

 

_____________ Btu/Hr

Vented gas heater

 

_____________ Btu/Hr

Gas fireplace logs

 

_____________ Btu/Hr

Other gas appliances* +

_____________ Btu/Hr

Total

=

_____________ Btu/Hr

*Do not include direct-vent gas appliances. Direct-vent draws com- bustion air from the outdoors and vents to the outdoors.

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

33,000

Btu/Hr

Total

=

73,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________________ Btu/Hr (maximum the space can support)

__________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

For morevisit www..com

111604-01B

Image 5
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualSafety Information Table of ContentsProduct Identification Log Base AssemblyLocal Codes Product FeaturesUnpacking AIR for Combustion and VentilationDetermining FRESH-AIR Flow for Heater Location Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceVentilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installing Hood InstallationCheck GAS Type Electrical HookupAssembling and Attaching Optional Brass Trim Installation ClearancesIncluded with Mantel Accessory Installing Cabinet Mantel Conventional Fireplace InstallationActual Framing Height 32 3 Front Width Depth BUILT-IN Fireplace InstallationSupport Bracket Firebox Wrapper Shield Power Screws Cord Installation Items Needed Installing GAS Piping to Fireplace LocationMantel Clearances for Built-In Installation Gas Connection Connecting Fireplace to GAS SupplyChecking GAS Connections Pressure Testing gas Supply Piping systemCheck all other internal joints for leaks Pressure Testing Fireplace Gas ConnectionsInstalling Logs 1 Installing LogsInstalling Batteries in Receiver For Your Safety Read Before LightingInstalling Battery into Remote Operating HeaterTo Turn OFF GAS To Appliance Manual Lighting ProcedureShutting Off Heater Shutting Off Burners Only pilot stays litHAND-HELD Remote Operation Pilot Flame Pattern Inspecting BurnersBurner Primary AIR Holes Main BurnerLogs Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Observed Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement Specifications Wiring DiagramTechnical Service Service HintsModels LMFP33PR Illustrated Parts BreakdownKEY Part Number LMFP33PR LMFP33NR Description QTY Parts ListFirebox LMFP33PR LMFP33NR KEY Part Number Description QTY Firebox LMFP33PR and LMFP33NRBlower Accessory GA3750A GA3700TA Series AccessoriesEquipment Shutoff Valve GA5010 Information VideoOwners Registration Form Postage Required 111604-01B Warranty Information

LMFP33PR specifications

Desa LMFP33PR is an advanced multipurpose electronic system that has gained attention for its impressive range of features and robust performance. Designed to cater to both commercial and residential applications, this device brings a blend of efficiency, flexibility, and user-friendliness to various tasks.

One of the standout features of the Desa LMFP33PR is its high power output, making it suitable for demanding applications. With a maximum wattage capacity that outstrips many competitors in its category, this device can handle significant loads, making it an ideal choice for businesses that require reliable energy sources. Its ability to support multiple devices simultaneously ensures that users can optimize productivity without compromising on performance.

In terms of technology, the Desa LMFP33PR incorporates innovative energy management systems. The integrated smart technology allows users to monitor energy consumption in real-time, offering insights into usage patterns. This can lead to informed decisions regarding energy use, ultimately resulting in cost savings and operational efficiency. Furthermore, the device is equipped with advanced safety features, including overload protection and surge suppression, which safeguards both the unit and connected devices.

The build quality of the Desa LMFP33PR is another aspect worth highlighting. Constructed from durable materials, it is designed to withstand the rigors of frequent use, making it ideal for environments where reliability is paramount. The compact design ensures that it can fit into various spaces without occupying too much physical room, a feature especially appreciated in busy work settings.

User experience is enhanced by an intuitive interface that simplifies operation. The inclusion of programmable settings allows users to customize its functionality according to their specific needs, adding a layer of convenience. Additionally, the Desa LMFP33PR is designed to be energy-efficient, aligning with the growing demand for sustainable solutions. By minimizing energy waste, this device contributes to environmentally friendly operations.

Finally, with customer support and service options readily available, users can access assistance whenever needed, ensuring a seamless experience throughout the lifecycle of the product. In conclusion, the Desa LMFP33PR stands out as a versatile and efficient solution for anyone in need of reliable electric management systems, combining power, durability, and smart technology in one package.