AIR FOR COMBUSTION

AND VENTILATION

Continued

Example:

 

30,000

 

Gas water heater

 

Btu/Hr

Vent-free fireplace

+

10,000

Btu/Hr

Total

=

40,000

Btu/Hr

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

__________ Btu/Hr (maximum the space can support)

__________ Btu/Hr (actual amount of Btu/Hr used) Example: 35,840 Btu/Hr (maximum the space

can support)

40,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the fireplace may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see option 3, Figure 4). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

 

 

12"

Ventilation

 

Ventilation Grills

Grills

 

Into Adjoining

Or

Into Adjoining Room,

Room,

Option 2

Remove

Option 1

 

Door into

 

 

 

 

Adjoining

 

 

Room,

 

 

Option

 

 

3

 

12"

Figure 4 - Ventilation Air from Inside

Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

Attic

 

Air

 

 

Outlet

 

 

Air

 

To Attic

 

 

 

 

To

 

 

Crawl

Inlet

 

Space

 

 

Air

 

 

 

Inlet Air

Ventilated

 

Crawl Space

 

 

Figure 5 - Ventilation Air from Outdoors

www.desatech.com116526-01B

Image 8
Contents Vdcfrpb and Vdcfrnb Shown with Optional Cabinet Mantel/Hearth Base AccessoryThermostat Models Vdcftnb and Vdcftpb Remote-Ready Models Table of Contents Safety Information Safety Information Optional Remote Control Accessories Product Features Product Identification Local CodesHood Assembly Air for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location AIR for Combustion VentilationProviding Adequate Ventilation Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Installation Check GAS TypeInstallation Installation ItemsFireplace Clearances Minimum Clearance to Combustible MaterialsBuilt-In Fireplace Installation Actual Framing HeightFront Width DepthOptional Mantel Installation Mantel ShelfSide of Firebox Top Louver Bottom LouverInstalling Optional Blower Accessory GA3450TA Removing Upper LouverOpen lower louver door by swinging door down see , Installing Blower AccessoryRemote Blower Bracket Switch Plate Screw Blower Bracket For Built-In InstallationExtension Cord Connecting to GAS Supply Checking GAS Connections Connecting equipment shutoff valve to heater controlInstallation Items Needed Pressure Testing Fireplace Gas Connections Equipment Open Shutoff Valve ClosedGas Regulator or Gas Control Valve Equipment Gas MeterInstalling 9-Volt Battery in Hand-Held Remote Control Unit Installing ReceiverReceiver Volt Terminal Battery Wires Battery Clip Optional Wall Switch GWMS2 Remote-Ready Models Only Control Valve To Wall Thermostat or SwitchFeed wires through rectangular slots Terminal W Terminal RInstalling LOG SET and Screen For Your Safety Read Before LightingOperating Fireplace Lighting InstructionsManual Lighting Procedure Operating FireplaceTo Turn OFF GAS To Appliance Thermostat Control OperationAUTO/OFF/ON Switch Operating BlowerPilot Burner Ignitor Electrode Piezo Flame Control Ignitor Button Adjustment KnobPilot Ignitor Burner Electrode Optional Hand-Held Remote OperationThermostat Series Model HRC200Optional GWMS2 Wall Mounted Switch Optional GWMT1 Wall mounted ThermostatCleaning Maintenance Inspecting BurnersPilot Flame Pattern Burner Flame PatternCleaning Maintenance Wiring DiagramLOG Set CabinetTroubleshooting Observed Problem Possible Cause RemedyTroubleshooting When heated, vapors from Mote-Ready Models Only Power is lowSlight smoke or odor during Initial operation Processes and log curingGas leak. See Warning Specifications Thermostat Models Remote-Ready ModelsRating Variable 17,000/30,000 Btu/Hr Rating Variable 17,000/26,000 Btu/HrIllustrated Parts Breakdown Firebox Models VDCParts List Outer Casing TopBaffle Outer CasingVdcftpb and Vdcftnb Illustrated Parts BreakdownThermostat Models Parts List REMOTE-READY Models Vdcfrnb and VdcfrpbBrass Flare Adapter Fitting THERMOSTAT-CONTROLLED Blower KIT GA3450T AccessoriesEquipment Shutoff Valve GA5010 WALL-MOUNT Thermostat AccessoriesWALL-MOUNT ON/OFF Switch Replacement Parts Service HintsTechnical Service Parts Under Warranty116526-01B Limited Warranty VENT-FREE Compact Classic Hearth Warranty InformationKeep this Warranty