Cal Flame LTR20091006 manual Installation Assembly

Page 10

8

Installation Assembly/

2)Having at least two ventilation openings at cylinder valve level in the side wall, equally sized, spaced at 180 degrees (3.14 rad), and unobstructed. Make sure each opening has a total free area of not less then ½ square inch per pound (3.2 sq. cm/kg) of stored fuel capacity and not less then a total free area of 10 square inches (64.5 sq. cm).

Ventilation openings need to be provided at floor level with a total free area of ½ inch per pound (3.2 sq. cm/k) of stored fuel capacity and not less than a total free area of 10 square inches if the ventila- tion openings at floor level are in a side wall, make sure there are at least two openings. The bottom of the openings shall be at floor level and the upper edge no more than 5 inches (127 mm) above the floor. The openings need to be equally sized, spaced at 180 degrees (3014 rad) and unobstructed.

Make sure every opening has minimum dimensions to permit the entrance of a 1/8 inch (3.2mm) diameter rod.

There shall be a minimum clearance of 2 inches (40.8mm) between the lower surface of the floor and the LP gas supply cylinder enclosure and the ground.

Check the rating plate to make sure the gas supply you are hooking up to is the gas type the firepit or fireplace is manufactured for.

If you do not have an updated filler valve on your existing propane tank, you will need to purchase one at your local hardware store, as you will not be allowed to refill the tank at any filling station.

Use the pressure regulator and hose assembly supplied with LP mod- els. Replacement pressure regulator and hose assemblies must be those specified in this manual.

The 20 lb LP gas cylinder used must include a collar to protect the cylinder valve.

Be certain to mount or set the 20 lb LP gas cylinder on a flat surface and restrain it to prevent it from tipping.

2009 Fireplaces and Firepits

www.calspas.com

LTR20091006, Rev. B

Image 10
Contents Page Maintenance Appendix InstallationOperation Safety Instructions Placement and LocationSet-Up Maintenance and Repair Precautions Regarding Children StorageInstallation LocationLeak Testing Procedure Liquid Propane LP RequirementsInstallation Assembly Connection Installation Natural GasFireplace Burner Installation Installation Assembly Fire Pit Burner Installation Installation Assembly Fireplace Log Set Placement Fire on Ice Glass Placement High Elevation Installation Natural Gas ConversionInstallation Assembly For your safety, read before lighting OperationUsing GrillYour Lighting Instructions for Automatic StarterWhat To Do If You Smell Gas To Turn Off GasLighting Your Wood Burning Fireplace Maintenance Appendix Replacement PartsFireplace Parts Firepit Parts Specifications Fireplace SpecificationsWarranty Warranty Conditions and LimitationsWarranty Exclusions Fireplaces and Firepits Contact Information