Trane PKGP-PRC001-EN manual Cooling Capacity, Heating Capacity, Step

Page 10

Selection Procedures

Cooling Capacity

Step 1

Calculate the building’s total and sensible cooling loads at design conditions. Use theTranecalculation form or any other standard accepted method.

Step 2

Given the following building requirements:

A

Electrical Characteristics: 460/60/3

B

Summer Design Conditions:

Entering Evaporator Coil: 80 DB/ 67WB

Outdoor Ambient: 95 DB

C

Total Cooling Load: 172 MBh

D

Sensible Cooling Load: 122 MBh

E

Airflow: 6000 cfm

F

External Static Pressure: .50 in. w.g.

G

Rooftop - downflow configuration.

H Accessories Economizer Supplementary Electric Heat

I

Heating Capacity 88 MBh

460 volt/3 phase Electric Supplemental Heat - at 6000 cfm

Size the equipment usingTable PD-3.

As a starting point, a rough determination of the size of the unit must be made.This selection will then be confirmed after examining the performance at the given conditions. Divide the total cooling load by nominal BTUH per ton (12 MBh per ton); then round up to the nearest unit size.

172 MBh/12 MBh = 14.33 (approx. 15 tons.)

Step 3

Table PD-3 shows that a WCD180B4 has a gross cooling capacity of 183.0 MBh and 129.0 MBh sensible capacity at 95 degree ambient and 6000 cfm with 80 DB/67 WB air entering the evaporator.

To Find Capacity at Intermediate Conditions

When the design conditions are between two numbers that are in the capacity table, interpolation is required to approximate the capacity.

Note: Extrapolation outside of the table conditions is not recommended.

Step 4

Verify that there will be enough capacity by determining net capacity. In order to select the correct unit which meets the building’s requirements, the fan motor heat must be deducted from the gross cooling capacity.The amount of heat that the fan motor generates is dependent on the effort by the motor cfm and static pressure.To determine the total unit static pressure, add the following:

External Static: 0.50 in.

Standard Filter 1 in: 0.11 in. (from table PD-13)

Economizer Return Air: 0.04 in. (from table PD-13)

Electric Heater Size 18 kW: .06 in.

Total Static Pressure: .71 in.

Note:The Evaporator Fan Performance Table PD-7 has already accounted for the pressure drop for standard filters and wet coils.

Therefore, the actual Total Static Pressure is .71 - .11 = .60.

With 6000 cfm and .60 inches,Table PD-7 shows 2.66 Bhp.

The note below Table PD-7 gives a formula to calculate Fan Motor Heat:

3.15x bhp = MBh

3.15x 2.66 = 8.38 MBh

Now subtracting the fan motor heat from the gross cooling capacity of the unit:

NetTotal Cooling Capacity =

183-8.38=170.62

Net Sensible Cooling Capacity=

129-8.38=120.62

Step 5

If the performance will not meet the required load of the building, try a selection at the next higher size unit.

Heating Capacity

Step 1

Calculate the building heating load using theTrane calculation form or other standard accepted method.

Step 2

Size the equipment usingTable PD-16 to match the heating loads at design conditions.

A

Total Heating Load: 88 MBh

B

Outdoor Ambient (Winter) 17 DB

C

Indoor ReturnTemperature: 70 DB

D

Airflow: 6000 Cfm

Use the integrated portion of Table PD-16 for the WCD180B4 to determine capacity at winter design conditions.The mechanical heating portion of the heat pump will provide 45 MBh.

Step 3

Because 45 MBh is less than the building’s required heating capacity at winter design conditions, a supplementary heater must be selected.

88 MBh - 45 MBh = 43 MBh

FromTable PD-20, at 480 volts, the 18 kW Heater will be adequate to do the job.

18 kW 61 MBh

FromTable ED-3 select heater AYDHTRK418A (18 kW 460/60/3).

10

PKGP-PRC001-EN

Image 10
Contents Packaged Heat Pumps Packaged Rooftop Air Conditioners IntroductionContents Factory Installed Options Field Installed Options Features BenefitsFactory or Field Installed Options Easy to Install, Service and Maintain Features and BenefitsQuality and Reliability Power Exhaust Option Clogged Filter/Fan Failure SwitchColoredAnd NumberedWiring Quick-Access PanelsRigorous Testing Easy to Install and Service Added EfficiencyCondensate Trap Power Exhaust AccessoryBarometric Relief Clearance RequirementsStep Cooling CapacityHeating Capacity To Find Capacity at Intermediate ConditionsModel Number Description Digits 9, 10 Factory Installed OptionsCapacity MBh Table GD-1 General Data GeneralData12½Ton EER2General Data Table GD-2 General DataPerformance MBH SHC MBH SHC MBH SHCWC*180B Data15TonMBH SHC Three Phase WCD240B Data20TonBHP Table PD-6 Evaporator Fan Performance 12½ Ton WC*150BBHP RPM Table PD-8 Evaporator Fan Performance 15 Ton WCH180B Table PD-7 Evaporator Fan Performance 15 Ton WCD180BCFM RPM BHP Table PD-9 Evaporator Fan Performance 20 Ton WC*240B RPM BHPTable PD-10 Standard Motor & Drive/Fan Speed RPM Data12½ 20TonsTable PD-12 Oversized Motor & Drive/Fan Speed RPM WCD240B WCH240BData12½Ton Data15Ton Data20Ton Table PD-19- Heating Capacity Correction Factors Table PD-20 Auxiliary Electric Heat CapacityField Installed Control Options ControlsElectrical Data Table ED-1 Unit WiringRPM FLA LRA 208/230 Volts Three Phase Volts Three Phase AYDHTRKW54A AYDHTRKW18AWCD150BW AYDHTRKW36A AYHHTRNW18AFLA LRA RPM RLA LRA Disconnect Switch Byothers Zonesensors Rooftop Unit Zone Sensors -Typical Number Of WiresJobsite Connections Wiring 12½ 20Tons TypicalWiring 12½ 20Tons Wiring 12½ 20Tons Wiring 12½ 20Tons 12½, 15Ton Dimensional DataDownflow Unit Clearance Downflow Duct Connections Field Fabricated Horizontal Unit Supply/Return and Unit ClearanceDimensional 19 5/16 73 7/16 26 5/16 Dimensional 12½ 20Tons DataAccessories Table DD-1Options Fiops Table DD-2Options Fiops Table DD-3 12½-20 Tons Table W-1 Accessory Net Weights Lbs Weights 12½ 20TonsTable W-1 Weights 12½ 20Tons Mechanical Specifications High Pressure Cutout Factory Installed OptionsTwo-Inch Pleated Filters Frostat Factory or Field Installed OptionsEconomizer Downflow Reference or Comparative EnthalpyManual Outside Air Damper Field Installed OptionsPowered Exhaust Roof Curb DownflowTrane

PKGP-PRC001-EN specifications

The Trane PKGP-PRC001-EN is a highly efficient and versatile rooftop packaged unit designed for commercial HVAC applications. This advanced system showcases Trane's commitment to quality, reliability, and energy efficiency while catering to a diverse range of climate control needs. Its innovative technologies and features make it a top choice for building owners and facility managers looking to enhance indoor comfort while minimizing energy costs.

One of the standout characteristics of the PKGP-PRC001-EN is its impressive cooling and heating capacities, which ensure optimal performance in various conditions. This unit is equipped with advanced scroll compressors that provide efficient cooling and heating, enabling it to maintain a comfortable environment even during extreme temperature fluctuations. The unit also features a multi-position design, allowing for easy installation and adaptation to different rooftop configurations.

In terms of energy efficiency, the PKGP-PRC001-EN excels with its high Seasonal Energy Efficiency Ratio (SEER) and Energy Efficiency Ratio (EER) ratings. These ratings signify its ability to deliver exceptional cooling performance while consuming less energy, ultimately lowering operational costs for facility owners. Additionally, the unit complies with the latest energy standards, including ASHRAE 90.1 and DOE regulations, further emphasizing its commitment to sustainability.

Another notable feature is its advanced control system. The PKGP-PRC001-EN comes equipped with Trane's proprietary Tracerâ„¢ controls that provide precise temperature and humidity management. These controls are user-friendly, allowing for easy programming and monitoring of the system's performance. Furthermore, the unit can be integrated with building management systems (BMS), offering greater control and efficiency.

The design of the PKGP-PRC001-EN also emphasizes durability and ease of maintenance. Constructed with high-quality materials, this unit withstands harsh environmental conditions while minimizing wear and tear over time. Access panels and a structured layout allow for straightforward maintenance, ensuring that service and repairs can be conducted quickly and efficiently.

In summary, the Trane PKGP-PRC001-EN is more than just an HVAC unit; it is a comprehensive solution for efficient heating and cooling in commercial settings. With its cutting-edge technologies, energy-efficient performance, and user-friendly control capabilities, this rooftop packaged unit is an excellent choice for those looking to optimize their HVAC operations while embracing sustainability and reliability.