Trane PKGP-PRC001-EN manual Data12½Ton

Page 22

Performance

Data(12½Ton)

Table PD-14 — 12½ Ton Downflow Three Phase Heating Capacities (Net) WCD150B3, B4, BW at 5000 CFM

Outdoor

Integrated Heating Capacity (MBh/1000)

 

Total Power in Kilowatts At

At Indicated Indoor Dry Bulb Temp.

Indicated Indoor Dry Bulb Temp.

Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F.

60

70

75

80

60

70

75

80

 

-8

51.9

50.3

49.6

49

9.56

10.37

10.83

11.32

 

-3

56.8

55.3

54.6

54

9.61

10.45

10.92

11.42

 

2

62.1

60.7

60

59.4

9.74

10.55

11.03

11.53

 

7

67.9

66.4

65.7

65.1

9.85

10.72

11.2

11.71

 

12

74.1

72.6

71.9

71.1

9.98

10.87

11.36

11.88

 

17

80.7

79.1

78.3

77.6

10.13

11.03

11.53

12.06

 

22

87.8

86

85.1

84.3

10.3

11.22

11.72

12.26

 

27

95.3

93.3

92.3

91.4

10.48

11.41

11.92

12.48

 

32

103.2

101

99.9

98.9

10.68

11.62

12.14

12.7

 

37

111.1

108.6

107.4

106.3

10.89

11.84

12.37

12.94

 

42

119.2

116.4

115.1

113.9

11.11

12.07

12.61

13.18

 

47

138.6

135.3

133.8

132.3

11.93

12.96

13.53

14.14

 

52

148.1

144.5

142.9

141.2

12.2

13.25

13.83

14.43

 

57

155.6

151.4

149.4

147.4

12.46

13.49

14.06

14.67

 

62

168.8

164.2

161.9

159.7

12.8

13.86

14.43

15.04

 

67

179.3

174.3

171.8

169.4

13.17

14.24

14.82

15.44

 

72

189.9

184.5

181.8

179.1

13.55

14.64

15.23

15.85

 

For other airflow conditions, see heating capacity correction factor (Table PD-19).

Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .35 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

Heating capacities and powers are integrated to include the effects of defrost in the frost region. All heating capacities and power (kW) are at 70% OD relative humidity.

Table PD-15— 12½ Ton Horizontal Three Phase Heating Capacities (Net) WCH150B3, B4, BW at 5000 CFM

Outdoor

Integrated Heating Capacity (MBh/1000)

 

Total Power in Kilowatts At

At Indicated Indoor Dry Bulb Temp.

Indicated Indoor Dry Bulb Temp.

Temp.

 

 

 

 

 

 

 

 

 

 

F.

60

70

75

80

60

70

75

80

 

-8

48.2

46.6

46

45.4

9.18

9.96

10.4

10.87

 

-3

52.7

51.3

50.6

50

9.23

10.03

10.48

10.96

 

2

57.7

56.3

55.7

55.1

9.35

10.13

10.58

11.07

 

7

63.1

61.7

61.1

60.4

9.46

10.29

10.75

11.24

 

12

68.9

67.5

66.8

66.1

9.58

10.43

10.9

11.4

 

17

75.2

73.6

72.9

72.1

9.73

10.59

11.07

11.58

 

22

81.8

80.1

79.3

78.4

9.88

10.77

11.25

11.77

 

27

88.9

87

86

85.1

10.06

10.96

11.45

11.98

 

32

96.3

94.2

93.1

92.1

10.25

11.16

11.66

12.2

 

37

103.7

101.4

100.2

99.1

10.45

11.37

11.88

12.42

 

42

111.3

108.7

107.5

106.3

10.67

11.6

12.11

12.66

 

47

137.3

133.9

132.4

130.9

11.53

12.52

13.07

13.66

 

52

146.8

143.1

141.4

139.8

11.8

12.8

13.36

13.96

 

57

154.4

150.1

148.1

146.1

12.04

13.04

13.6

14.19

 

62

167.7

162.9

160.7

158.4

12.37

13.39

13.95

14.55

 

67

178.1

173.1

170.6

168.2

12.72

13.76

14.33

14.93

 

72

188.8

183.4

180.7

178

13.1

14.15

14.73

15.33

 

For other airflow conditions, see heating capacity correction factor (Table PD-19).

Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .40 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.

Heating capacities and powers are integrated to include the effects of defrost in the frost region. All heating capacities and power (kW) are at 70% OD relative humidity.

22

PKGP-PRC001-EN

Image 22
Contents Packaged Heat Pumps Packaged Rooftop Air Conditioners IntroductionContents Factory Installed Options Field Installed Options Features BenefitsFactory or Field Installed Options Easy to Install, Service and Maintain Features and BenefitsQuality and Reliability Power Exhaust Option Clogged Filter/Fan Failure SwitchColoredAnd NumberedWiring Quick-Access PanelsRigorous Testing Easy to Install and Service Added EfficiencyCondensate Trap Power Exhaust AccessoryBarometric Relief Clearance RequirementsStep Cooling CapacityHeating Capacity To Find Capacity at Intermediate ConditionsModel Number Description Digits 9, 10 Factory Installed OptionsCapacity MBh Table GD-1 General Data GeneralData12½Ton EER2General Data Table GD-2 General DataPerformance MBH SHC MBH SHC MBH SHCWC*180B Data15TonMBH SHC Three Phase WCD240B Data20TonBHP Table PD-6 Evaporator Fan Performance 12½ Ton WC*150BBHP RPM Table PD-8 Evaporator Fan Performance 15 Ton WCH180B Table PD-7 Evaporator Fan Performance 15 Ton WCD180BCFM RPM BHP Table PD-9 Evaporator Fan Performance 20 Ton WC*240B RPM BHPTable PD-10 Standard Motor & Drive/Fan Speed RPM Data12½ 20TonsTable PD-12 Oversized Motor & Drive/Fan Speed RPM WCD240B WCH240BData12½Ton Data15Ton Data20Ton Table PD-19- Heating Capacity Correction Factors Table PD-20 Auxiliary Electric Heat CapacityField Installed Control Options ControlsElectrical Data Table ED-1 Unit WiringRPM FLA LRA 208/230 Volts Three Phase Volts Three Phase AYDHTRKW54A AYDHTRKW18AWCD150BW AYDHTRKW36A AYHHTRNW18AFLA LRA RPM RLA LRA Disconnect Switch Byothers Zonesensors Rooftop Unit Zone Sensors -Typical Number Of WiresJobsite Connections Wiring 12½ 20Tons TypicalWiring 12½ 20Tons Wiring 12½ 20Tons Wiring 12½ 20Tons 12½, 15Ton Dimensional DataDownflow Unit Clearance Downflow Duct Connections Field Fabricated Horizontal Unit Supply/Return and Unit ClearanceDimensional 19 5/16 73 7/16 26 5/16 Dimensional 12½ 20Tons DataAccessories Table DD-1Options Fiops Table DD-2Options Fiops Table DD-3 12½-20 Tons Table W-1 Accessory Net Weights Lbs Weights 12½ 20TonsTable W-1 Weights 12½ 20Tons Mechanical Specifications High Pressure Cutout Factory Installed OptionsTwo-Inch Pleated Filters Frostat Factory or Field Installed OptionsEconomizer Downflow Reference or Comparative EnthalpyManual Outside Air Damper Field Installed OptionsPowered Exhaust Roof Curb DownflowTrane