Electrical
Data
Table ED-1 — Unit Wiring
|
|
| Standard Indoor Fan Motor |
| Oversize Indoor Fan Motor |
| ||
|
| Unit | Minimum | Maximum Fuse Size | Minimum | Maximum Fuse Size | ||
| Unit | Operating | Circuit | orMaximum | Circuit | orMaximum | ||
Tons | Model No. | VoltageRange | Ampacity | Circuit Breaker1 | Ampacity | Circuit Breaker1 | ||
| WC*150B3 | 66.0 | 80 |
| 72.0 | 80 |
| |
12½ | WC*150B4 | 31.0 | 40 |
| 34.0 | 40 |
| |
| WC*150BW | 25.0 | 30 |
| 28.0 | 35 |
| |
|
|
|
|
|
|
|
|
|
| WC*180B3 | 76.0 | 90 |
| 82.0 | 100 |
| |
15 | WC*180B4 | 39.0 | 45 |
| 42.0 | 50 |
| |
| WC*180BW | 31.0 | 35 |
| 33.0 | 40 |
| |
|
|
|
|
|
|
|
|
|
| WC*240B3 | 96.0 | 125 |
| 103.0 | 125 |
| |
20 | WC*240B4 | 49.0 | 60 |
| 53.0 | 60 |
| |
| WC*240BW | 38.0 | 45 |
| 41.0 | 50 |
| |
|
|
|
|
|
|
|
|
|
Note:
1. HACR type circuit breaker per NEC.
Table
|
|
| Accessory |
|
|
| Amps |
|
|
|
| Operating |
|
|
|
| |
|
|
|
|
|
|
|
| |
| Tons |
| Voltage | Phase | HP | RPM | FLA | LRA |
|
|
|
|
|
|
|
|
|
12½, 15, | 20 | 1 | 3/4 | 1040 | 6.6 | 13.5 | ||
|
|
|
|
|
| |||
460 | 1 | 3/4 | 1040 | 3.2 | 8.4 | |||
|
|
|
|
|
|
|
|
|
|
|
| 575 | 1 | 3/4 | 1040 | 2.1 | 5.2 |
|
|
|
|
|
|
|
|
|
*Indicates both downflow and horizontal units.