Trane PKGP-PRC001-EN manual Electrical Data, Table ED-1 Unit Wiring, Rpm Fla Lra

Page 27

Electrical

Data

Table ED-1 — Unit Wiring

 

 

 

Standard Indoor Fan Motor

 

Oversize Indoor Fan Motor

 

 

 

Unit

Minimum

Maximum Fuse Size

Minimum

Maximum Fuse Size

 

Unit

Operating

Circuit

orMaximum

Circuit

orMaximum

Tons

Model No.

VoltageRange

Ampacity

Circuit Breaker1

Ampacity

Circuit Breaker1

 

WC*150B3

187-253

66.0

80

 

72.0

80

 

12½

WC*150B4

414-506

31.0

40

 

34.0

40

 

 

WC*150BW

517-633

25.0

30

 

28.0

35

 

 

 

 

 

 

 

 

 

 

 

WC*180B3

187-253

76.0

90

 

82.0

100

 

15

WC*180B4

414-506

39.0

45

 

42.0

50

 

 

WC*180BW

517-633

31.0

35

 

33.0

40

 

 

 

 

 

 

 

 

 

 

 

WC*240B3

187-253

96.0

125

 

103.0

125

 

20

WC*240B4

414-506

49.0

60

 

53.0

60

 

 

WC*240BW

517-633

38.0

45

 

41.0

50

 

 

 

 

 

 

 

 

 

 

Note:

1. HACR type circuit breaker per NEC.

Table ED-2 — Electrical Characteristics — Power Exhaust Accessory

 

 

 

Accessory

 

 

 

Amps

 

 

 

 

Operating

 

 

 

 

 

 

 

 

 

 

 

 

 

Tons

 

Voltage

Phase

HP

RPM

FLA

LRA

 

 

 

 

 

 

 

 

 

12½, 15,

20

208-230

1

3/4

1040

6.6

13.5

 

 

 

 

 

 

460

1

3/4

1040

3.2

8.4

 

 

 

 

 

 

 

 

 

 

 

 

575

1

3/4

1040

2.1

5.2

 

 

 

 

 

 

 

 

 

*Indicates both downflow and horizontal units.

PKGP-PRC001-EN

27

Image 27
Contents Packaged Heat Pumps Introduction Packaged Rooftop Air ConditionersContents Features Benefits Factory Installed Options Field Installed OptionsFactory or Field Installed Options Features and Benefits Easy to Install, Service and MaintainQuality and Reliability Quick-Access Panels Clogged Filter/Fan Failure SwitchColoredAnd NumberedWiring Power Exhaust OptionRigorous Testing Added Efficiency Easy to Install and ServiceClearance Requirements Power Exhaust AccessoryBarometric Relief Condensate TrapTo Find Capacity at Intermediate Conditions Cooling CapacityHeating Capacity StepDigits 9, 10 Factory Installed Options Model Number DescriptionCapacity MBh EER2 GeneralData12½Ton Table GD-1 General DataTable GD-2 General Data General DataMBH SHC MBH SHC MBH SHC PerformanceData15Ton WC*180BMBH SHC Data20Ton Three Phase WCD240BTable PD-6 Evaporator Fan Performance 12½ Ton WC*150B BHPBHP RPM Table PD-7 Evaporator Fan Performance 15 Ton WCD180B Table PD-8 Evaporator Fan Performance 15 Ton WCH180BCFM RPM BHP RPM BHP Table PD-9 Evaporator Fan Performance 20 Ton WC*240BData12½ 20Tons Table PD-10 Standard Motor & Drive/Fan Speed RPMTable PD-12 Oversized Motor & Drive/Fan Speed RPM WCH240B WCD240BData12½Ton Data15Ton Data20Ton Table PD-20 Auxiliary Electric Heat Capacity Table PD-19- Heating Capacity Correction FactorsControls Field Installed Control OptionsTable ED-1 Unit Wiring Electrical DataRPM FLA LRA 208/230 Volts Three Phase Volts Three Phase AYHHTRNW18A AYDHTRKW18AWCD150BW AYDHTRKW36A AYDHTRKW54AFLA LRA RPM RLA LRA Zone Sensors -Typical Number Of Wires Disconnect Switch Byothers Zonesensors Rooftop UnitJobsite Connections Typical Wiring 12½ 20TonsWiring 12½ 20Tons Wiring 12½ 20Tons Wiring 12½ 20Tons Dimensional Data 12½, 15TonDownflow Unit Clearance Horizontal Unit Supply/Return and Unit Clearance Downflow Duct Connections Field FabricatedDimensional 19 5/16 73 7/16 26 5/16 Table DD-1 Dimensional 12½ 20Tons DataAccessoriesTable DD-2 Options FiopsOptions Fiops Table DD-3 12½-20 Tons Weights 12½ 20Tons Table W-1 Accessory Net Weights LbsTable W-1 Weights 12½ 20Tons Mechanical Specifications Factory Installed Options High Pressure CutoutTwo-Inch Pleated Filters Reference or Comparative Enthalpy Factory or Field Installed OptionsEconomizer Downflow FrostatRoof Curb Downflow Field Installed OptionsPowered Exhaust Manual Outside Air DamperTrane