Performance
Data(20Ton)
Table
Outdoor | Integrated Heating Capacity (MBh/1000) |
|
| Total Power in Kilowatts A | |||||||
| At Indicated Indoor Dry Bulb Temp. |
| Indicated Indoor Dry Bulb Temp. | ||||||||
Temp. |
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| |
F. | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
| ||
78.1 | 75.8 | 74.9 | 74.0 | 16.7 | 17.8 | 18.4 | 19.1 |
| |||
86.8 | 84.4 | 83.4 | 82.5 | 16.8 | 17.9 | 18.6 | 19.3 |
| |||
2 | 96.0 | 93.6 | 92.4 | 91.4 | 16.9 | 18.1 | 18.7 | 19.5 |
| ||
7 | 106.4 | 103.8 | 102.0 | 100.9 | 17.1 | 18.3 | 18.9 | 19.7 |
| ||
12 | 119.9 | 117.1 | 115.8 | 114.6 | 17.3 | 18.6 | 19.2 | 20.0 |
| ||
17 | 131.0 | 128.0 | 126.6 | 125.3 | 17.5 | 18.8 | 19.5 | 20.2 |
| ||
22 | 142.5 | 139.4 | 137.9 | 136.4 | 17.7 | 19.0 | 19.8 | 20.5 |
| ||
27 | 154.5 | 151.2 | 149.6 | 148.0 | 18.0 | 19.3 | 20.0 | 20.8 |
| ||
32 | 167.2 | 163.6 | 161.7 | 160.0 | 18.3 | 19.6 | 20.3 | 21.1 |
| ||
37 | 180.8 | 176.9 | 174.8 | 172.9 | 18.5 | 19.8 | 20.5 | 21.3 |
| ||
42 | 194.0 | 189.8 | 187.5 | 185.5 | 18.7 | 20.0 | 20.7 | 21.5 |
| ||
47 | 213.9 | 209.0 | 206.6 | 204.3 | 18.9 | 20.2 | 20.9 | 21.7 |
| ||
52 | 228.5 | 223.1 | 220.4 | 217.8 | 19.0 | 20.4 | 21.1 | 21.9 |
| ||
57 | 243.4 | 237.4 | 234.5 | 231.7 | 19.4 | 20.8 | 21.5 | 22.3 |
| ||
62 | 262.1 | 255.5 | 252.3 | 249.1 | 19.9 | 21.2 | 21.9 | 22.7 |
| ||
67 | 278.3 | 271.2 | 267.7 | 264.1 | 20.3 | 21.7 | 22.4 | 23.2 |
| ||
72 | 295.6 | 288.1 | 284.3 | 280.5 | 20.8 | 22.2 | 23.0 | 23.8 |
|
For other airflow conditions, see heating capacity correction factor (Table
Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .40 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
Heating capacities and powers are integrated to include the effects of defrost in the frost region. All heating capacities and power (kW) are at 70% OD relative humidity.
Table
Outdoor | Integrated Heating Capacity (MBh/1000) |
|
| Total Power in Kilowatts At | ||||||
At Indicated Indoor Dry Bulb Temp. |
| Indicated Indoor Dry Bulb Temp. | ||||||||
Temp. |
| |||||||||
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
F. | 60 | 70 | 75 | 80 | 60 | 70 | 75 | 80 |
| |
77.7 | 75.4 | 74.5 | 73.6 | 15.4 | 16.4 | 17.0 | 17.6 |
| ||
86.3 | 84.0 | 82.9 | 82.0 | 15.5 | 16.5 | 17.1 | 17.8 |
| ||
2 | 95.5 | 93.0 | 92.0 | 90.9 | 15.6 | 16.7 | 17.3 | 18.0 |
| |
7 | 105.9 | 103.2 | 101.5 | 100.4 | 15.8 | 16.9 | 17.5 | 18.2 |
| |
12 | 109.9 | 107.3 | 106.1 | 105.0 | 16.0 | 17.1 | 17.8 | 18.4 |
| |
17 | 120.0 | 117.3 | 116.1 | 114.8 | 16.2 | 17.3 | 18.0 | 18.7 |
| |
22 | 130.6 | 127.7 | 126.4 | 125.0 | 16.4 | 17.6 | 18.2 | 18.9 |
| |
27 | 141.6 | 138.5 | 137.1 | 135.6 | 16.6 | 17.8 | 18.5 | 19.2 |
| |
32 | 153.2 | 149.9 | 148.2 | 146.6 | 16.9 | 18.1 | 18.7 | 19.5 |
| |
37 | 179.7 | 175.9 | 173.8 | 172.0 | 17.6 | 18.9 | 19.6 | 20.4 |
| |
42 | 192.9 | 188.7 | 186.5 | 184.5 | 17.9 | 19.2 | 19.9 | 20.7 |
| |
47 | 210.6 | 205.8 | 203.4 | 201.1 | 18.3 | 19.6 | 20.3 | 21.0 |
| |
52 | 225.0 | 219.6 | 217.0 | 214.4 | 19.0 | 20.3 | 21.0 | 21.8 |
| |
57 | 239.6 | 233.7 | 230.9 | 228.0 | 19.4 | 20.7 | 21.4 | 22.2 |
| |
62 | 256.8 | 250.3 | 247.2 | 244.0 | 19.8 | 21.1 | 21.9 | 22.6 |
| |
67 | 272.6 | 265.7 | 262.3 | 258.8 | 20.3 | 21.6 | 22.3 | 23.1 |
| |
72 | 289.6 | 282.2 | 278.5 | 274.8 | 20.8 | 22.1 | 22.9 | 23.7 |
|
For other airflow conditions, see heating capacity correction factor (Table
Net Heating Capacity and Power Input include indoor fan heat at nominal cfm and .40 inch ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
Heating capacities and powers are integrated to include the effects of defrost in the frost region. All heating capacities and power (kW) are at 70% OD relative humidity.
24 |