11. Operation Control

11.1 Cooling Operation

11.1.1Outdoor fan control

When cooling operation is enabled, based on outdoor ambient temperature, fan motor control will be adjusted according to figure below:

11.1.2Powerful Operation 1

During cooling operation, this control is to concentrate outdoor unit capability to the powerful operation enabled indoor unit by temporary stop the capability supply to low load demand indoor units.

Operation start condition:

o Powerful operation ON for targeted indoor unit.

Operation content:

o If other indoor units (where Powerful operation are OFF) achieve setting temperature continuously for 1 minutes after received powerful command from indoor unit, then capability supply to other indoor units are stopped for minimum 3 minutes. Capability supply stop period follows powerful operation period.

Operation stops when comply either one of the following conditions:

o When other indoor units (where Powerful operation are OFF) is lower than setting temperature. o When the powerful operation is OFF for all indoor units.

o When Quiet operation received from 1 indoor unit. o When protection control starts.

11.1.3Powerful Operation 2

During cooling operation, this control is to provide fast cooling operation compare to normal operation.

Operation start if all condition below are complied: o Powerful operation ON for indoor unit.

Operation content:

o Outdoor fan speed will adjust automatically.

o Compressor frequency will adjust automatically.

Operation stop when comply either one of the follow conditions: o When the powerful operation is OFF for all indoor units.

20

Image 20
Contents Table of Contents Disassembly and Assembly Instructions Safety Precautions Items to be followed are classified by the symbolsPage Specification Model Outdoor Unit CU-2S18NBU-1Multi split combination possibility Dimensions Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Electronic Circuit Diagram Printed Circuit Board Main Printed Circuit BoardNoise Filter Printed Circuit Board Installation Information Check PointsInstallation Instruction Outdoor Unit Installation DiagramOutdoor Unit Installation Guidelines Connecting the Piping to Outdoor Unit Gas Leak CheckingEvacuation of the Equipment Heat Insulation Powerful Operation Operation ControlCooling Operation Outdoor fan controlElectronic Parts Temperature Rise Protection 1 Cool Electronic Parts Temperature Rise Protection 2 CoolProtection Control Freeze Prevention control CoolTime Delay Safety Control Restart Control IPM power transistor Protection ControlCooling overload control Cool 12.7 30 seconds Force OperationCompressor discharge high pressure protection control Compressor Protection Control Gas leak detection controlValve close detection control Servicing Mode Wiring Error CheckPump Down Operation Test OperationPower Save Mode Mode priority functionTroubleshooting Guide Self Diagnosis FunctionIndoor high Check indoor heat Exchanger Disassembly and Assembly Instructions Outdoor Unit Removal ProcedureRemoving the Cabinet Top Plate and Cabinet Front Plate Remove the Control Board Cover and Particular PlatesRemoving the Control P.C. Board Removing the Propeller Fan and Fan MotorPage CS-S9NKUW-1 CU-2S18NBU-1 Technical DataOperation Characteristics Page CS-S9NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1 CU-2S18NBU-1 Page CS-S12NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1+CS-S9NKUW-1 CU-2S18NBU-1 Page Exploded View and Replacement Parts List REF. no Description & Name QTY Shock Absorber Left