Panasonic CU-2S18NBU-1 service manual Multi split combination possibility

Page 6

Multi split combination possibility:

o A single outdoor unit enables air conditioning of up to two separate rooms for CU-2S18NBU-1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CU-2S18NBU-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall

 

 

 

2.8 kW

 

 

 

 

CS-S9NKUW-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2 kW

 

 

 

 

CS-S12NKUW-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity range of connectable indoor units

 

 

 

 

 

From 5.6 kW to 6.4 kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 room maximum pipe length (m (ft))

 

 

 

 

 

25 (82.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length

Allowable elevation (m (ft))

 

 

 

 

 

15 (49.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total allowable pipe length (m (ft))

 

 

 

 

 

50 (164.0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total pipe length for maximum chargeless length (m (ft))

 

 

 

20 (65.6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional gas amount over chargeless length (g/m (oz/ft))

 

 

 

20 (0.2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: “●” : Available

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remarks for CU-2S18NBU-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

At least two indoor units must be connected.

 

 

 

 

 

 

 

 

 

 

 

2.

The total nominal cooling capacity of indoor unit that will be connected to outdoor unit must be within connectable capacity range of

 

 

indoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(as shown in the table above)

 

 

 

 

 

 

 

 

 

 

 

 

 

Example: The indoor units’ combination below is possible to connect to CU-2S18NBU-1. (Total nominal capacity of indoor units is

 

 

between 5.6 kW to 6.4 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

1) Two CS-S9NKUW-1 only. (Total nominal cooling capacity is 5.6 kW)

 

 

 

 

 

 

 

 

 

2) One CS-S9NKUW-1 and one CS-S12NKUW-1. (Total nominal cooling capacity is 6.0 kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit combination

Operation

Capacity (kW)

Input Power (W)

Current (A)

Current (A)

 

Moisture

Outdoor Unit

 

 

 

Mode

 

 

 

 

 

208V

 

230V

 

Removal

 

 

 

Operation

 

Class (kW)

Rating

 

Min - Max

Rating

Min - Max

60Hz

 

60Hz

Volume (L/h)

 

 

 

 

 

 

 

 

 

 

One-room

 

2.8

Cooling

2.82

 

1.81 ~ 3.27

850

390 ~ 1020

4.5

4.1

0.5

 

 

 

Operation

 

3.2

3.21

 

1.85 ~ 3.75

1000

390 ~ 1230

5.2

4.7

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

CU-2S18NBU-1

 

 

 

 

 

 

 

 

 

 

 

 

Two-room

 

2.8 + 2.8

 

4.89

 

2.09 ~ 5.86

1450

390 ~ 1920

7.6

6.9

0.5 + 0.5

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.8 + 3.2

4.89

 

2.10 ~ 5.86

1450

390 ~ 1870

7.6

6.9

0.5 + 0.6

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2 + 3.2

 

4.89

 

2.10 ~ 5.86

1450

390 ~ 1840

7.6

6.9

0.6 + 0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit combination

Operation

Capacity (BTU/h)

Input Power (W)

Current (A)

Current (A)

 

Moisture

Outdoor Unit

 

 

 

Mode

 

 

 

 

 

208V

 

230V

 

Removal

 

 

 

Operation

 

Class (kW)

Rating

 

Min - Max

Rating

Min - Max

60Hz

 

60Hz

Volume (Pt/h)

 

 

 

 

 

 

 

 

 

 

One-room

 

2.8

Cooling

9600

 

6200 ~ 11200

850

390 ~ 1020

4.5

4.1

1.1

 

 

 

Operation

 

3.2

10900

 

6300 ~ 12800

1000

390 ~ 1230

5.2

4.7

1.3

 

 

 

 

 

 

 

 

 

 

 

 

 

CU-2S18NBU-1

 

 

 

 

 

 

 

 

 

 

 

 

Two-room

 

2.8 + 2.8

 

16700

 

7100 ~ 20000

1450

390 ~ 1920

7.6

6.9

1.1 + 1.1

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.8 + 3.2

16700

 

7200 ~ 20000

1450

390 ~ 1870

7.6

6.9

1.1 + 1.3

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.2 + 3.2

 

16700

 

7200 ~ 20000

1450

390 ~ 1840

7.6

6.9

1.3 + 1.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications are subject to change without notice for further improvement.

6

Image 6
Contents Table of Contents Disassembly and Assembly Instructions Safety Precautions Items to be followed are classified by the symbolsPage Specification Model Outdoor Unit CU-2S18NBU-1Multi split combination possibility Dimensions Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Electronic Circuit Diagram Printed Circuit Board Main Printed Circuit BoardNoise Filter Printed Circuit Board Installation Information Check PointsInstallation Instruction Outdoor Unit Installation DiagramOutdoor Unit Installation Guidelines Connecting the Piping to Outdoor Unit Gas Leak CheckingEvacuation of the Equipment Heat Insulation Cooling Operation Powerful OperationOperation Control Outdoor fan controlProtection Control Electronic Parts Temperature Rise Protection 1 CoolElectronic Parts Temperature Rise Protection 2 Cool Freeze Prevention control CoolCooling overload control Cool Time Delay Safety Control Restart ControlIPM power transistor Protection Control 12.7 30 seconds Force OperationCompressor Protection Control Gas leak detection control Valve close detection controlCompressor discharge high pressure protection control Pump Down Operation Servicing ModeWiring Error Check Test OperationPower Save Mode Mode priority functionTroubleshooting Guide Self Diagnosis FunctionIndoor high Check indoor heat Exchanger Removing the Cabinet Top Plate and Cabinet Front Plate Disassembly and Assembly InstructionsOutdoor Unit Removal Procedure Remove the Control Board Cover and Particular PlatesRemoving the Control P.C. Board Removing the Propeller Fan and Fan MotorPage Technical Data Operation CharacteristicsCS-S9NKUW-1 CU-2S18NBU-1 Page CS-S9NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1 CU-2S18NBU-1 Page CS-S12NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1+CS-S9NKUW-1 CU-2S18NBU-1 Page Exploded View and Replacement Parts List REF. no Description & Name QTY Shock Absorber Left