Panasonic CU-2S18NBU-1 Servicing Mode, Pump Down Operation, Test Operation, Wiring Error Check

Page 24

13. Servicing Mode

13.1 Pump Down Operation

Operate the pump down according to the following procedures.

1Confirm the valve on the liquid side and gas side is open.

2Press PUMP DOWN switch (SW1) on the display printed circuit board for more than 5 seconds. Pump down (cooling) operation is performed for 15 minutes.

3Set the liquid side 3 way valve to close position and wait until the pressure gauge indicates 1.45 PSI.

4Immediately set the gas side valve to close position and then press the PUMP DOWN switch (SW1) to stop the pump down operation.

Note: Pump down operation will stop automatically after 15 minutes if PUMP DOWN switch (SW1) is not pressed again.

Pump down operation cannot be restarted until 3 minutes after compressor is stopped.

LED

2

3

4

5

Message

 

 

 

 

 

 

 

Pump down operation progress

Status

 

3 minutes before operation end

 

 

2 minutes before operation end

 

 

 

1 minute before operation end

 

 

 

 

 

 

 

 

 

Pump down operation end

 

 

 

 

 

 

: Flashing

13.2 Test Operation

Test operation can be carried out using OPERATION TEST switch (SW2) on the display printed circuit board inside the outdoor unit. For cooling test, press the TEST OPERATION switch (SW2) for more than 5 seconds. LED 1 and LED 2 will illuminate when shift into cooling test operation.

13.3 Wiring Error Check

This product capable to correcting the wiring errors automatically by following procedures.

1Confirm the valve on the liquid side and gas side is open.

2Press WIRING CHECK switch (SW3) on the display printed circuit board for more than 10 seconds to start wiring check operation.

3Wiring check process will complete in approximately 10 minutes. However, wiring check operation will not start within 3 minutes after compressor is stopped. When outdoor air temperature is less than 41°F or unit has

abnormality, wiring check will not start. (See NOTE 2).

The LED 2 to 6 in display printed circuit board inside the outdoor unit indicate whether correction is possible or not and the status of the correction, as shown in the table below.

LED

2

 

3

 

4

 

5

 

6

Message

 

 

 

 

 

 

 

 

 

 

 

ROOM

A

 

B

 

-

 

-

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

All flashing

 

Automatic correction impossible

 

 

 

Status

LED 2, 4, 6 and LED 3,

Wiring check in progress

5 alternatively flashing

 

Flashing one after

Automatic correction completed

 

 

 

another

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other than above

 

Unit has abnormally (Note 4)

 

 

 

 

 

 

 

 

 

 

 

If automatic correct is impossible, check the indoor unit wiring and piping manually.

24

Image 24
Contents Table of Contents Disassembly and Assembly Instructions Safety Precautions Items to be followed are classified by the symbolsPage Specification Model Outdoor Unit CU-2S18NBU-1Multi split combination possibility Dimensions Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Electronic Circuit Diagram Printed Circuit Board Main Printed Circuit BoardNoise Filter Printed Circuit Board Installation Information Check PointsInstallation Instruction Outdoor Unit Installation DiagramOutdoor Unit Installation Guidelines Connecting the Piping to Outdoor Unit Gas Leak CheckingEvacuation of the Equipment Heat Insulation Powerful Operation Operation ControlCooling Operation Outdoor fan controlElectronic Parts Temperature Rise Protection 1 Cool Electronic Parts Temperature Rise Protection 2 CoolProtection Control Freeze Prevention control CoolTime Delay Safety Control Restart Control IPM power transistor Protection ControlCooling overload control Cool 12.7 30 seconds Force OperationCompressor Protection Control Gas leak detection control Valve close detection controlCompressor discharge high pressure protection control Servicing Mode Wiring Error CheckPump Down Operation Test OperationPower Save Mode Mode priority functionTroubleshooting Guide Self Diagnosis FunctionIndoor high Check indoor heat Exchanger Disassembly and Assembly Instructions Outdoor Unit Removal ProcedureRemoving the Cabinet Top Plate and Cabinet Front Plate Remove the Control Board Cover and Particular PlatesRemoving the Control P.C. Board Removing the Propeller Fan and Fan MotorPage Technical Data Operation CharacteristicsCS-S9NKUW-1 CU-2S18NBU-1 Page CS-S9NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1 CU-2S18NBU-1 Page CS-S12NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1+CS-S9NKUW-1 CU-2S18NBU-1 Page Exploded View and Replacement Parts List REF. no Description & Name QTY Shock Absorber Left