12.10 Compressor Protection Control (Gas leak detection control 1)

Control start conditions

o For 5 minutes, the compressor continuously operates and total current is low. o During Cooling or Soft Dry operation:

Indoor intake temperature — indoor piping temperature is below 39.2°F.

Control content

o Compressor stops (and restart after 3 minutes)

o If the conditions above happen 4 times within 60 minutes, the unit will stop operation (“F91” is indicated).

12.11Compressor Protection Control (Gas leak detection control 2)

This control detect gas leakage condition to prevent compressor damage.

Control start condition

o All connected indoor units capability supply ON. o Compressor ON with maximum frequency.

o Compressor discharge temperature high.

Control content

o Compressor OFF during this control (“F91” is memorized in EEPROM)

o If the above conditions happen 2 times within 60 minutes, indoor units’ Timer LED will blinks (“F91” is indicated at all indoor units)

12.12 Valve close detection control

This control detects 3-way valve close condition to prevent damage to refrigerant cycle.

Start conditions:

o For all connected indoor units, if Indoor intake temperature — indoor piping temperature are between 28.4°F and 35.6°F continuously for 5 minutes after compressor ON at first cooling operation.

o The first cooling operation is defined as cooling operation is ON for less than 8 minutes after new installation or after pump down.

Control content

o During this control, compressor stop, indoor units’ Timer LED will blink. (“F91” is indicated at indoor units)

Error reset can be done by power supply reset or reset by using remote control.

12.13 Compressor discharge high pressure protection control

This control protect by using high pressure switch during operation.

Start conditions

o High pressure switch is activated (from normally close to open) when outdoor operation mode is cooling during compressor running.

Control 1 content

o Compressor stop when high pressure switch is opened and restart after high pressure switch closed. If this condition happen 4 times within 30 minutes, “F94” is indicated.

o After 30 minutes, counter is reset if this condition does not happen for 4 times.

Control 1 stop conditions o Power supply reset

o Reset by using remote control

23

Image 23
Contents Table of Contents Disassembly and Assembly Instructions Items to be followed are classified by the symbols Safety PrecautionsPage Model Outdoor Unit CU-2S18NBU-1 SpecificationMulti split combination possibility Dimensions Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Electronic Circuit Diagram Main Printed Circuit Board Printed Circuit BoardNoise Filter Printed Circuit Board Check Points Installation InformationOutdoor Unit Installation Diagram Installation InstructionOutdoor Unit Installation Guidelines Gas Leak Checking Connecting the Piping to Outdoor UnitEvacuation of the Equipment Heat Insulation Outdoor fan control Powerful OperationOperation Control Cooling OperationFreeze Prevention control Cool Electronic Parts Temperature Rise Protection 1 CoolElectronic Parts Temperature Rise Protection 2 Cool Protection Control12.7 30 seconds Force Operation Time Delay Safety Control Restart ControlIPM power transistor Protection Control Cooling overload control CoolCompressor discharge high pressure protection control Compressor Protection Control Gas leak detection controlValve close detection control Test Operation Servicing ModeWiring Error Check Pump Down OperationMode priority function Power Save ModeSelf Diagnosis Function Troubleshooting GuideIndoor high Check indoor heat Exchanger Remove the Control Board Cover and Particular Plates Disassembly and Assembly InstructionsOutdoor Unit Removal Procedure Removing the Cabinet Top Plate and Cabinet Front PlateRemoving the Propeller Fan and Fan Motor Removing the Control P.C. BoardPage CS-S9NKUW-1 CU-2S18NBU-1 Technical DataOperation Characteristics Page CS-S9NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1 CU-2S18NBU-1 Page CS-S12NKUW-1x2 CU-2S18NBU-1 Page CS-S12NKUW-1+CS-S9NKUW-1 CU-2S18NBU-1 Page Exploded View and Replacement Parts List REF. no Description & Name QTY Shock Absorber Left