Deltech Fitness LS2580, LS60 General Piping Information, Not USE Plug or Gate Valves

Page 10

2.4General Piping Information

NOTE 1: Use the proper pressure rated piping, fittings and valves as approved by ASME, ANSI, ASA, etc. Separate or special requirements by local and/or municipal codes may also apply.

NOTE 2: The manufacturer is not liable for code viola- tions, downtime, component failure or conse- quential damages to customer supplied com- ponents and/or equipment.

NOTE 3: Where it is undesirable to interrupt process flow, a redundant system with block valves should be installed to permit servicing and maintenance of the dryer and associated filter assemblies. The recommended block valve MUST be of a type which will provide bubble- tight shut-off. Ball, globe or butterfly valves with soft seats are suitable for this purpose. DO

NOT USE PLUG OR GATE VALVES.

NOTE 4: All inlet and outlet connections, valve and inter- connecting piping MUST be of the same size as the dryer’s gas inlet connection or larger. The manufacturer and its affiliates are not liable for excessive pressure drops and loss of ca- pacity caused by undersized or incorrectly in- stalled piping and/or piping components. Refer to Table 2.1 for inlet and outlet connection sizes for your dryer system.

NOTE 5: Carefully inspect all piping lengths and compo- nents BEFORE installation. Remove any inter- nal oil, water, dirt, or debris which may have accumulated during shipment and/or storage.

NOTE 6: Leakage from piping connections and/or asso- ciated components installed upstream of the dryer will cause a loss of gas pressure and un- necessary compressor cycling. The slightest leakage from piping connections and/or asso- ciated components installed downstream of the dryer’s outlet connection can easily cause a degradation of the dried gas dew point. The use of TFE tape on all male pipe threads and the application of sufficient torque at assembly will greatly reduce chances of leakage and subsequent rework.

1.All external piping must be supplied by the customer unless otherwise specified. Refer to Table 2.1 for connection sizes. Inlet and outlet manual shut-off valves and a vent valve are recommended so the dry- ers and filters can be isolated and depressurized for servicing. Refer to Figure 2.1 for recommended pip- ing layout.

2.Be sure all piping is supported. Do not allow the weight of any piping to bear on the dryer or filters.

Table 2.1

CONNECTIONS

 

FO1 Connections¹

F02/FO7 Connections²

Model

(Inches)

(Inches)

 

 

 

 

 

 

Inlet

Outlet

Inlet

Outlet

 

 

 

 

 

LS60

1" NPT

¾ " NPT

1" NPT

1" NPT

LS110

1¼ " NPT

¾ " NPT

1" NPT

1" NPT

LS130

1¼ " NPT

1" NPT

1" NPT

1" NPT

LS185

1½ " NPT

1" NPT

1" NPT

1" NPT

LS240

1½ " NPT

1¼ " NPT

1½ " NPT

1½ " NPT

 

 

 

 

 

LS270

1½ " NPT

1¼ " NPT

1½ " NPT

1½ " NPT

LS360

1½ " NPT

1½ " NPT

1½ " NPT

1½ " NPT

LS505

2½ " NPT

2" NPT

2" NPT

2" NPT

LS630

2½ " NPT

2½ " NPT

2" NPT

2" NPT

LS760

2½ " NPT

2½ " NPT

2" NPT

2" NPT

 

 

 

 

 

LS1000

3" FLG

2½ " NPT

3" FLG

3" FLG

LS1250

3" FLG

3" FLG

3" FLG

3" FLG

LS1500

4" FLG

4" FLG

4" FLG

4" FLG

LS2070

4" FLG

4" FLG

4" FLG

4" FLG

LS2580

4" FLG

4" FLG

4" FLG

4" FLG

 

FO1 Connections¹

F02/FO7 Connections²

Model

(Inches)

(Inches)

 

 

 

 

 

 

Inlet

Outlet

Inlet

Outlet

 

 

 

 

 

LSC60

¾ " NPT

¾ " NPT

1" NPT

1" NPT

LSC110

1" NPT

¾ " NPT

1" NPT

1" NPT

LSC130

1" NPT

¾ " NPT

1" NPT

1" NPT

LSC185

1¼ " NPT

¾ " NPT

1" NPT

1" NPT

LSC240

1¼ " NPT

1" NPT

1" NPT

1½ " NPT

LSC270

1¼ " NPT

1" NPT

1" NPT

1½ " NPT

LSC360

1½ " NPT

1¼ " NPT

1" NPT

1½ " NPT

LSC505

2" NPT

1¼ " NPT

1½ " NPT

2" NPT

LSC630

2" NPT

1½ " NPT

1½ " NPT

2" NPT

LSC760

2½ " NPT

2" NPT

2" NPT

2" NPT

 

 

 

 

 

LSC1000

2½ " NPT

2½ "NPT

2" NPT

2" NPT

LSC1250

3" FLG

3" FLG

3" FLG

3" FLG

LSC1500

3" FLG

3" FLG

3" FLG

3" FLG

LSC2070

4" FLG

4" FLG

4" FLG

4" FLG

LSC2580

4" FLG

4" FLG

4" FLG

4" FLG

 

 

 

 

 

¹F01 – Standard mounted filter package

²F02 /F07 – Optional mounted filter packages

3.Purge Exhaust Piping is not required on Models LS60 through LS1500. However, if it is necessary to have a remote mounted muffler, consult with your local Deltech Sales Representative for special piping in- structions.

On Models LS2070 and LS2580, refer to the Purge Exhaust Muffler Section of the manual for Purge Ex- haust Piping instructions.

2 - 2 Installation

Image 10
Contents Hydrobloc LS Series Heatless Compressed AIR Dryer Page Contents Section Maintenance and Repair Hydrobloc LS Series Specifications ScfmModel Prefilter Afterfilter General System Information Prefilter AssemblyForeword DryerAfterfilter Assembly Automatic Drain ValvesEquipment Handling Receiving and InspectionMechanical Set-Up General Piping Information Not USE Plug or Gate ValvesPurge Exhaust Restrictor Electrical ConnectionPurge Exhaust Muffler Static Sensitive Devices Remote Alarm Connection Equipment CheckInstrumentation Moisture Indicator Option a & B Valve Switching Failure Option a & BPurge Flow Indicator Chamber Pressure GaugesPage How It Works Automatic Drain ValveOperation Initial Start-Up For Dryers With DEC Controller Dryer Models LS60 through LS1000Dryer Models LS1250 and LS1500 Dryer Models LS2070 and LS2580 Operation Normal Start-Up or Restart For Dryers With DEC Controller Models LS60 through LS1000 onlyDryer Models LS1250 and LS1500 Normal Operational Checks Dryer ShutdownOperation Maintenance and Repair Preventative Maintenance ScheduleDesiccant Charging Procedures AnnuallyFor Dryer Models LS60 through LS1500 Filter Element ReplacementFor Dryer Models LS2070 and LS2580 Servicing The Internal Float Drain Valve If Equipped Automatic Drain Valve Disassembly and Servicing Automatic Drain Valve ComponentsMaintenance and Repair Moisture Indicator Recharging Procedure Inlet and Purge Exhaust Switching Valve Maintenance LS60 through LS760Inlet and Purge Exhaust Switching Valve LS1000 LS1000 3 Inlet Switching Valve Maintenance Models LS1250 and LS1500LS1250, LS1500 10 2 Purge Exhaust Switching Valve Maintenance Model LS1250 onlyLS1250 11 3 Purge Exhaust Switching Valve Maintenance Model LS1500 onlyPurge Exhaust Switching Valve Purge and Outlet Check Valve Maintenance Models LS60 through LS76013 11 13 3 Purge and Outlet Check Valve Maintenance Models LS1000 through LS1500Maintenance and Repair 4 Remote Flow Restrictor Maintenance Flow Restrictor Maintenance Models LS1500 through LS2580Actuator Subassembly Shaft Subassembly Purge Adjusting Valve Models LS2070 and LS2580Pilot Gas Filter Maintenance Page Troubleshooting Guide Shutdown and Depressurize Dryer. Inspect desiccant De-energize Dryer Power Supply. Replace fuse if blown, Shutdown and Depressurize Dryer. Refer to the Inlet SwitchDe-energize Dryer Power Supply. Check power supply input Shutdown and Depressurize Dryer. Refer to the PurgeShutdown and Depressurize Dryer. Replace damaged, faulty Shutdown and Depressurize Dryer. Drain desiccant fromLess the piping to the Purge Exhaust Muffler is ad For Models LS1500 through LS2580Removal of the Flow restrictor should not be done un Equately supported. Failure to do so may resultNot lit, Shutdown and Depressurize Dryer. Provide a During Repressurization CycleShutdown and Depressurize Dryer. Replace pressure sen PROBLEM/POSSIBLE Cause Shutdown and Depressurize Dryer. Disassemble, clean If voltage is present. De-energize Dryer Power Supply. RePROBLEM/POSSIBLE Cause Checks and Remedy Page Appendix a Purge Curves Calculation of Purge Pressure Setting Table a 1 Inlet Airflow at Various Inlet Air Pressures¹Orifice Dia Gas Air Temp 100F Figure A.2 Critical Orifice Calibration Curve Figure A.3 Critical Orifice Calibration Curve Figure A.4 Critical Orifice Calibration Curve Figure A.5 Critical Orifice Calibration Curve Figure A.6 Critical Orifice Calibration Curve Figure A.7 Critical Orifice Calibration Curve Psig Pressure Purge Figure A.9 Critical Orifice Calibration Curve Purge Pressure P1 Psig Figure A.11 Critical Orifice Calibration Curve Figure A.12 Critical Orifice Calibration Curve Figure A.13 Critical Orifice Calibration Curve Appendix B Hydrobloc LS Replacement Parts 1276865 1275442 Appendix C Page Hydrobloc LSC Specifications Model Prefilter Afterfilter Hydrobloc LSC Purge Curves Table C 1 Inlet Airflow at Various Inlet Air Pressures¹Figure C.1 Critical Orifice Calibration Curve Figure C.2 Critical Orifice Calibration Curve Figure C.3 Critical Orifice Calibration Curve Figure C.4 Critical Orifice Calibration Curve Figure C.5 Critical Orifice Calibration Curve Figure C.6 Critical Orifice Calibration Curve Figure C.7 Critical Orifice Calibration Curve Figure C.8 Critical Orifice Calibration Curve Figure C.9 Critical Orifice Calibration Curve Figure C.10 Critical Orifice Calibration Curve Figure C.11 Critical Orifice Calibration Curve Figure C.12 Critical Orifice Calibration Curve Figure C.13 Critical Orifice Calibration Curve Hydrobloc LSC Replacement Parts 1198157 1218635 1200806 1180918 1218638 Description Quantity Model Page Page Deltech

LS60, LS2580 specifications

Deltech Fitness is renowned for providing high-quality strength training equipment, and their LS2580 and LS60 models are no exception. Both of these machines have been designed with the serious fitness enthusiast in mind, offering a range of features that cater to effective strength training routines.

The LS2580 is a multi-station home gym designed to facilitate a variety of exercises without needing multiple machines. This versatility allows users to perform a full-body workout in the comfort of their own home. One of the main features of the LS2580 is its adjustable weight stack, which provides users with the flexibility to customize their workouts. It boasts a robust and stable frame, engineered to withstand the demands of heavy usage.

With a focus on user safety, the LS2580 incorporates several safety features, including easily accessible adjustment points and non-slip grips. This makes switching between exercises seamless and reduces the risk of injury. The machine also supports a range of movements including lat pulldowns, leg presses, chest presses, and more, allowing users to target different muscle groups effectively.

On the other hand, the Deltech Fitness LS60 is a slightly simpler yet equally impressive machine that excels in offering a compact solution for strength training. The LS60 focuses on essential muscle groups, catering to those who may have limited space but do not want to compromise on their workout regimen. It is designed with a sturdy frame and is ideal for users who prioritize stability and durability in their fitness equipment.

One of the standout features of the LS60 is its adjustable seat height, making it suitable for various body types. This adaptability ensures that everyone can maintain proper form during workouts, which is crucial for both performance and safety. The LS60 also comes with various attachment points, allowing users to incorporate resistance bands or other accessories to enhance their training.

In terms of technology, both the LS2580 and LS60 emphasize user-friendly design elements that promote an intuitive workout experience. The clear labeling of each exercise station makes transitioning between workouts simple and efficient.

In summary, both Deltech Fitness LS2580 and LS60 present compelling options for fitness enthusiasts, providing a versatile and effective solution for strength training. Whether you opt for the comprehensive features of the LS2580 or the compact design of the LS60, you can expect durability, safety, and a focus on achieving your fitness goals at home.