Deltech Fitness LS60 instruction manual Dryer Models LS2070 and LS2580

Page 21

right chamber. Both Purge Exhaust Switching Valves will close. The desiccant chambers will im- mediately begin pressurizing to system pressure as indicated by chamber pressure gauges.

10.The Moisture Indicator’s (if dryer so-equipped) bleed valve is installed directly into the back of the indicator’s body. Close the Indicator’s Bleed Valve. FULLY open the Moisture Indicator Supply Valve.

11.Soap bubble test all external piping, fittings, and con- nections. Locate and repair all noted points of leak- age. Do not soap bubble test components lo- cated inside dryer control system's enclosure.

Note: Small leaks noted in inlet piping to the dryer will not affect operation, other than a slight loss of pressure supplied to the dryer. HOWEVER, any gas leaks, (no matter how small), detected at, or down- stream of the dryer outlet MUST BE FIXED to ensure that the dryer will provide a continuous supply of pro- cess gas at specified dew point, to intended points- of-use.

IMPORTANT: Water molecules can diffuse through a pinhole-size leak even though pressure inside the piping is several hundred PSIG. It is not uncommon to have a minute pinhole leak in a gas line cause an increase in dew point from -40°F to -10°F at a dis- tance of forty or more feet downstream of the leak.

12.SLOWLY open the System Outlet Isolation Valve (customer supplied), while monitoring the Outlet Pressure Gauge (if dryer so-equipped). DO NOT per- mit the Dryer's Outlet Pressure Gauge to exceed a 5% drop in pressure while pressurizing downstream piping.

13.Close the System Bypass Valve (if gas system has been so-equipped).

14.Open and adjust the Moisture Indicator’s Bleed Valve until a very slight, continuous gas bleed is felt ex- hausting from the bleed valve’s exhaust port. Ensure that the granular indicator crystals remain motionless after final adjustment.

15.Energize the dryer’s electrical power supply.

16.Refer to Appendix A (Appendix C for -100°F pdp) of this manual and calculate your dryer model's purge pressure setting as instructed.

17.Locate the Purge Adjusting Valve. Slowly rotate dryer’s Purge Adjusting Valve until the Purge Pres- sure Indicator indicates the calculated purge pressure setting. (See following Note).

Note: The purge pressure can only be read and ad- justed when an off-stream desiccant chamber has depressurized for regeneration. (When the off- stream chamber is pressurized, the Purge Pressure Indicator will read “system pressure”.)

For dryers with the Hydrobloc Energy Management System: During operation in the Energy Manage- ment Mode, the off-stream chamber may remain pressurized (in ENERGY MANAGEMENT ACTIVE). If this condition is noted, proceed as follows to adjust purge pressure.

a)Open Dryer Control System Enclosure. Locate DIP switches on MEC CPU Board.

b)Switch DIP switch position 7 to OFF position (down). De-energize dryer’s electrical power sup- ply for approximately fifteen (15) seconds; then re-energize. Dryer is now in Fixed Cycle Opera- tion. The off-stream chamber will depressurize to atmosphere for regeneration.

c)Calculate and set purge pressure as previously instructed.

d)Return DIP switch position 7 to ON position. De-energize the dryer’s electrical power supply for approximately fifteen (15) seconds; then re- energize. Dryer should be in Compu-Save En- ergy Saver Mode.

18.The Start-Up procedure for models LS1250 and LS1500 is now complete. Proceed to the Normal Op- eration Checks section of this manual for final opera- tional checks and adjustments.

Dryer Models LS2070 and LS2580

Do not start the dryer with compressed air flow through the dryer. Close customer supplied dryer shut-off valves before beginning start-up procedure.

1.Refer to the General Arrangement drawing as neces- sary for component identification and location while conducting start-up and operational procedures.

Note: If your dryer cannot be started, or fails to start due to special installation or other problems, contact your local Deltech Sales Representative for assis- tance.

2.Remove the Pilot Gas Filter Bowl. Verify that the pi- lot gas filter cartridge is installed. Replace Filter Bowl ensuring that O-ring is properly seated. Close the filter bowl bleed valve.

3.All Prefilter and Afterfilter Assemblies are shipped WITH filter cartridges installed. Verify that prefilter and afterfilter cartridges are installed. Prefilter and Afterfilter cartridges are NOT interchangeable and must be installed in their respective assemblies ONLY. The proper filter cartridge part number is listed on each Prefilter and Afterfilter Assembly.

4.Replace and tighten filter assembly bowls. Ensure that O-rings are properly seated.

Operation 3 - 5

Image 21
Contents Hydrobloc LS Series Heatless Compressed AIR Dryer Page Contents Section Maintenance and Repair Scfm Hydrobloc LS Series SpecificationsModel Prefilter Afterfilter Foreword Prefilter AssemblyGeneral System Information DryerAutomatic Drain Valves Afterfilter AssemblyReceiving and Inspection Equipment HandlingMechanical Set-Up Not USE Plug or Gate Valves General Piping InformationElectrical Connection Purge Exhaust RestrictorPurge Exhaust Muffler Static Sensitive Devices Equipment Check Remote Alarm ConnectionInstrumentation Purge Flow Indicator Valve Switching Failure Option a & BMoisture Indicator Option a & B Chamber Pressure GaugesPage Automatic Drain Valve How It WorksOperation Dryer Models LS60 through LS1000 Initial Start-Up For Dryers With DEC ControllerDryer Models LS1250 and LS1500 Dryer Models LS2070 and LS2580 Operation Models LS60 through LS1000 only Normal Start-Up or Restart For Dryers With DEC ControllerDryer Models LS1250 and LS1500 Dryer Shutdown Normal Operational ChecksOperation Preventative Maintenance Schedule Maintenance and RepairAnnually Desiccant Charging ProceduresFilter Element Replacement For Dryer Models LS60 through LS1500For Dryer Models LS2070 and LS2580 Servicing The Internal Float Drain Valve If Equipped Automatic Drain Valve Components Automatic Drain Valve Disassembly and ServicingMaintenance and Repair Moisture Indicator Recharging Procedure LS60 through LS760 Inlet and Purge Exhaust Switching Valve MaintenanceInlet and Purge Exhaust Switching Valve LS1000 LS1000 Models LS1250 and LS1500 3 Inlet Switching Valve MaintenanceLS1250, LS1500 Model LS1250 only 10 2 Purge Exhaust Switching Valve MaintenanceLS1250 Model LS1500 only 11 3 Purge Exhaust Switching Valve MaintenancePurge Exhaust Switching Valve Models LS60 through LS760 Purge and Outlet Check Valve Maintenance13 11 Models LS1000 through LS1500 13 3 Purge and Outlet Check Valve MaintenanceMaintenance and Repair 4 Remote Flow Restrictor Maintenance Models LS1500 through LS2580 Flow Restrictor MaintenanceActuator Subassembly Shaft Subassembly Models LS2070 and LS2580 Purge Adjusting ValvePilot Gas Filter Maintenance Page Troubleshooting Guide Shutdown and Depressurize Dryer. Inspect desiccant De-energize Dryer Power Supply. Check power supply input Shutdown and Depressurize Dryer. Refer to the Inlet SwitchDe-energize Dryer Power Supply. Replace fuse if blown, Shutdown and Depressurize Dryer. Refer to the PurgeShutdown and Depressurize Dryer. Drain desiccant from Shutdown and Depressurize Dryer. Replace damaged, faultyRemoval of the Flow restrictor should not be done un For Models LS1500 through LS2580Less the piping to the Purge Exhaust Muffler is ad Equately supported. Failure to do so may resultDuring Repressurization Cycle Not lit, Shutdown and Depressurize Dryer. Provide aShutdown and Depressurize Dryer. Replace pressure sen PROBLEM/POSSIBLE Cause If voltage is present. De-energize Dryer Power Supply. Re Shutdown and Depressurize Dryer. Disassemble, cleanPROBLEM/POSSIBLE Cause Checks and Remedy Page Appendix a Purge Curves Table a 1 Inlet Airflow at Various Inlet Air Pressures¹ Calculation of Purge Pressure SettingOrifice Dia Gas Air Temp 100F Figure A.2 Critical Orifice Calibration Curve Figure A.3 Critical Orifice Calibration Curve Figure A.4 Critical Orifice Calibration Curve Figure A.5 Critical Orifice Calibration Curve Figure A.6 Critical Orifice Calibration Curve Figure A.7 Critical Orifice Calibration Curve Psig Pressure Purge Figure A.9 Critical Orifice Calibration Curve Purge Pressure P1 Psig Figure A.11 Critical Orifice Calibration Curve Figure A.12 Critical Orifice Calibration Curve Figure A.13 Critical Orifice Calibration Curve Appendix B Hydrobloc LS Replacement Parts 1276865 1275442 Appendix C Page Hydrobloc LSC Specifications Model Prefilter Afterfilter Table C 1 Inlet Airflow at Various Inlet Air Pressures¹ Hydrobloc LSC Purge CurvesFigure C.1 Critical Orifice Calibration Curve Figure C.2 Critical Orifice Calibration Curve Figure C.3 Critical Orifice Calibration Curve Figure C.4 Critical Orifice Calibration Curve Figure C.5 Critical Orifice Calibration Curve Figure C.6 Critical Orifice Calibration Curve Figure C.7 Critical Orifice Calibration Curve Figure C.8 Critical Orifice Calibration Curve Figure C.9 Critical Orifice Calibration Curve Figure C.10 Critical Orifice Calibration Curve Figure C.11 Critical Orifice Calibration Curve Figure C.12 Critical Orifice Calibration Curve Figure C.13 Critical Orifice Calibration Curve Hydrobloc LSC Replacement Parts 1198157 1218635 1200806 1180918 1218638 Description Quantity Model Page Page Deltech

LS60, LS2580 specifications

Deltech Fitness is renowned for providing high-quality strength training equipment, and their LS2580 and LS60 models are no exception. Both of these machines have been designed with the serious fitness enthusiast in mind, offering a range of features that cater to effective strength training routines.

The LS2580 is a multi-station home gym designed to facilitate a variety of exercises without needing multiple machines. This versatility allows users to perform a full-body workout in the comfort of their own home. One of the main features of the LS2580 is its adjustable weight stack, which provides users with the flexibility to customize their workouts. It boasts a robust and stable frame, engineered to withstand the demands of heavy usage.

With a focus on user safety, the LS2580 incorporates several safety features, including easily accessible adjustment points and non-slip grips. This makes switching between exercises seamless and reduces the risk of injury. The machine also supports a range of movements including lat pulldowns, leg presses, chest presses, and more, allowing users to target different muscle groups effectively.

On the other hand, the Deltech Fitness LS60 is a slightly simpler yet equally impressive machine that excels in offering a compact solution for strength training. The LS60 focuses on essential muscle groups, catering to those who may have limited space but do not want to compromise on their workout regimen. It is designed with a sturdy frame and is ideal for users who prioritize stability and durability in their fitness equipment.

One of the standout features of the LS60 is its adjustable seat height, making it suitable for various body types. This adaptability ensures that everyone can maintain proper form during workouts, which is crucial for both performance and safety. The LS60 also comes with various attachment points, allowing users to incorporate resistance bands or other accessories to enhance their training.

In terms of technology, both the LS2580 and LS60 emphasize user-friendly design elements that promote an intuitive workout experience. The clear labeling of each exercise station makes transitioning between workouts simple and efficient.

In summary, both Deltech Fitness LS2580 and LS60 present compelling options for fitness enthusiasts, providing a versatile and effective solution for strength training. Whether you opt for the comprehensive features of the LS2580 or the compact design of the LS60, you can expect durability, safety, and a focus on achieving your fitness goals at home.