DIP Switch Settings
The DIP switches are location on the back of the Optical Communication Unit. You can control the basic configuration of the Optical Communication Unit by turning the DIP switches on and off in various combinations.
1 2 3 4 5 6 7 8 9 10
■Flow Control
| 9 | 10 |
None | OFF | OFF * |
X ON/X OFF | ON | OFF |
RS/CS | OFF | ON |
Special Software | ON | ON |
■Optical Communication Unit – Host Data Rate
| 6 | 7 | 8 |
2,400bps | OFF | OFF | OFF |
4,800bps | ON | OFF | OFF |
9,600bps | OFF | ON | OFF * |
19,200bps | ON | ON | OFF |
38,400bps | OFF | OFF | ON |
57,600bps | ON | OFF | ON |
115,200bps | OFF | ON | ON |
■Pocket PC Terminal – Optical Communication Unit Data Rate
12
38,400bps OFF ON
115,200bps | ON | OFF * |
*Indicates initial default settings.
Important
■Connection Type
| 3 | 4 | 5 |
With Host | OFF | OFF | ON (No daisy chain) * |
|
|
| OFF (Daisy chain) |
Daisy Chain | ON | OFF | OFF |
Intermediate Unit |
|
|
|
Daisy Chain | ON | OFF | ON |
Terminator Unit |
|
|
|
Use only the settings shown above. Other settings other than those noted above are for special maintenance modes.
37