PROGRAMMING GROUP 2: METER CALIBRATION

9.1STANDARD CALIBRATION

WARNING - READ THIS SECTION CAREFULLY BEFORE PROCEEDING

Calibration does not need to be accomplished to change CT or PT ratios. (See GROUP 1).

Meter calibration cannot be performed if the meter is installed for service. The sensing must be connected to a power supply with variable voltage and separate current outputs.

The calibration procedure requires highly accurate and stable input signals. Incorrect readings result from improper calibration procedures. If unsure, return unit to the factory for calibration.

BEFORE calibrating any channel, make note of its Full Scale Setting (see Ch. 8). Set the Full Scale in accordance with Table 9-1for calibration. Restore original Full Scale Setting when calibration is completed.

The first function in GROUP 2 (STD.CORR) is NOT to be changed by the user. Please make

note of the value here ( ) before using any other function in this Group. If the STD.CORR value is inadvertently lost or changed, contact the factory for assistance.

All sensitive electronic measuring devices drift slightly over time, requiring periodic calibration. We recommend returning the meter to the factory on a yearly basis.

TABLE 9-0: GROUP 2 PROGRAMMING FORMAT

FUNCTION NUMBER

FUNCTION

P.

Standard Correction. Factory Procedure only.

0.

High End Calibration, VOLTS AN

1.

High End Calibration, VOLTS BN

2.

High End Calibration, VOLTS CN

3.

High End Calibration, AMPS A

4.

High End Calibration, AMPS B

5.

High End Calibration, AMPS C

6.

Low End Calibration, AMPS A

7.

Low End Calibration, AMPS B

8.

Low End Calibration, AMPS C

E.

Exit Programming GROUP 2

The Full Scale and Calibration values should be equal during the calibration procedure. The meter may be rescaled without calibrating by changing the full scale in GROUP 1, FUNCTION 0 or 1. (See Table 9-1)

TABLE 9-1: SOURCE, FULL SCALE AND VALUE SETTINGS FOR CALIBRATION

CALIBRATION TYPE/

CALIB. SOURCE

FULL SCALE SETTING

CALIBRATION VALUE

RANGES

NECESSARY

 

 

VOLTS 120/208V

120V

120V

120

VOLTS 277/480V

300V

300V

300

VOLTS 4/1 PT

120V

480V

480

VOLTS 60/1 PT

120V

7.20KV

7.20

AMPS Hi End 1000/5 CT

5A

1000A

1000

AMPS Hi End 5000/5 CT

5A

5.00KA

5.00

AMPS Lo End 1000/5 CT

2.5A

 

500

AMPS Lo End 5000/5 CT

2.5A

 

2.50

 

 

 

31

GE Industrial Systems

Image 36
Contents EPM 3000P All Rights Reserved Customer Service and Support Installation & O P E R a T I O N O G R a M M I N G Installation & Operation Mechanical InstallationMechanical Installation PortElectrical Installation CT Size VA Maximum Distance CT to EPM3000PListing of Connection Diagrams Electrical InstallationWith Direct Voltage and CTs With 2 CTs and 2 PTsIII. Open Delta PT Connection With 3 CTs and 2 PTsThree Phase System Wye System with PTs DUAL-PHASE Back ViewCOM Communication Installation RS-232CRS-485 RS-485 Hookup Diagram 2 wire Half Duplex Communication InstallationRS-485 Hookup Diagram 2 wire Half Duplex Detail View EPM3000P Overview Volts Amps‰ Unprotected Reset ‰ Protected ResetEPM3000P Overview Voltage Phase Reversal Voltage Phase Imbalance LimitAccess Operation I000222 ÖTo Print the Programming DATA, follow these steps300.0 General Procedure Overview GROUPS, Functions, and Switch PacksGeneral Procedure Overview PasswordUsed for Standard Numeric Data EntryEntering the Programming Mode 555Programming Group 0 Global Meter Setup Function NumberGlobal Meter Setup 020I20 Pack Switch Feature Segment Position Computer Controlled Dedicated Alarm 03.0S E T I25 Programming Group Input Voltage PT Ratio Full ScaleInput Current CT Type Full Scale I50 Programming GroupVolts 4/1 PT Programming Group 2 Meter Calibration To change the CALIBRATION, follow these steps250 Programming Group 4 SET Limits & Relays 10.1Set Limits & Relays LM1 LED LM2 LED ABOVE/BELOW Relay ValueLM1 LED LM2 LED ABOVE/ below Relay Level Set Limits and Relays ÖTo program Limits or RELAYS, follow these stepsSee to Exit Phase Reversal Percent Phase ImbalancePhase Reversal & Phase Imbalance Set Limits/Relays ÖTo change the Phase Reversal settings, follow these stepsI0.0 Exiting the Programming Mode If YOU are Located AT