CHAPTER 9
PROGRAMMING GROUP 2: METER CALIBRATION
9.1STANDARD CALIBRATION
WARNING - READ THIS SECTION CAREFULLY BEFORE PROCEEDING
⌦Calibration does not need to be accomplished to change CT or PT ratios. (See GROUP 1).
⌦Meter calibration cannot be performed if the meter is installed for service. The sensing must be connected to a power supply with variable voltage and separate current outputs.
⌦The calibration procedure requires highly accurate and stable input signals. Incorrect readings result from improper calibration procedures. If unsure, return unit to the factory for calibration.
⌦BEFORE calibrating any channel, make note of its Full Scale Setting (see Ch. 8). Set the Full Scale in accordance with Table
⌦The first function in GROUP 2 (STD.CORR) is NOT to be changed by the user. Please make
note of the value here ( ) before using any other function in this Group. If the STD.CORR value is inadvertently lost or changed, contact the factory for assistance.
All sensitive electronic measuring devices drift slightly over time, requiring periodic calibration. We recommend returning the meter to the factory on a yearly basis.
TABLE
FUNCTION NUMBER | FUNCTION |
P. | Standard Correction. Factory Procedure only. |
0. | High End Calibration, VOLTS AN |
1. | High End Calibration, VOLTS BN |
2. | High End Calibration, VOLTS CN |
3. | High End Calibration, AMPS A |
4. | High End Calibration, AMPS B |
5. | High End Calibration, AMPS C |
6. | Low End Calibration, AMPS A |
7. | Low End Calibration, AMPS B |
8. | Low End Calibration, AMPS C |
E. | Exit Programming GROUP 2 |
The Full Scale and Calibration values should be equal during the calibration procedure. The meter may be rescaled without calibrating by changing the full scale in GROUP 1, FUNCTION 0 or 1. (See Table
TABLE
CALIBRATION TYPE/ | CALIB. SOURCE | FULL SCALE SETTING | CALIBRATION VALUE |
RANGES | NECESSARY |
|
|
VOLTS 120/208V | 120V | 120V | 120 |
VOLTS 277/480V | 300V | 300V | 300 |
VOLTS 4/1 PT | 120V | 480V | 480 |
VOLTS 60/1 PT | 120V | 7.20KV | 7.20 |
AMPS Hi End 1000/5 CT | 5A | 1000A | 1000 |
AMPS Hi End 5000/5 CT | 5A | 5.00KA | 5.00 |
AMPS Lo End 1000/5 CT | 2.5A |
| 500 |
AMPS Lo End 5000/5 CT | 2.5A |
| 2.50 |
|
|