GE EPM 3000P instruction manual Phase Reversal, Percent Phase Imbalance

Page 43

CHAPTER 11

PROGRAMMING GROUP 7: PHASE REVERSAL & PHASE IMBALANCE SET LIMITS/RELAYS

11.1VOLTAGE PHASE REVERSAL AND PHASE IMBALANCE

The set limit alerts the user of an unbalanced or a reversed phase in a Three-phase System. The EPM3000P has two options for this purpose.

PHASE REVERSAL:

Activates when a reversed phase enters the EPM3000P’s metering system.

PERCENT PHASE IMBALANCE:

Activates when the user’s present value percent phase imbalance is exceeded. For example: an unbalanced Three- phase System.

DIAGRAM 11.1: EXAMPLE OF SET LIMITS

1 0 .0 %

L im its T rig g e re d

 

 

P H A S E

 

L im its N o t

IM B A L A N C E

 

(% )

 

T rig g e re d

 

1 0 :0 0 A M

1 1 :0 0 A M

T H R E E P H A S E S Y S T E M IM B A L A N C E

11.2TRIP RELAY

NOTE: THE -NLOPTION MUST BE PURCHASED TO HAVE RELAYS TRIGGERED FROM LIMIT CONDITIONS.

The EPM3000P has two Relays. These relays are linked through the program to Set Limits LM1 and LM2. The user can program above or below set limits for every reading. When a measurement exceeds a particular value, the set limit triggers and alerts the user. Each relay has provisions for a separate delay time (see Chapter 8).

cTRIP RELAY I dTRIP RELAY II eLEVEL

Whether to trip Relay 1. Whether to trip Relay 2.

The level at which the warning mechanism trips. Percentage of voltage imbalance is entered for setup level.

-OR-

fENABLE/DISABLE In the event of Phase Reversal, indicates whether to enable or disable phase reversal detection.

TABLE 11-0: GROUP 7 PROGRAMMING FORMAT

FUNCTION NUMBER

FUNCTION

0.

Voltage Phase Reversal Detection

1.

Voltage Phase Imbalance

E.

Exit Programming GROUP 7

38

GE Industrial Systems

Image 43
Contents EPM 3000P All Rights Reserved Customer Service and Support Installation & O P E R a T I O N O G R a M M I N G Mechanical Installation Installation & OperationPort Mechanical InstallationCT Size VA Maximum Distance CT to EPM3000P Electrical InstallationElectrical Installation Listing of Connection DiagramsWith 2 CTs and 2 PTs With Direct Voltage and CTsWith 3 CTs and 2 PTs III. Open Delta PT ConnectionThree Phase System Wye System with PTs Back View DUAL-PHASECOM RS-232C Communication InstallationRS-485 Communication Installation RS-485 Hookup Diagram 2 wire Half DuplexRS-485 Hookup Diagram 2 wire Half Duplex Detail View Volts Amps EPM3000P Overview‰ Protected Reset ‰ Unprotected ResetEPM3000P Overview Voltage Phase Imbalance Limit Voltage Phase ReversalI000 Access OperationÖTo Print the Programming DATA, follow these steps 222300.0 GROUPS, Functions, and Switch Packs General Procedure OverviewStandard Numeric Data Entry General Procedure OverviewPassword Used for555 Entering the Programming ModeFunction Number Programming Group 0 Global Meter Setup020 Global Meter SetupI20 Pack Switch Feature Segment Position 03.0 Computer Controlled Dedicated AlarmS E T I25 Input Voltage PT Ratio Full Scale Programming GroupInput Current CT Type Full Scale Programming Group I50Volts 4/1 PT To change the CALIBRATION, follow these steps Programming Group 2 Meter Calibration250 10.1 Programming Group 4 SET Limits & Relays LM1 LED LM2 LED ABOVE/BELOW Relay Value Set Limits & Relays LM1 LED LM2 LED ABOVE/ below Relay Level ÖTo program Limits or RELAYS, follow these steps Set Limits and RelaysSee to Exit Percent Phase Imbalance Phase ReversalÖTo change the Phase Reversal settings, follow these steps Phase Reversal & Phase Imbalance Set Limits/RelaysI0.0 If YOU are Located AT Exiting the Programming Mode