CHAPTER 11
PROGRAMMING GROUP 7: PHASE REVERSAL & PHASE IMBALANCE SET LIMITS/RELAYS
11.1VOLTAGE PHASE REVERSAL AND PHASE IMBALANCE
The set limit alerts the user of an unbalanced or a reversed phase in a
PHASE REVERSAL:
Activates when a reversed phase enters the EPM3000P’s metering system.
PERCENT PHASE IMBALANCE:
Activates when the user’s present value percent phase imbalance is exceeded. For example: an unbalanced Three- phase System.
DIAGRAM 11.1: EXAMPLE OF SET LIMITS
1 0 .0 % | L im its T rig g e re d | |
|
| |
P H A S E |
| L im its N o t |
IM B A L A N C E |
| |
(% ) |
| T rig g e re d |
| 1 0 :0 0 A M | 1 1 :0 0 A M |
T H R E E P H A S E S Y S T E M IM B A L A N C E |
11.2TRIP RELAY
NOTE: THE
The EPM3000P has two Relays. These relays are linked through the program to Set Limits LM1 and LM2. The user can program above or below set limits for every reading. When a measurement exceeds a particular value, the set limit triggers and alerts the user. Each relay has provisions for a separate delay time (see Chapter 8).
cTRIP RELAY I dTRIP RELAY II eLEVEL
Whether to trip Relay 1. Whether to trip Relay 2.
The level at which the warning mechanism trips. Percentage of voltage imbalance is entered for setup level.
fENABLE/DISABLE In the event of Phase Reversal, indicates whether to enable or disable phase reversal detection.
TABLE
FUNCTION NUMBER | FUNCTION |
0. | Voltage Phase Reversal Detection |
1. | Voltage Phase Imbalance |
E. | Exit Programming GROUP 7 |
38
GE Industrial Systems