Charging

Charging

Charging

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set for each indoor line.

Any time total line set is used either shorter or longer then the nominal 15m(50ft) line set length the refrigerant charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are either added or removed based on 20g/m(0.22oz/ft) of R-410A per meter(foot).

 

Max total length

 

 

Max Elevation

Max elevation

Additional

 

Max length of

Min length of

between each indoor

Capacity (Btu/h)

of all pipes

between indoor

 

(A+B)

each pipe (A/B)

each pipe (A/B)

unit and outdoor unit

units (h2)

Refrigerant

 

 

 

(h1)

 

 

 

 

 

 

 

18k

30m(100ft)

15m(50ft)

5m(16ft)

7.5m(25ft)

7.5m(25ft)

20g/m(0.22oz/ft)

 

 

 

 

 

 

 

Example: A 75ft line set is used for dual - zone 25 additional ft X 0.22 ounces per foot= add 5.5 ounces of R- 410A

Important:(Unit is critically charge)

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit name- plate charge adjusting for line sets longer or shorter than 7.5m(25ft) for each indoor unit.

Service Manual 33

Image 33
Contents HEAT CONTROLLER, INC Only for authorized service personnelWall Mounted Multi-SplitSystem Air Conditioning/Heat PumpTABLE OF CONTENTS 2Multi type Air ConditionerService Manual SymbolsUsedinthisManualCombination table Combination tableInstallation Safety PrecautionsSafety Precautions 4Multi type Air ConditionerSafety Precautions Do not install, remove, or reService Manual Safety Precautions 6Multi type Air ConditionerWhen the product is soaked an Authorized Service CenterSafety Precautions InstallationInstall the drain hose to ensure that installing the productOperational 8Multi type Air ConditionerSafety Precautions Service Manual Safety Precautions•Be careful and avoid personal injury •They may burn or explodeDimensions DimensionsIndoorUnit Split Type IndoorDimensions OutdoorUnitService Manual UE 18kBtu/hProduct Specifications Product Specifications12Multi type Air Conditioner Outdoor UnitService Manual Product SpecificationsIndoor Unit B-DMH18DB-1InstallationParts InstallationInstallationTools InstallationInstallation Select the best locationRooftop Installations Indoor unit16Multi type Air Conditioner Piping length and elevationInstallation Multi Piping TypeFixing Installation Plate InstallationService Manual Flaringwork Flaring Work and Connection of PipingFlaring Work and Connection of Piping 18Multi type Air ConditionerFor right rear piping Connecting the PipingService Manual Flaring Work and Connection of PipingFlaring Work and Connection of Piping 20Multi type Air ConditionerFor left rear piping Service ManualFlaring Work and Connection of Piping 22Multi type Air Conditioner Indoor unit installationFlaring Work and Connection of Piping REMOTE CONTROL PREPARATIONOPTIONAL HOW TO MOUNT ONTO A WALL HOW TO INSERT BATTERIESFlaring Work and Connection of Piping 24Multi type Air Conditioner Flaring Work and Connection of PipingOutdoor Service Manual Connectthe cabletotheIndoorunitFlaring Work and Connection of Piping Line voltage 208~230VConnectthe cabletotheOutdoor unit 26Multi type Air ConditionerEvery wire must be connected firmly Connectionmethod ofthe connectingcableExample How to connect wiring to the terminalsService Manual Connectthecable totheindoorunit 28Multi type Air Conditionerrating on the unit rating plate Service Manual CheckingthedrainageTo check the drainage Drain piping30Multi type Air Conditioner Formingthe pipingAir Purging and Evacuation Service ManualCheckingmethod Air Purging and Evacuation32Multi type Air Conditioner EvacuationRepeat evacuation procedure for each indoor unit Finishing the jobCharging ChargingImportant:Unit is critically charge Test Running Test Running34Multi type Air Conditioner Prepare remote controlFunctionofcontrol Operation1. MAIN UNIT FUNCTION OperationOperation 36Multi type Air ConditionerDefrost ControlHeating Fuzzy OperationOff-TimerOperation On-TimerOperationService Manual OperationOff-Timer = On-TimerOperation 38Multi type Air ConditionerSleep Timer Operation OperationOperation Service ManualForced Operation Buzzer Sounding Operation40Multi type Air Conditioner FunctionofIndoorUnitOperation ON/OFF by Remote controller Time Delay Safety ControlService Manual FunctionofOutdoor UnitOperation Operating Step42Multi type Air Conditioner RemoteControlOperationSETTING BUTTONS 7ON/OFF TIMER BUTTONSDisassembly DisassemblyIndoor Unit To remove the Grille from the ChassisDisassembly 44Multi type Air Conditioner2. To remove the Control Box 3.To remove the Discharge GrilleDisassembly Service Manual5.To remove the Motor Cover 6.To remove the Cross-FlowFanSchematic Diagram Schematic DiagramElectronicControlDevice 1.Indoor Unit2. Outdoor Unit Schematic DiagramTMP87CM41F Schematic Diagram 48 Multi type Air Conditioner1. Room Type Indoor Unit 2. Outdoor Unit Wiring DiagramSchematic Diagram Service Manual1. Indoor Unit ComponentsLocations•TOP VIEW • BOTTOM VIEW2. Display ASSEMBLY 1 Split Type 6871A20682A Schematic Diagram52Multi type Air Conditioner 3. Outdoor UnitSchematic Diagram 1 Component side2 Solder side Schematic DiagramRefrigerationCycleDiagram Troubleshooting GuideTroubleshooting Guide 54Multi type Air ConditionerOutdoor Error Indoor ErrorSelf-diagnosisFunction Troubleshooting GuideTrouble analysis CycleTroubleshooting Guide56Multi type Air Conditioner Troubleshooting GuideTrouble ElectronicPartsTroubleshooting GuideThe Product doesn’t operate at all Troubleshooting Guide58Multi type Air Conditioner Product doesnt operate with the remote controllerTroubleshooting Guide TroubleTroubleshooting Guide The Compressor/Outdoor Fan are dont operateService Manual TroubleWhen indoor Fan does not operate Trouble 4 When indoor Fan does not operate60Multi type Air Conditioner Troubleshooting GuideWhen Vertical Louver does not operate Trouble 5 When the louver does not operateTroubleshooting Guide Service Manual62Multi type Air Conditioner ErrorCodeTroubleshooting Guide Trouble ShootingPower input AC 230V.Outdoor, Indoor Troubleshooting Guide• The connecting wires are misconnected TitleTroubleshooting Guide 64Multi type Air ConditionerError Cause of errorTroubleshooting Guide Service ManualCause of error Title2-way, 3-wayValve 2-way, 3-wayValve66Multi type Air Conditioner 2-wayValve Liguid SideService Manual 1 Pumping down2-way, 3-wayValve 2.Operate the unit for 10 to 15 minutes68Multi type Air Conditioner 2 Evacuation7.Mount the valve caps and the service port caps 2-way, 3-wayValveService Manual 3 Gas Charging2-way, 3-wayValve After Evacuation1900 WELLWORTH AVENUE • JACKSON, MICHIGAN HEAT CONTROLLER, INCTHE QUALITY LEADER IN CONDITIONING AIR 05/15/07