Heat Controller DMH18DB-1 manual 36Multi type Air Conditioner, Operation, Defrost ControlHeating

Page 36
■Defrost Control(Heating)

Operation

27°C(80.6°F), it operates with Super-Low(while in sleep mode, with the medium airflow speed).

While compressor off, the indoor fan is off when the indoor pipe temp is below 33°C(91.4°F), when above 35°C(95°F) , it operates with the low airflow speed.

While in defrost control, the indoor is outdoor fans are turned off.

Defrost Control(Heating)

Defrost operation is controlled by timer and sensing temperature of outdoor pipe.

The first defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes passed from starting of heating operation and more than 4 minutes operation of compressor.

Defrost ends after 12 minutes passed from starting of defrost operation when the outdoor pipe temperature rises over 15°C(59°F) even before 12 minutes.

The second defrost starts only when the outdoor pipe temperature falls below -6°C(21.2°F) after 35 minutes passed from ending of the first defrost and more than 4 minutes operation of compressor.

Fuzzy Operation

When any of operation mode is not selected like the moment of the power on or when 3 hrs has passed since the operation off, the operation mode is selected.

When determining the operation mode, the compressor, the outdoor fan, and the 4 way valve are off and only the indoor fan is operated for 15 seconds. Then an operation mode is selected according to the intake air temp at that moment as follows.

24°C(75.2°F) Intake Air Temp

Fuzzy Operation for Cooling

21°C(69.8°F) Intake Air Temp<24°C(75.2°F)

Fuzzy Operation for Dehumidification

Intake Air Temp<21°C(69.8°F)

Fuzzy Operation for Heating

If any of the operation modes among cooling / dehumidification / heating mode operations is carried out for 10 sec or longer before Fuzzy operation, the mode before Fuzzy operation is operated.

1)Fuzzy Operation for Cooling

According to the setting temperature selected by Fuzzy rule, when the intake air temp is 0.5°C(0.9°F) or more

below the setting temp, the compressor is turned off. When 0.5°C(0.9°F) or more above the setting temp, the

compressor is turned on.

 

Compressor ON Temp

Setting Temp +0.5°C(0.9°F)

Compressor OFF Temp

Setting Temp + 0.5°C(0.9°F)

At the beginning of Fuzzy mode operation, the setting temperature is automatically selected according to the intake air temp at that time.

26°C(78.8°F)Intake Air Temp

25°C(77°F)

24°C(75.2°F)Intake Air Temp<26°C(78.8°F)

Intake Air Temp + 1°C(1.8°F)

22°C(71.6°F)Intake Air Temp<24°C(75.2°F)

Intake Air Temp + 0.5°C(0.9°F)

18°C(64.4°F)Intake Air Temp<22°C(71.6°F)

Intake Air Temp

Intake Air Temp<18°C(64.4°F)

18°C(64.4°F)

When the Fuzzy key (Temperature Control key) is input after the initial setting temperature is selected, the Fuzzy key value and the intake air temperature at that time are compared to select the setting temperature automatically according to the Fuzzy rule.

While in Fuzzy operation, the airflow speed of the indoor fan is automatically selected according to the temper- ature.

36Multi type Air Conditioner

Image 36
Contents Only for authorized service personnel HEAT CONTROLLER, INCWall Mounted Multi-SplitSystem Air Conditioning/Heat Pump2Multi type Air Conditioner TABLE OF CONTENTSSymbolsUsedinthisManual Service ManualCombination table Combination tableSafety Precautions InstallationSafety Precautions 4Multi type Air ConditionerSafety Precautions Do not install, remove, or reService Manual 6Multi type Air Conditioner Safety PrecautionsWhen the product is soaked an Authorized Service CenterInstallation Safety PrecautionsInstall the drain hose to ensure that installing the productOperational 8Multi type Air ConditionerSafety Precautions Safety Precautions Service Manual•Be careful and avoid personal injury •They may burn or explodeDimensions DimensionsIndoorUnit Split Type IndoorOutdoorUnit DimensionsService Manual UE 18kBtu/hProduct Specifications Product Specifications12Multi type Air Conditioner Outdoor UnitProduct Specifications Service ManualIndoor Unit B-DMH18DB-1Installation InstallationPartsInstallationTools InstallationSelect the best location InstallationRooftop Installations Indoor unitPiping length and elevation 16Multi type Air ConditionerInstallation Multi Piping TypeFixing Installation Plate InstallationService Manual Flaring Work and Connection of Piping FlaringworkFlaring Work and Connection of Piping 18Multi type Air ConditionerConnecting the Piping For right rear pipingService Manual Flaring Work and Connection of Piping20Multi type Air Conditioner Flaring Work and Connection of PipingFor left rear piping Service ManualFlaring Work and Connection of Piping 22Multi type Air Conditioner Indoor unit installationFlaring Work and Connection of Piping REMOTE CONTROL PREPARATIONOPTIONAL HOW TO MOUNT ONTO A WALL HOW TO INSERT BATTERIESFlaring Work and Connection of Piping 24Multi type Air Conditioner Flaring Work and Connection of PipingOutdoor Connectthe cabletotheIndoorunit Service ManualFlaring Work and Connection of Piping Line voltage 208~230VConnectthe cabletotheOutdoor unit 26Multi type Air ConditionerEvery wire must be connected firmly Connectionmethod ofthe connectingcableExample How to connect wiring to the terminalsService Manual Connectthecable totheindoorunit 28Multi type Air Conditionerrating on the unit rating plate Checkingthedrainage Service ManualTo check the drainage Drain pipingFormingthe piping 30Multi type Air ConditionerService Manual Air Purging and EvacuationCheckingmethod Air Purging and EvacuationEvacuation 32Multi type Air ConditionerRepeat evacuation procedure for each indoor unit Finishing the jobCharging ChargingImportant:Unit is critically charge Test Running Test Running34Multi type Air Conditioner Prepare remote controlOperation Functionofcontrol1. MAIN UNIT FUNCTION Operation36Multi type Air Conditioner OperationDefrost ControlHeating Fuzzy OperationOn-TimerOperation Off-TimerOperationService Manual Operation38Multi type Air Conditioner Off-Timer = On-TimerOperationSleep Timer Operation OperationService Manual OperationForced Operation Buzzer Sounding OperationFunctionofIndoorUnit 40Multi type Air ConditionerOperation ON/OFF by Remote controller Time Delay Safety ControlFunctionofOutdoor Unit Service ManualOperation Operating StepRemoteControlOperation 42Multi type Air ConditionerSETTING BUTTONS 7ON/OFF TIMER BUTTONSDisassembly DisassemblyIndoor Unit To remove the Grille from the Chassis44Multi type Air Conditioner Disassembly2. To remove the Control Box 3.To remove the Discharge GrilleService Manual Disassembly5.To remove the Motor Cover 6.To remove the Cross-FlowFanSchematic Diagram Schematic DiagramElectronicControlDevice 1.Indoor Unit2. Outdoor Unit Schematic DiagramTMP87CM41F 48 Multi type Air Conditioner Schematic DiagramWiring Diagram 1. Room Type Indoor Unit 2. Outdoor UnitSchematic Diagram Service ManualComponentsLocations 1. Indoor Unit•TOP VIEW • BOTTOM VIEWSchematic Diagram 2. Display ASSEMBLY 1 Split Type 6871A20682A3. Outdoor Unit 52Multi type Air ConditionerSchematic Diagram 1 Component sideSchematic Diagram 2 Solder sideTroubleshooting Guide RefrigerationCycleDiagramTroubleshooting Guide 54Multi type Air ConditionerIndoor Error Outdoor ErrorSelf-diagnosisFunction Troubleshooting GuideCycleTroubleshooting Guide Trouble analysis56Multi type Air Conditioner Troubleshooting GuideElectronicPartsTroubleshooting Guide TroubleThe Product doesn’t operate at all Troubleshooting GuideProduct doesnt operate with the remote controller 58Multi type Air ConditionerTroubleshooting Guide TroubleThe Compressor/Outdoor Fan are dont operate Troubleshooting GuideService Manual TroubleTrouble 4 When indoor Fan does not operate When indoor Fan does not operate60Multi type Air Conditioner Troubleshooting GuideTrouble 5 When the louver does not operate When Vertical Louver does not operateTroubleshooting Guide Service ManualErrorCode 62Multi type Air ConditionerTroubleshooting Guide Trouble ShootingTroubleshooting Guide Power input AC 230V.Outdoor, Indoor• The connecting wires are misconnected Title64Multi type Air Conditioner Troubleshooting GuideError Cause of errorService Manual Troubleshooting GuideCause of error Title2-way, 3-wayValve 2-way, 3-wayValve66Multi type Air Conditioner 2-wayValve Liguid Side1 Pumping down Service Manual2-way, 3-wayValve 2.Operate the unit for 10 to 15 minutes2 Evacuation 68Multi type Air Conditioner7.Mount the valve caps and the service port caps 2-way, 3-wayValve3 Gas Charging Service Manual2-way, 3-wayValve After EvacuationHEAT CONTROLLER, INC 1900 WELLWORTH AVENUE • JACKSON, MICHIGANTHE QUALITY LEADER IN CONDITIONING AIR 05/15/07