Heat Controller DMH18DB-1 manual Air Purging and Evacuation, Checkingmethod, Service Manual

Page 31
Air Purging and Evacuation

Air Purging and Evacuation

Air Purging and Evacuation

Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.

1.Pressure in the system rises.

2.Operating current rises.

3.Cooling(or heating) efficiency drops.

4.Moisture in the refrigerant circuit may freeze and block capillary tubing.

5.Water may lead to corrosion of parts in the refrigeration system.

Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.

CheckingmethodService ManualCheckingManual backgroundmethodManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

Preparation

Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test run has been complet- ed. Remove the service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the liq- uid and the gas side service valves on the outdoor unit are kept closed at this stage.

Leakage test

1.Do a leakage test of all joints of the tubing(both indoor and outdoor) and both gas and liquid side ser- vice valves.

Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.

2.After the system is found to be free of leaks, relieve the nitrogen pressure by loosening the charge hose connector at the nitrogen cylinder. When the system pressure is reduced to normal, disconnect the hose from the cylinder.

• Connect the manifold valve(with pressure gauges) and dry

 

 

 

 

nitrogen gas cylinder to this service port with charge

 

 

 

 

hoses.

 

 

 

 

CAUTION: Be sure to use a manifold

 

 

 

 

valve for leak testing.

 

 

Indoor unit

 

The high side manifold valve must always

 

 

 

 

be kept closed.

 

 

 

 

• Pressurize the system to no more than 150 P.S.I.G.

Outdoor unit

 

 

with dry nitrogen gas and close the cylinder valve

 

 

 

 

when the gauge reading reached 150 P.S.I.G. Next,

 

 

 

 

test for leaks with liquid soap.

 

 

 

 

CAUTION: To avoid nitrogen entering the

 

 

 

 

refrigerant system in a liquid state, the top

Manifold valve

 

of the cylinder must be higher than its bottom

 

when you pressurize the system. Usually, the

Pressure

Lo

Hi

 

cylinder is used in a vertical standing position.

gauge

 

 

 

 

 

 

 

NOTICE : Leakage test shoud be done for each

 

 

Charge hose

 

 

 

 

 

indoor unit connection set, separately.

 

 

 

 

 

 

 

Nitrogen gas

 

 

 

 

cylinder(in vertical

 

 

 

 

standing position)

 

 

 

 

Service Manual

31

Image 31
Contents Air Conditioning/Heat Pump Only for authorized service personnelHEAT CONTROLLER, INC Wall Mounted Multi-SplitSystemTABLE OF CONTENTS 2Multi type Air ConditionerCombination table SymbolsUsedinthisManualService Manual Combination table4Multi type Air Conditioner Safety PrecautionsInstallation Safety PrecautionsDo not install, remove, or re Safety PrecautionsService Manual an Authorized Service Center 6Multi type Air ConditionerSafety Precautions When the product is soakedinstalling the product InstallationSafety Precautions Install the drain hose to ensure that8Multi type Air Conditioner OperationalSafety Precautions •They may burn or explode Safety PrecautionsService Manual •Be careful and avoid personal injurySplit Type Indoor DimensionsDimensions IndoorUnitUE 18kBtu/h OutdoorUnitDimensions Service ManualOutdoor Unit Product SpecificationsProduct Specifications 12Multi type Air ConditionerB-DMH18DB-1 Product SpecificationsService Manual Indoor UnitInstallation InstallationInstallationParts InstallationToolsIndoor unit Select the best locationInstallation Rooftop InstallationsMulti Piping Type Piping length and elevation16Multi type Air Conditioner InstallationInstallation Fixing Installation PlateService Manual 18Multi type Air Conditioner Flaring Work and Connection of PipingFlaringwork Flaring Work and Connection of PipingFlaring Work and Connection of Piping Connecting the PipingFor right rear piping Service ManualFlaring Work and Connection of Piping 20Multi type Air ConditionerService Manual For left rear pipingFlaring Work and Connection of Piping Indoor unit installation 22Multi type Air ConditionerFlaring Work and Connection of Piping HOW TO MOUNT ONTO A WALL HOW TO INSERT BATTERIES REMOTE CONTROL PREPARATIONOPTIONALFlaring Work and Connection of Piping Flaring Work and Connection of Piping 24Multi type Air ConditionerOutdoor Line voltage 208~230V Connectthe cabletotheIndoorunitService Manual Flaring Work and Connection of Piping26Multi type Air Conditioner Connectthe cabletotheOutdoor unitEvery wire must be connected firmly How to connect wiring to the terminals Connectionmethod ofthe connectingcableExampleService Manual 28Multi type Air Conditioner Connectthecable totheindoorunitrating on the unit rating plate Drain piping CheckingthedrainageService Manual To check the drainage30Multi type Air Conditioner Formingthe pipingAir Purging and Evacuation Service ManualAir Purging and Evacuation CheckingmethodFinishing the job Evacuation32Multi type Air Conditioner Repeat evacuation procedure for each indoor unitCharging ChargingImportant:Unit is critically charge Prepare remote control Test RunningTest Running 34Multi type Air ConditionerOperation OperationFunctionofcontrol 1. MAIN UNIT FUNCTIONFuzzy Operation 36Multi type Air ConditionerOperation Defrost ControlHeatingOperation On-TimerOperationOff-TimerOperation Service ManualOperation 38Multi type Air ConditionerOff-Timer = On-TimerOperation Sleep Timer OperationBuzzer Sounding Operation Service ManualOperation Forced OperationTime Delay Safety Control FunctionofIndoorUnit40Multi type Air Conditioner Operation ON/OFF by Remote controllerOperating Step FunctionofOutdoor UnitService Manual Operation7ON/OFF TIMER BUTTONS RemoteControlOperation42Multi type Air Conditioner SETTING BUTTONSTo remove the Grille from the Chassis DisassemblyDisassembly Indoor Unit3.To remove the Discharge Grille 44Multi type Air ConditionerDisassembly 2. To remove the Control Box6.To remove the Cross-FlowFan Service ManualDisassembly 5.To remove the Motor Cover1.Indoor Unit Schematic DiagramSchematic Diagram ElectronicControlDeviceSchematic Diagram 2. Outdoor UnitTMP87CM41F Schematic Diagram 48 Multi type Air ConditionerService Manual Wiring Diagram1. Room Type Indoor Unit 2. Outdoor Unit Schematic Diagram• BOTTOM VIEW ComponentsLocations1. Indoor Unit •TOP VIEW2. Display ASSEMBLY 1 Split Type 6871A20682A Schematic Diagram1 Component side 3. Outdoor Unit52Multi type Air Conditioner Schematic Diagram2 Solder side Schematic Diagram54Multi type Air Conditioner Troubleshooting GuideRefrigerationCycleDiagram Troubleshooting GuideTroubleshooting Guide Indoor ErrorOutdoor Error Self-diagnosisFunctionTroubleshooting Guide CycleTroubleshooting GuideTrouble analysis 56Multi type Air ConditionerTroubleshooting Guide ElectronicPartsTroubleshooting GuideTrouble The Product doesn’t operate at allTrouble Product doesnt operate with the remote controller58Multi type Air Conditioner Troubleshooting GuideTrouble The Compressor/Outdoor Fan are dont operateTroubleshooting Guide Service ManualTroubleshooting Guide Trouble 4 When indoor Fan does not operateWhen indoor Fan does not operate 60Multi type Air ConditionerService Manual Trouble 5 When the louver does not operateWhen Vertical Louver does not operate Troubleshooting GuideTrouble Shooting ErrorCode62Multi type Air Conditioner Troubleshooting GuideTitle Troubleshooting GuidePower input AC 230V.Outdoor, Indoor • The connecting wires are misconnectedCause of error 64Multi type Air ConditionerTroubleshooting Guide ErrorTitle Service ManualTroubleshooting Guide Cause of error2-wayValve Liguid Side 2-way, 3-wayValve2-way, 3-wayValve 66Multi type Air Conditioner2.Operate the unit for 10 to 15 minutes 1 Pumping downService Manual 2-way, 3-wayValve2-way, 3-wayValve 2 Evacuation68Multi type Air Conditioner 7.Mount the valve caps and the service port capsAfter Evacuation 3 Gas ChargingService Manual 2-way, 3-wayValve05/15/07 HEAT CONTROLLER, INC1900 WELLWORTH AVENUE • JACKSON, MICHIGAN THE QUALITY LEADER IN CONDITIONING AIR