Heat Controller DMH18DB-1 manual Functionofcontrol, Main Unit Function, Operation Indicator

Page 35
Operation

Operation

Operation

Functionofcontrol1. MAIN UNIT FUNCTIONFunctionOperation IndicatorofSleep Timer IndicatorcontrolTimer IndicatorDefrost IndicatorManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual backgroundManual background

1. MAIN UNIT FUNCTION

DISPLAY

Operation Indicator

On while in appliance operation, off while in appliance pause

Flashing while in disconnection or short in Thermistor (3 sec off / 0.5 sec on)

Sleep Timer Indicator

On while in sleep timer mode, off when sleep timer cancel or appliance operation pause

Timer Indicator

On while in timer mode (on/off), off when timer mode is completed or canceled

Defrost Indicator

Off except when hot start during heating mode operation or while in defrost control

Cooling Mode Operation

When the intake air temperature reaches 0.5°C(0.9°F) below the setting temp, the compressor and the outdoor fan stop.

When it reaches 0.5°C(0.9°F) above the setting temp, they start to operate again.

Compressor ON Temp

Setting Temp+0.5°C(0.9°F)

Compressor OFF Temp

Setting Temp-0.5°C(0.9°F)

While in compressor running, operating with the airflow speed set by the remote control. While compressor is off fan operates at low speed regardless of the setting.

Soft Dry Operation Mode

When the dehumidification operation input by the remote control is received, the intake air temperature is detected and the setting temp is automatically set according to the intake air temperature.

26°C(78.8°F) Intake Air Temp

25°C(77°F)

24°C(75.2°F) Intake Intake Air Temp<26°C(78.8°F)

Intake Air Temp-1°C(30.2°F)

18°C(64.4°F) Intake Intake Air Temp<24°C(75.2°F)

Intake Air Temp-0.5°C(31.1°F)

Intake Air Temp<18°C(64.4°F)

18°C(64.4°F)

While compressor off, the indoor fan repeats low airflow speed and stop.

While the intake air temp is between compressor on temp. and compressor off temp., 10-min dehumidification operation and 4-min compressor off repeat.

Compressor ON Temp. Setting Temp+0.5°C(0.9°F) Compressor OFF Temp. Setting Temp-0.5°C(0.9°F)

In 10-min dehumidification operation, the indoor fan operates with the low airflow speed.

Heating Mode Operation

When the intake air temp reaches +3°(37.4°F)…above the setting temp, the compressor is turned off. When below the setting temp, the compressor is turned on.

Compressor ON Temp. Setting Temp. Compressor OFF Temp. Setting Temp.+3°C(37.4°F)

While compressor on, the indoor fan is off when the indoor pipe temp. is below 20°C(68°F), when above

27°C(80.6°F) , it operates with the low or setting speed. When the indoor pipe temp is between 20°C(68°F) and

Service Manual 35

Image 35
Contents Air Conditioning/Heat Pump Only for authorized service personnelHEAT CONTROLLER, INC Wall Mounted Multi-SplitSystemTABLE OF CONTENTS 2Multi type Air ConditionerCombination table SymbolsUsedinthisManualService Manual Combination table4Multi type Air Conditioner Safety PrecautionsInstallation Safety PrecautionsService Manual Safety PrecautionsDo not install, remove, or re an Authorized Service Center 6Multi type Air ConditionerSafety Precautions When the product is soakedinstalling the product InstallationSafety Precautions Install the drain hose to ensure thatSafety Precautions Operational8Multi type Air Conditioner •They may burn or explode Safety PrecautionsService Manual •Be careful and avoid personal injurySplit Type Indoor DimensionsDimensions IndoorUnitUE 18kBtu/h OutdoorUnitDimensions Service ManualOutdoor Unit Product SpecificationsProduct Specifications 12Multi type Air ConditionerB-DMH18DB-1 Product SpecificationsService Manual Indoor UnitInstallation InstallationInstallationParts InstallationToolsIndoor unit Select the best locationInstallation Rooftop InstallationsMulti Piping Type Piping length and elevation16Multi type Air Conditioner InstallationService Manual Fixing Installation PlateInstallation 18Multi type Air Conditioner Flaring Work and Connection of PipingFlaringwork Flaring Work and Connection of PipingFlaring Work and Connection of Piping Connecting the PipingFor right rear piping Service ManualFlaring Work and Connection of Piping 20Multi type Air ConditionerFlaring Work and Connection of Piping For left rear pipingService Manual Flaring Work and Connection of Piping 22Multi type Air ConditionerIndoor unit installation Flaring Work and Connection of Piping REMOTE CONTROL PREPARATIONOPTIONALHOW TO MOUNT ONTO A WALL HOW TO INSERT BATTERIES Outdoor 24Multi type Air ConditionerFlaring Work and Connection of Piping Line voltage 208~230V Connectthe cabletotheIndoorunitService Manual Flaring Work and Connection of PipingEvery wire must be connected firmly Connectthe cabletotheOutdoor unit26Multi type Air Conditioner Service Manual Connectionmethod ofthe connectingcableExampleHow to connect wiring to the terminals rating on the unit rating plate Connectthecable totheindoorunit28Multi type Air Conditioner Drain piping CheckingthedrainageService Manual To check the drainage30Multi type Air Conditioner Formingthe pipingAir Purging and Evacuation Service ManualAir Purging and Evacuation CheckingmethodFinishing the job Evacuation32Multi type Air Conditioner Repeat evacuation procedure for each indoor unitImportant:Unit is critically charge ChargingCharging Prepare remote control Test RunningTest Running 34Multi type Air ConditionerOperation OperationFunctionofcontrol 1. MAIN UNIT FUNCTIONFuzzy Operation 36Multi type Air ConditionerOperation Defrost ControlHeatingOperation On-TimerOperationOff-TimerOperation Service ManualOperation 38Multi type Air ConditionerOff-Timer = On-TimerOperation Sleep Timer OperationBuzzer Sounding Operation Service ManualOperation Forced OperationTime Delay Safety Control FunctionofIndoorUnit40Multi type Air Conditioner Operation ON/OFF by Remote controllerOperating Step FunctionofOutdoor UnitService Manual Operation7ON/OFF TIMER BUTTONS RemoteControlOperation42Multi type Air Conditioner SETTING BUTTONSTo remove the Grille from the Chassis DisassemblyDisassembly Indoor Unit3.To remove the Discharge Grille 44Multi type Air ConditionerDisassembly 2. To remove the Control Box6.To remove the Cross-FlowFan Service ManualDisassembly 5.To remove the Motor Cover1.Indoor Unit Schematic DiagramSchematic Diagram ElectronicControlDeviceTMP87CM41F 2. Outdoor UnitSchematic Diagram Schematic Diagram 48 Multi type Air ConditionerService Manual Wiring Diagram1. Room Type Indoor Unit 2. Outdoor Unit Schematic Diagram• BOTTOM VIEW ComponentsLocations1. Indoor Unit •TOP VIEW2. Display ASSEMBLY 1 Split Type 6871A20682A Schematic Diagram1 Component side 3. Outdoor Unit52Multi type Air Conditioner Schematic Diagram2 Solder side Schematic Diagram54Multi type Air Conditioner Troubleshooting GuideRefrigerationCycleDiagram Troubleshooting GuideTroubleshooting Guide Indoor ErrorOutdoor Error Self-diagnosisFunctionTroubleshooting Guide CycleTroubleshooting GuideTrouble analysis 56Multi type Air ConditionerTroubleshooting Guide ElectronicPartsTroubleshooting GuideTrouble The Product doesn’t operate at allTrouble Product doesnt operate with the remote controller58Multi type Air Conditioner Troubleshooting GuideTrouble The Compressor/Outdoor Fan are dont operateTroubleshooting Guide Service ManualTroubleshooting Guide Trouble 4 When indoor Fan does not operateWhen indoor Fan does not operate 60Multi type Air ConditionerService Manual Trouble 5 When the louver does not operateWhen Vertical Louver does not operate Troubleshooting GuideTrouble Shooting ErrorCode62Multi type Air Conditioner Troubleshooting GuideTitle Troubleshooting GuidePower input AC 230V.Outdoor, Indoor • The connecting wires are misconnectedCause of error 64Multi type Air ConditionerTroubleshooting Guide ErrorTitle Service ManualTroubleshooting Guide Cause of error2-wayValve Liguid Side 2-way, 3-wayValve2-way, 3-wayValve 66Multi type Air Conditioner2.Operate the unit for 10 to 15 minutes 1 Pumping downService Manual 2-way, 3-wayValve2-way, 3-wayValve 2 Evacuation68Multi type Air Conditioner 7.Mount the valve caps and the service port capsAfter Evacuation 3 Gas ChargingService Manual 2-way, 3-wayValve05/15/07 HEAT CONTROLLER, INC1900 WELLWORTH AVENUE • JACKSON, MICHIGAN THE QUALITY LEADER IN CONDITIONING AIR