Heat Controller DMH18DB-1 The Compressor/Outdoor Fan are dont operate, Trouble, Service Manual

Page 59
The Compressor/Outdoor Fan are don't operate

Troubleshooting Guide

Trouble 3

The Compressor/Outdoor Fan are don't operate

Turn on the main power.

Operate Cooling Mode by setting the disired temperature of the remote controller is less than one of the Indoor temperature by 1°C at least.

When in air circulation mode, compressor/outdoor fan is stopped.

Check the sensor for Indoor temperature is attatched as close as to be effected by the themperature of Heat Exchange (EVA.)

When the sensor circuit for Indoor temperature and connector are in bad connection or are not engaged, Compressor/Outdoor fan is stopped.

Check the related circuit of R01H(1K), R02H(1K), R03H(1K), R04H(1K), Micom(pin No. 74 ,

75 , 76 , 77 ).

Check the Indoor temperature sensor is disconnected or not (about 10K at 25°C).

Check the Relay(RY-PWR, RY-START) for driving Compressor.

Check the voltage between brown and blue cable of terminal to connect the Outdoor (About AC208V / 230V).

Check the related circuit of relay in Outdoor PCB Ass'y.

Check Point

Comp. ON

Comp. OFF

Between Micom(No. 50,51) and

DC 5V

DC 0V

GND

 

 

Between IC01M(No. 10) and

DC 1V

DC 12V

GND

 

 

 

 

 

Turn off main power.

Check the electrical wiring diagram of Outdoor side.

Check the open or short of connecting wires between Indoor and Outdoor.

Service Manual 59

Image 59
Contents Air Conditioning/Heat Pump Only for authorized service personnelHEAT CONTROLLER, INC Wall Mounted Multi-SplitSystemTABLE OF CONTENTS 2Multi type Air ConditionerCombination table SymbolsUsedinthisManualService Manual Combination table4Multi type Air Conditioner Safety PrecautionsInstallation Safety PrecautionsService Manual Safety PrecautionsDo not install, remove, or re an Authorized Service Center 6Multi type Air ConditionerSafety Precautions When the product is soakedinstalling the product InstallationSafety Precautions Install the drain hose to ensure thatSafety Precautions Operational8Multi type Air Conditioner •They may burn or explode Safety PrecautionsService Manual •Be careful and avoid personal injurySplit Type Indoor DimensionsDimensions IndoorUnitUE 18kBtu/h OutdoorUnitDimensions Service ManualOutdoor Unit Product SpecificationsProduct Specifications 12Multi type Air ConditionerB-DMH18DB-1 Product SpecificationsService Manual Indoor UnitInstallation InstallationInstallationParts InstallationToolsIndoor unit Select the best locationInstallation Rooftop InstallationsMulti Piping Type Piping length and elevation16Multi type Air Conditioner InstallationService Manual Fixing Installation PlateInstallation 18Multi type Air Conditioner Flaring Work and Connection of PipingFlaringwork Flaring Work and Connection of PipingFlaring Work and Connection of Piping Connecting the PipingFor right rear piping Service ManualFlaring Work and Connection of Piping 20Multi type Air ConditionerFlaring Work and Connection of Piping For left rear pipingService Manual Flaring Work and Connection of Piping 22Multi type Air ConditionerIndoor unit installation Flaring Work and Connection of Piping REMOTE CONTROL PREPARATIONOPTIONALHOW TO MOUNT ONTO A WALL HOW TO INSERT BATTERIES Outdoor 24Multi type Air ConditionerFlaring Work and Connection of Piping Line voltage 208~230V Connectthe cabletotheIndoorunitService Manual Flaring Work and Connection of PipingEvery wire must be connected firmly Connectthe cabletotheOutdoor unit26Multi type Air Conditioner Service Manual Connectionmethod ofthe connectingcableExampleHow to connect wiring to the terminals rating on the unit rating plate Connectthecable totheindoorunit28Multi type Air Conditioner Drain piping CheckingthedrainageService Manual To check the drainage30Multi type Air Conditioner Formingthe pipingAir Purging and Evacuation Service ManualAir Purging and Evacuation CheckingmethodFinishing the job Evacuation32Multi type Air Conditioner Repeat evacuation procedure for each indoor unitImportant:Unit is critically charge ChargingCharging Prepare remote control Test RunningTest Running 34Multi type Air ConditionerOperation OperationFunctionofcontrol 1. MAIN UNIT FUNCTIONFuzzy Operation 36Multi type Air ConditionerOperation Defrost ControlHeatingOperation On-TimerOperationOff-TimerOperation Service ManualOperation 38Multi type Air ConditionerOff-Timer = On-TimerOperation Sleep Timer OperationBuzzer Sounding Operation Service ManualOperation Forced OperationTime Delay Safety Control FunctionofIndoorUnit40Multi type Air Conditioner Operation ON/OFF by Remote controllerOperating Step FunctionofOutdoor UnitService Manual Operation7ON/OFF TIMER BUTTONS RemoteControlOperation42Multi type Air Conditioner SETTING BUTTONSTo remove the Grille from the Chassis DisassemblyDisassembly Indoor Unit3.To remove the Discharge Grille 44Multi type Air ConditionerDisassembly 2. To remove the Control Box6.To remove the Cross-FlowFan Service ManualDisassembly 5.To remove the Motor Cover1.Indoor Unit Schematic DiagramSchematic Diagram ElectronicControlDeviceTMP87CM41F 2. Outdoor UnitSchematic Diagram Schematic Diagram 48 Multi type Air ConditionerService Manual Wiring Diagram1. Room Type Indoor Unit 2. Outdoor Unit Schematic Diagram• BOTTOM VIEW ComponentsLocations1. Indoor Unit •TOP VIEW2. Display ASSEMBLY 1 Split Type 6871A20682A Schematic Diagram1 Component side 3. Outdoor Unit52Multi type Air Conditioner Schematic Diagram2 Solder side Schematic Diagram54Multi type Air Conditioner Troubleshooting GuideRefrigerationCycleDiagram Troubleshooting GuideTroubleshooting Guide Indoor ErrorOutdoor Error Self-diagnosisFunctionTroubleshooting Guide CycleTroubleshooting GuideTrouble analysis 56Multi type Air ConditionerTroubleshooting Guide ElectronicPartsTroubleshooting GuideTrouble The Product doesn’t operate at allTrouble Product doesnt operate with the remote controller58Multi type Air Conditioner Troubleshooting GuideTrouble The Compressor/Outdoor Fan are dont operateTroubleshooting Guide Service ManualTroubleshooting Guide Trouble 4 When indoor Fan does not operateWhen indoor Fan does not operate 60Multi type Air ConditionerService Manual Trouble 5 When the louver does not operateWhen Vertical Louver does not operate Troubleshooting GuideTrouble Shooting ErrorCode62Multi type Air Conditioner Troubleshooting GuideTitle Troubleshooting GuidePower input AC 230V.Outdoor, Indoor • The connecting wires are misconnectedCause of error 64Multi type Air ConditionerTroubleshooting Guide ErrorTitle Service ManualTroubleshooting Guide Cause of error2-wayValve Liguid Side 2-way, 3-wayValve2-way, 3-wayValve 66Multi type Air Conditioner2.Operate the unit for 10 to 15 minutes 1 Pumping downService Manual 2-way, 3-wayValve2-way, 3-wayValve 2 Evacuation68Multi type Air Conditioner 7.Mount the valve caps and the service port capsAfter Evacuation 3 Gas ChargingService Manual 2-way, 3-wayValve05/15/07 HEAT CONTROLLER, INC1900 WELLWORTH AVENUE • JACKSON, MICHIGAN THE QUALITY LEADER IN CONDITIONING AIR