System Start-Up
For proper unit function and safety, follow everything in this
PRE-START CHECK LIST
1.Disconnect and
2.Check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and accessories for tightness.
3.Rotate the fan wheel by hand and assure no parts are rubbing.
4.Check the
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit Size | G |
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| |
25 - 50 | 1/4 inch |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
| |
65 - 85 | 3/8 inch |
|
|
|
|
|
|
|
| |
|
|
| G |
|
| |||||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
Wheel Overlap Dimensions
special tools required
•Voltage Meter
•Tachometer
•Amperage Meter
1.Check Voltage
Before starting the unit, compare the supplied voltage with the unit’s nameplate voltage and the motor voltage. Units are not provided with thermal overload protection unless a control center has been ordered with the unit or the motor has been selected with thermal overload protection.
2. Check Blower Rotation
A common problem is wheel rotation in the wrong direction. For centrifugal fans, incorrect wheel rotation will provide poor air performance, motor overloading and possible burnout. Rotation should be checked while the fan is coasting to a stop. Proper wheel rotation is shown.
R |
|
| R |
|
|
ot |
| ot |
| ||
| a |
| a | ||
|
| ti |
|
| ti |
|
| o |
|
| o |
|
| n |
|
| n |
BackwardForward
InclinedCurved
Proper Wheel Rotation
When connecting a
any two supply power connections will reverse the direction of rotation.
To reverse the rotation, turn the power off and use the following procedure:
•For single phase units, rewire the motor per the instructions on the motor.
•For three phase units, interchange any two power leads. This can be done at the motor starter.
3.Check for Vibration
Check for unusual noise, vibration or overheating of bearings. Excessive vibration may be experienced during initial
to other parts of the building by the ductwork. To eliminate this undesirable effect, Greenheck has used a heavy canvas connection between the scroll and the discharge of the fan. If noise is an issue, we recommend using heavy canvas connections on the inlet of the fan. Refer to the Troubleshooting section of this manual if a problem develops.
4. Air Volume Check and Measurement
Along with the building balance, the unit’s air volume (cfm) should be measured and compared with its rated air volume. This unit is flexible for varying air volume, but the actual air volume should be known for making final adjustments. The most accurate way to measure the air volume is by using the pitot traverse method in the ductwork away from the blower. Other methods can be used, but should be proven and accurate. To adjust the air volume, change the fan rpm or the system losses. See Troubleshooting section in this guide.
5. Measure Motor Voltage, Amperage and Fan RPM
All access doors must be installed. Measure and record the input voltage and motor amperage(s).
To measure the fan RPM, the blower door will need to be removed. Minimize measurement time because the motor may over amp with the door removed.
Compare measured amps to the motor nameplate full load amps and correct if over amping. See the Troubleshooting section in this guide.
10 Model MSCF Modular Small Cabinet Fan
®