SERVICING

These capacitors have a 15,000 ohm, 2 watt resistor wired across its terminals. The object of the resistor is to discharge the capacitor under certain operating conditions, rather than having it discharge across the closing of the contacts within the switching device such as the Start Relay, and to reduce the chance of shock to the servicer. See the Servicing Section for specific information concerning capacitors.

RELAY, START

A potential or voltage type relay is used to take the start ca- pacitor out of the circuit once the motor comes up to speed. This type of relay is position sensitive. The normally closed contacts are wired in series with the start capacitor and the relay holding coil is wired parallel with the start winding. As the motor starts and comes up to speed, the increase in volt- age across the start winding will energize the start relay hold- ing coil and open the contacts to the start capacitor.

Two quick ways to test a capacitor are a resistance and a capacitance check.

S-15A RESISTANCE CHECK

1. Discharge capacitor and remove wire leads.

DISCHARGE CAPACITOR THROUGH A 20 TO 30 OHM RESISTOR BEFORE HANDLING.

2.Set an ohmmeter on its highest ohm scale and connect the leads to the capacitor -

A.Good Condition - indicator swings to zero and slowly returns to infinity. (Start capacitor will bleed resistor will not return to infinity. It will still read the resistance of the resistor).

B.Shorted - indicator swings to zero and stops there - replace.

C.Open - no reading - replace. (Start capacitor would read resistor resistance).

S-15B CAPACITANCE CHECK

DISCHARGE CAPACITOR THROUGH A 20 TO 30 OHM RESISTOR BEFORE HANDLING.

Using a hookup as shown below, take the amperage and volt- age readings and use them in the formula:

Capacitance (MFD) = 2650 X Amperage

Voltage

Volt / Ohm

Meter

15 AMP FUSE

 

AMMETER

 

 

 

 

 

 

Volt / Ohm

TESTING CAPACITANCE

Meter

 

 

 

r Capacito

TESTING CAPACITOR RESISTANCE

26

Image 26
Contents Service Instructions System Operation Scheduled MaintenanceProduct Design ServicingWiring Diagrams 16B Checking Fan & Blower Motor ECM MotorsRecognize Safety SYMBOLS, Words and Labels Important InformationSafe Refrigerant Handling Product Identification Accessories Part Number Description Fits ModelsMeasurement in inches Filter Size 16 x 25 xRequires 1 filter ACCESSORIES*PH1524-60M4 MOTORIZED/MANUAL Fresh AIR Dampers Downflow ApplicationsModel Return Supply ModelEconomizer GPH13MED103 Roof Curbs PGC101/102/103 46 1/4 39 3/8 14 1/2 12 1/2 x 15 x 22 1/2Product Design Location & ClearancesCompressors Indoor Blower MotorElectrical Wiring Line Voltage WiringHeating Cycle System OperationCooling Cooling CycleFAN Operation Airflow Adjustments for Indoor Blower MotorDefrost Cycle Thermostat Wiring Thermostat Fan Only ModeCFM Trim Adjust CFM DeliveryTypical Heat Pump System in Cooling Typical Heat Pump System in HeatingOnce a Year Scheduled MaintenanceOnce a Month Cooling /HEAT PUMP- Service Analysis Guide ServicingChecking Voltage Line Voltage NOW Present3C Heating Anticipator Checking Wiring3B Cooling Anticipator Indoor Blower MotorChecking Transformer and Control Circuit Single PhaseThree Phase Checking Contactor ContactsChecking Capacitor Checking Loss of Charge ProtectorChecking High Pressure Control Ammeter 15A Resistance Check15B Capacitance Check RELAY, StartChecking Motors APH15 M Series OnlyChart on Next Chart from Previous GPH15 M Series Only 16D Checking GE X13TM MotorsChecking Compressor Windings GE X13TM Motor Connections17B Ground Test Testing Compressor Windings17A Resistance Test Compressor Ground Test17D Operation Test 17C Unloader Test ProcedureUnloader Test Procedure Testing Defrost Thermostat Testing Crankcase HeaterTesting Defrost Control Checking Reversing Valve and SolenoidEvacuation Leak Testing Nitrogen or NITROGEN-TRACEDRefrigeration Repair Practice Brazing MaterialsCharging An inaccurately charged system will cause future prob- lemsThermostatic Expansion Valve Final Charge AdjustmentChecking Compressor Efficiency TXV ValvesUnderfeeding Superheat and Subcooling Adjustment on TXV ApplicationsOverfeeding SuperheatSubcooling = SAT. Liquid TEMP. Liquid Line Temp Checking SubcoolingTwo Speed Application *PH1548**-*PH1560 Heat Pump Heating CyclePressure vs. Temperature Chart 410A Required Liquid Line Temperature Refrigerant Overcharge Checking Expansion Valve OperationChecking Restricted Liquid Line NON-CONDENSABLESReversing Valve Replacement Suction Line Drier Clean-Up MethodChecking External Static Pressure Checking Temperature RiseChecking Temperature Rise Total External StaticWiring Diagrams OT18-60A Outdoor ThermostatRoom Thermostat Single Phase HKR** Heat KIT PH15**M4Diagrams GPH13MED Economizer for *PH15**M4
Related manuals
Manual 26 pages 45.36 Kb

R-410A specifications

Goodman Manufacturing, a well-respected name in the HVAC industry, has made significant advancements with their R-410A refrigerant technology. R-410A, a hydrofluorocarbon (HFC), has positioned itself as a superior alternative to the older R-22 refrigerant, which has been phased out due to its ozone-depleting properties. Goodman’s commitment to energy efficiency and environmental sustainability is well reflected in their use of R-410A in their air conditioning and heat pump systems.

One of the main features of Goodman’s R-410A systems is their exceptional energy efficiency. The R-410A refrigerant operates at a higher pressure than R-22, which allows for better heat transfer and improved cooling capacity. This results in reduced energy consumption and lower utility bills for consumers. Goodman’s air conditioning units designed for use with R-410A are often rated with high Seasonal Energy Efficiency Ratio (SEER) ratings, making them an eco-friendly choice for residential and commercial applications.

Another notable technology employed by Goodman is their commitment to reliable performance through advanced compressor designs. Goodman's scroll compressors are optimized for R-410A, ensuring quieter operation and reducing vibration levels. These compressors are known for their efficiency and longevity, making them a favorite among homeowners seeking dependable and durable climate control solutions.

Goodman's multi-stage cooling systems that utilize R-410A offer precise temperature control and enhanced comfort. By controlling the speed of the compressor, Goodman’s units can adjust output according to the heating or cooling demand, maximizing comfort while minimizing energy waste. This adaptability not only enhances indoor air quality but also contributes to a greener environment by using less energy.

Furthermore, Goodman incorporates high-tech diagnostic controls into their systems. These controls provide real-time performance data, allowing homeowners and technicians to monitor system status and troubleshoot issues more easily. By using R-410A combined with these innovative technologies, Goodman emphasizes reliability and user-friendly operation.

In conclusion, Goodman Manufacturing’s use of R-410A refrigerant reflects their dedication to efficiency, reliability, and environmental stewardship in HVAC solutions. The combination of advanced compressor technologies, high energy efficiency, and innovative controls solidifies Goodman’s reputation as a leader in the industry, offering homeowners and businesses the comfort and peace of mind they deserve.