Goodman Mfg R-410A manual Checking Expansion Valve Operation, Checking Restricted Liquid Line

Page 41

SERVICING

S-110 CHECKING EXPANSION VALVE OPERATION

1.Remove the remote bulb of the expansion valve from the suction line.

2.Start the system and cool the bulb in a container of ice water, closing the valve. As you cool the bulb, the suction pressure should fall and the suction temperature will rise.

3.Next warm the bulb in your hand. As you warm the bulb, the suction pressure should rise and the suction tempera- ture will fall.

4.If a temperature or pressure change is noticed, the expan- sion valve is operating. If no change is noticed, the valve is restricted, the power element is faulty, or the equalizer tube is plugged.

5.Capture the charge, replace the valve and drier, evacuate and recharge.

S-112 CHECKING RESTRICTED LIQUID LINE

When the system is operating, the liquid line is warm to the touch. If the liquid line is restricted, a definite temperature drop will be noticed at the point of restriction. In severe cases, frost will form at the restriction and extend down the line in the direction of the flow.

Discharge and suction pressures will be low, giving the ap- pearance of an undercharged unit. However, the unit will have normal to high subcooling.

If a restriction is located, replace the restricted part, replace drier, evacuate and recharge.

S-113 REFRIGERANT OVERCHARGE

An overcharge of refrigerant is normally indicated by exces- sively high head pressure and/or liquid return to the compres- sor.

If high head pressure is not indicated, an overcharge or a sys- tem containing non-condensables could be the problem.

If overcharging is indicated:

1.Start the system.

2.Remove small quantities of gas from the suction line dill valve until the head pressure is reduced to normal.

3.Observe the system while running a cooling performance test, if a shortage of refrigerant is indicated, then the sys- tem contains non-condensables. See S-114 Non- Condensables.

S-114 NON-CONDENSABLES

Check for non-condensables.

1.Shut down the system and allow the pressures to equalize for a minimum of 15 minutes.

2.Take a pressure reading.

3.Compare this pressure to the temperature of the coldest coil since this is where most of the refrigerant will be. If the pressure indicates a higher temperature than that of the coil temperature, non-condensables are present.

To remove the non-condensables.

1.Remove the refrigerant charge.

2.Replace and/or install liquid line drier

3.Evacuate and recharge.

S-115 COMPRESSOR BURNOUT

When a compressor burns out, high temperature develops caus- ing the refrigerant, oil and motor insulation to decompose form- ing acids and sludge.

If a compressor is suspected of being burned-out, attach a refrigerant hose to the liquid line dill valve and properly remove and dispose of the refrigerant.

VIOLATION OF EPA REGULATIONS MAY RESULT IN FINES OR OTHER PENALITIES.

Now determine if a burn out has actually occurred. Confirm by analyzing an oil sample using a Sporlan Acid Test Kit, AK-3 or its equivalent.

Remove the compressor and obtain an oil sample from the suction stub. If the oil is not acidic, either a burnout has not occurred or the burnout is so mild that a complete clean-up is not necessary.

If acid level is unacceptable, the system must be cleaned by using the clean-up drier method.

DO NOT ALLOW THE SLUDGE OR OIL TO CONTACT THE SKIN, SEVERE BURNS MAY RESULT.

41

Image 41
Contents Service Instructions Product Design Scheduled MaintenanceSystem Operation Servicing16B Checking Fan & Blower Motor ECM Motors Wiring DiagramsImportant Information Recognize Safety SYMBOLS, Words and LabelsSafe Refrigerant Handling Product Identification Part Number Description Fits Models AccessoriesMeasurement in inches Filter Size 16 x 25 xRequires 1 filter MOTORIZED/MANUAL Fresh AIR Dampers Downflow Applications ACCESSORIES*PH1524-60M4Model Model Return SupplyEconomizer GPH13MED103 PGC101/102/103 46 1/4 39 3/8 14 1/2 12 1/2 x 15 x 22 1/2 Roof CurbsLocation & Clearances Product DesignIndoor Blower Motor CompressorsLine Voltage Wiring Electrical WiringCooling System OperationHeating Cycle Cooling CycleFAN Operation Airflow Adjustments for Indoor Blower MotorDefrost Cycle CFM Trim Adjust Thermostat Fan Only ModeThermostat Wiring CFM DeliveryTypical Heat Pump System in Heating Typical Heat Pump System in CoolingOnce a Year Scheduled MaintenanceOnce a Month Servicing Cooling /HEAT PUMP- Service Analysis GuideLine Voltage NOW Present Checking Voltage3B Cooling Anticipator Checking Wiring3C Heating Anticipator Indoor Blower MotorThree Phase Single PhaseChecking Transformer and Control Circuit Checking Contactor ContactsChecking Capacitor Checking Loss of Charge ProtectorChecking High Pressure Control 15B Capacitance Check 15A Resistance CheckAmmeter RELAY, StartAPH15 M Series Only Checking MotorsChart on Next Chart from Previous Checking Compressor Windings 16D Checking GE X13TM MotorsGPH15 M Series Only GE X13TM Motor Connections17A Resistance Test Testing Compressor Windings17B Ground Test Compressor Ground Test17D Operation Test 17C Unloader Test ProcedureUnloader Test Procedure Testing Defrost Control Testing Crankcase HeaterTesting Defrost Thermostat Checking Reversing Valve and SolenoidRefrigeration Repair Practice Leak Testing Nitrogen or NITROGEN-TRACEDEvacuation Brazing MaterialsAn inaccurately charged system will cause future prob- lems ChargingChecking Compressor Efficiency Final Charge AdjustmentThermostatic Expansion Valve TXV ValvesOverfeeding Superheat and Subcooling Adjustment on TXV ApplicationsUnderfeeding SuperheatTwo Speed Application *PH1548**-*PH1560 Checking SubcoolingSubcooling = SAT. Liquid TEMP. Liquid Line Temp Heat Pump Heating CyclePressure vs. Temperature Chart 410A Required Liquid Line Temperature Checking Restricted Liquid Line Checking Expansion Valve OperationRefrigerant Overcharge NON-CONDENSABLESSuction Line Drier Clean-Up Method Reversing Valve ReplacementChecking Temperature Rise Checking Temperature RiseChecking External Static Pressure Total External StaticOT18-60A Outdoor Thermostat Wiring DiagramsRoom Thermostat PH15**M4 Single Phase HKR** Heat KITGPH13MED Economizer for *PH15**M4 Diagrams
Related manuals
Manual 26 pages 45.36 Kb

R-410A specifications

Goodman Manufacturing, a well-respected name in the HVAC industry, has made significant advancements with their R-410A refrigerant technology. R-410A, a hydrofluorocarbon (HFC), has positioned itself as a superior alternative to the older R-22 refrigerant, which has been phased out due to its ozone-depleting properties. Goodman’s commitment to energy efficiency and environmental sustainability is well reflected in their use of R-410A in their air conditioning and heat pump systems.

One of the main features of Goodman’s R-410A systems is their exceptional energy efficiency. The R-410A refrigerant operates at a higher pressure than R-22, which allows for better heat transfer and improved cooling capacity. This results in reduced energy consumption and lower utility bills for consumers. Goodman’s air conditioning units designed for use with R-410A are often rated with high Seasonal Energy Efficiency Ratio (SEER) ratings, making them an eco-friendly choice for residential and commercial applications.

Another notable technology employed by Goodman is their commitment to reliable performance through advanced compressor designs. Goodman's scroll compressors are optimized for R-410A, ensuring quieter operation and reducing vibration levels. These compressors are known for their efficiency and longevity, making them a favorite among homeowners seeking dependable and durable climate control solutions.

Goodman's multi-stage cooling systems that utilize R-410A offer precise temperature control and enhanced comfort. By controlling the speed of the compressor, Goodman’s units can adjust output according to the heating or cooling demand, maximizing comfort while minimizing energy waste. This adaptability not only enhances indoor air quality but also contributes to a greener environment by using less energy.

Furthermore, Goodman incorporates high-tech diagnostic controls into their systems. These controls provide real-time performance data, allowing homeowners and technicians to monitor system status and troubleshoot issues more easily. By using R-410A combined with these innovative technologies, Goodman emphasizes reliability and user-friendly operation.

In conclusion, Goodman Manufacturing’s use of R-410A refrigerant reflects their dedication to efficiency, reliability, and environmental stewardship in HVAC solutions. The combination of advanced compressor technologies, high energy efficiency, and innovative controls solidifies Goodman’s reputation as a leader in the industry, offering homeowners and businesses the comfort and peace of mind they deserve.