TROUBLESHOOTING
FAN BLADE SETTING DIMENSIONS
Shown in Figure 8 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to Table 1 for unit specific dimension.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.
FIGURE 8
FAN BLADE SETTING
AIRFLOW
"A"
TABLE 1
FAN BLADE DIMENSION
Model | Dimension | |
A | ||
| ||
W17A2 / W17L2 |
| |
W18A2 / W18L2 | 1.00" | |
W24A2 / W24L2 |
| |
W30A2 / W30L2 | 1.25" | |
W36A2 / W36L2 | ||
| ||
W42A2 / W42L2 |
| |
W48A2 / W48L2 | 1.75" | |
W60A2 / W60L2 | ||
| ||
W70A2 / W70L2 |
|
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.
The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.
REMOVAL OF FAN SHROUD
1.Disconnect all power to the unit.
2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3.Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.
4.Unwire condenser fan motor.
5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.
6.Service motor/fan as needed.
7.Reverse steps to reinstall.