Bard w17a2 FAN Blade Setting Dimensions, Refrigerant Charge, Removal of FAN Shroud

Page 18

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Shown in Figure 8 is the correct fan blade setting for proper air delivery across the outdoor coil. Refer to Table 1 for unit specific dimension.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 8

FAN BLADE SETTING

AIRFLOW

"A"

MIS-1724

TABLE 1

FAN BLADE DIMENSION

Model

Dimension

A

 

W17A2 / W17L2

 

W18A2 / W18L2

1.00"

W24A2 / W24L2

 

W30A2 / W30L2

1.25"

W36A2 / W36L2

 

W42A2 / W42L2

 

W48A2 / W48L2

1.75"

W60A2 / W60L2

 

W70A2 / W70L2

 

R-410A

REFRIGERANT CHARGE

This unit was charged at the factory with the quantity of refrigerant listed on the serial plate. AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity.

The following pressure tables show nominal pressures for the units. Since many installation specific situations can affect the pressure readings, this information should only be used by certified technicians as a guide for evaluating proper system performance. They shall not be used to adjust charge. If charge is in doubt, reclaim, evacuate and recharge the unit to the serial plate charge.

REMOVAL OF FAN SHROUD

1.Disconnect all power to the unit.

2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.

3.Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

Manual

2100-581B

Page

18 of 26

Image 18
Contents Bard Manufacturing Company, Inc Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersShipping Damage GeneralAIR Conditioner Wall Mount Model Nomenclature Fresh AIR Intake Duct WorkFilters Condensate DrainWall Mounting Information Mounting the UnitRight Unit Left UnitMounting Instructions Mounting Instructions Recommended 1 Clearance from 29 7/8 Combustible MaterialsW42A2, W42L2, W48A2, W48L2, W60A2, W60L2, W70A2, W70L2 Electric Heat Clearance Concrete Block Wall Installation Wall Mounting InstructionsCommon Wall Mounting Installations Free AIR Flow Ducted Supply No Duct Return AT UnitWiring Main Power Wiring LOW Voltage WiringTAP Range Safety Practices Topping OFF System ChargeThree Phase Scroll Compressor Start UP Information Important Installer NoteHigh Pressure Switch Phase MonitorPressure Service Ports Sequence of OperationCompressor Control Module FAN Blade Dimension FAN Blade Setting DimensionsFAN Blade Setting Refrigerant ChargeCooling Pressure Table DB/WBElectrical Specifications W**A Series Electrical Specifications W**L Series Recommended Airflow Indoor Blower PerformanceMaximum ESP of Operation Electric Heat only Electric Heat Optional Accessories Right Hand Heater Kits Circuit Breaker Wmcb & Pull Disconnect WmpdOptional Accessories Left Hand KitsVent & Control Options W17, W18, W24 W30, W36 W42, W48, W60, W70