TABLE 5
RECOMMENDED AIRFLOW
| Nominal | Nominal | Recommended | Factory Speed | ||
Model | Rated | Rated | ||||
Airflow Range | Connection | |||||
| CFM * | ESP * | ||||
|
|
|
| |||
W17A, W17L | 600 | .40 | 550 | - 725 | Low | |
|
|
|
|
|
| |
W18A, W18L | 550 | .45 | 550 | - 725 | Low | |
W24A, W24L | 800 | .30 | 700 | - 950 | Single | |
W30A, W30L | 1000 | .30 | 850 - 1300 | High | ||
|
|
|
|
| ||
W36A, W36L | 1100 | .20 | 930 - 1350 | High | ||
W42A, W42L | 1400 | .45 | 1600 - 1150 | High | ||
|
|
|
|
|
| |
W48A, W48L | 1550 | .30 | 1750 | - 1285 | High | |
W60A, W60L | 1700 | .40 | 1950 | - 1375 | High | |
|
|
|
|
|
| |
W70A, W70L | 1700 | .20 | 1950 | - 1375 | High |
* Rated CFM and ESP on factory speed connection.
TABLE 6
INDOOR BLOWER PERFORMANCE
Speed |
| W17/18 |
| W24 |
| W30 |
|
| W36 |
|
| W42/48 |
|
| W60 |
|
| W70 |
| ||||||||
High | Low | Single | High | Low | High | Low | High | Low | High | Low | High | Low | |||||||||||||||
| |||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
ESP | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | Dry | Wet | |
(Inch | |||||||||||||||||||||||||||
Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | Coil | ||
H20) | |||||||||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
0.0 | 1045 | 1025 | 760 | 745 | 990 | 970 | 1370 | 1285 | 910 | 885 | 1415 | 1275 | 955 | 925 | 1850 | 1800 | 1605 | 1555 | 2080 | 2015 | 1505 | 1460 | 2050 | 1845 | 1490 | 1400 | |
0.1 | 1010 | 970 | 730 | 715 | 945 | 925 | 1305 | 1225 | 885 | 860 | 1350 | 1215 | 945 | 915 | 1775 | 1725 | 1545 | 1500 | 2020 | 1960 | 1450 | 1405 | 1970 | 1770 | 1425 | 1340 | |
0.2 | 940 | 905 | 700 | 685 | 890 | 870 | 1225 | 1135 | 850 | 815 | 1265 | 1125 | 925 | 900 | 1685 | 1640 | 1460 | 1415 | 1925 | 1865 | 1395 | 1355 | 1905 | 1700 | 1375 | 1295 | |
0.3 | 860 | 830 | 670 | 655 | 820 | 800 | 1115 | 1020 | 790 | 755 | 1190 | 1060 | 875 | 850 | 1590 | 1550 | 1390 | 1345 | 1870 | 1815 | 1340 | 1300 | 1830 | 1645 | 1225 | 1150 | |
0.4 | 780 | 750 | 610 | 595 | 735 | 720 | 1005 | 910 | 695 | 660 | 1085 | 975 | 780 | 755 | 1495 | 1460 | 1310 | 1270 | 1755 | 1705 | 1225 | 1185 | 1725 | 1550 | 1140 | 1070 | |
0.5 | 665 | 640 | 485 | 455 | 605 | 590 | 865 | 775 | 590 | 560 | 970 | 865 | 640 | 615 | 1400 | 1365 | 1225 | 1185 | 1660 | 1610 | 1125 | 1085 | 1500 | 1350 | 1050 | 985 |
TABLE 7
MAXIMUM ESP OF OPERATION
ELECTRIC HEAT ONLY
| W17A/L, |
|
|
|
|
|
|
|
|
|
Model | W18A/L, |
| W30A/L, W36A/L |
| W42A/L, W48A/L | W60A/L, W70A/L | ||||
| W24A/L |
|
|
|
|
|
|
|
|
|
Outlet | FRONT | FRONT | TOP |
| FRONT | FRONT | ||||
Speed | Single | High | Low | High |
| Low | High | Low | High | Low |
.50 | .50 | .50 | .50 |
| .50 | .50 | .50 | .50 | .50 | |
|
|
| .50 |
| .45 |
|
|
|
| |
.50 | .50 | .50 |
|
|
| .50 | .50 | .50 | .50 | |
.50 | .50 | .50 |
|
|
|
|
|
|
| |
| .50 | .45 | .50 |
| .35 | .50 | .50 | .50 | .50 | |
| .40 | .35 |
|
|
| .50 | .50 | .50 | .50 | |
|
|
|
|
|
| .50 | .45 | .50 | .40 | |
.50 | .50 | .50 | .50 |
| .50 | .50 | .50 | .50 | .50 | |
.50 | .50 | .40 |
|
|
|
|
|
|
| |
| .50 | .50 | .45 |
| .40 | .50 | .50 | .50 | .50 | |
| .45 | .30 |
|
|
| .50 | .50 | .50 | .50 | |
|
|
|
|
|
| .50 | .50 | .50 | .50 | |
| .50 | .50 | .50 |
| .50 | .50 | .50 | .50 | .50 | |
| .50 | .50 |
|
|
|
|
|
|
| |
| .50 | .40 | .45 |
| .40 | .50 | .50 | .50 | .50 | |
| .45 | .35 |
|
|
| .50 | .50 | .50 | .50 |
Values shown are for units equipped with standard
Derate ESP by .15 for
Manual | |
Page | 22 of 26 |