Bard w17a2 installation instructions Electrical Specifications W**L Series

Page 21

TABLE 4

Electrical Specifications — W**L Series

 

 

No.

 

Single Circuit

 

 

 

 

Dual Circuit

 

 

 

 

 

 

Rated

 

Minimum

Maximum

 

 

 

Field

Maximum

Field

Circuit

External Fuse

Field Power

Ground

MODEL

Volts &

Minimum

Power

External

Power

Ground

Ampacity

or Ckt. Breaker

Wire Size

Wire Size

 

Phase

Circuit

 

Circuits

Fuse or

Wire

Wire

 

 

 

 

 

 

 

 

 

 

 

 

Ampacity

Ckt. A

Ckt. B

Ckt. A

Ckt. B

Ckt. A

 

Ckt. B

Ckt. A

 

Ckt. B

 

 

 

Ckt. Brkr.

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W17, 18L2-A00,A0Z

 

1

16

20

12

12

 

 

 

 

 

 

 

 

 

 

A05

230/208-1

1

30

30

10

10

 

 

 

 

 

 

 

 

 

 

A08

1

46

50

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A10

 

1

56

60

6

10

 

 

 

 

 

 

 

 

 

 

W24L2-A00, A0Z

 

1

21

30

10

10

 

 

 

 

 

 

 

 

 

 

A05

230/208-1

1

30

30

10

10

 

 

 

 

 

 

 

 

 

 

A08

1

46

50

8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A10

 

1

56

60

6

10

 

 

 

 

 

 

 

 

 

 

W24L2-B00, B0Z

230/208-3

1

15

20

12

12

 

 

 

 

 

 

 

 

 

 

B06

1

22

25

10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W24L2-C00, C0Z

460-3

1

9

15

14

14

 

 

 

 

 

 

 

 

 

 

C06

1

11

15

14

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W30L2-A00*, A0Z*

 

1

24

35

8

10

 

 

 

 

 

 

 

 

 

 

A05*

 

1

32

35

8

10

 

 

 

 

 

 

 

 

 

 

A08

230/208-1

1

47

50

8

10

 

 

 

 

 

 

 

 

 

 

A10*

 

1

58

60

6

10

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

84

90

4

8

58

26

60

30

6

 

10

10

 

10

W30L2-B00*, B0Z*

 

1

18

20

12

12

 

 

 

 

 

 

 

 

 

 

B09*

230/208-3

1

33

35

8

10

 

 

 

 

 

 

 

 

 

 

B15

 

1

51

60

6

10

 

 

 

 

 

 

 

 

 

 

W30L2-C00*, C0Z*

 

1

11

15

14

14

 

 

 

 

 

 

 

 

 

 

C09*

460-3

1

17

20

12

12

 

 

 

 

 

 

 

 

 

 

C15

 

1

26

30

10

10

 

 

 

 

 

 

 

 

 

 

W36L2-A00*, A0Z*

 

1

29

35

8

10

 

 

 

 

 

 

 

 

 

 

A05*

230/208-1

1

32

35

8

10

 

 

 

 

 

 

 

 

 

 

A10*

1

58

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

84

90

4

8

58

26

60

30

6

 

10

10

 

10

W36L2-B00*, B0Z*

 

1

23

30

10

10

 

 

 

 

 

 

 

 

 

 

B09*

230/208-3

1

33

35

8

10

 

 

 

 

 

 

 

 

 

 

B15

 

1

51

60

6

10

 

 

 

 

 

 

 

 

 

 

W36L2-C00*, C0Z*

 

1

11

15

14

14

 

 

 

 

 

 

 

 

 

 

C09*

460-3

1

16

20

12

12

 

 

 

 

 

 

 

 

 

 

C15

 

1

26

30

10

10

 

 

 

 

 

 

 

 

 

 

W42L2-A00, A0Z

 

1

32

50

8

10

 

 

 

 

 

 

 

 

 

 

A05

230/208-1

1

32

50

8

10

 

 

 

 

 

 

 

 

 

 

A10

1

58

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

84

90

4

8

58

26

60

30

6

 

10

10

 

10

W42L2-B00, B0Z

 

1

24

35

8

10

 

 

 

 

 

 

 

 

 

 

B09

230/208-3

1

33

35

8

10

 

 

 

 

 

 

 

 

 

 

B15

 

1

51

60

6

10

 

 

 

 

 

 

 

 

 

 

W42L2-C00, C0Z

 

1

12

15

14

14

 

 

 

 

 

 

 

 

 

 

C09

460-3

1

17

20

12

12

 

 

 

 

 

 

 

 

 

 

C15

 

1

26

30

10

10

 

 

 

 

 

 

 

 

 

 

W48L2-A00, A0Z

 

1

39

50

8

10

 

 

 

 

 

 

 

 

 

 

A05

230/208-1

1

39

50

8

10

 

 

 

 

 

 

 

 

 

 

A10

1

58

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

84

90

4

8

58

26

60

30

6

 

10

10

 

10

W48L2-B00, B0Z

 

1

27

40

8

10

 

 

 

 

 

 

 

 

 

 

B09

230/208-3

1

33

40

8

10

 

 

 

 

 

 

 

 

 

 

B15

 

1

51

60

6

10

 

 

 

 

 

 

 

 

 

 

W48L2-C00, C0Z

 

1

13

20

12

12

 

 

 

 

 

 

 

 

 

 

C09

460-3

1

17

20

12

12

 

 

 

 

 

 

 

 

 

 

C15

 

1

26

30

10

10

 

 

 

 

 

 

 

 

 

 

W60L2-A00, A0Z

 

1

42

60

8

10

 

 

 

 

 

 

 

 

 

 

A05

230/208-1

1

42

60

8

10

 

 

 

 

 

 

 

 

 

 

A10

1

60

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

86

90

3

8

60

26

60

30

6

 

10

10

 

10

W60L2-B00, B0Z

 

1

28

40

8

10

 

 

 

 

 

 

 

 

 

 

B09

230/208-3

1

35

40

8

10

 

 

 

 

 

 

 

 

 

 

B15

 

1

53

60

6

10

 

 

 

 

 

 

 

 

 

 

W60L2-C00, C0Z

 

1

15

20

12

12

 

 

 

 

 

 

 

 

 

 

C09

460-3

1

18

20

12

12

 

 

 

 

 

 

 

 

 

 

C15

 

1

27

30

10

10

 

 

 

 

 

 

 

 

 

 

W70L2-A0Z

 

1

56

60

6

10

 

 

 

 

 

 

 

 

 

 

A05

230/208-1

1

56

60

6

10

 

 

 

 

 

 

 

 

 

 

A10

1

59

60

6

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A15

 

1 or 2

85

90

4

8

59

26

60

30

6

 

10

10

 

10

W70L2-B0Z

 

1

38

60

8

10

 

 

 

 

 

 

 

 

 

 

B09

230/208-3

1

38

60

8

10

 

 

 

 

 

 

 

 

 

 

B15

 

1

53

60

6

10

 

 

 

 

 

 

 

 

 

 

W70L2-C0Z

 

1

19

30

10

10

 

 

 

 

 

 

 

 

 

 

C09

460-3

1

19

30

10

10

 

 

 

 

 

 

 

 

 

 

C15

 

1

27

35

18

10

 

 

 

 

 

 

 

 

 

 

Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

Based on 75C copper wire. All wiring must conform to the National Electrical Code and all local codes.

These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electrical code (latest version), Article 310 for power conductor sizing.

Caution: When more than one field power circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three (3) current carrying conductors are in a raceway.

* Top outlet supply option is available only factory installed and only on the selected models.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all local codes.

Manual

2100-581B

Page

21 of 26

Image 21
Contents Bard Manufacturing Company, Inc Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsShipping Damage GeneralAIR Conditioner Wall Mount Model Nomenclature Filters Duct WorkFresh AIR Intake Condensate DrainMounting the Unit Wall Mounting InformationLeft Unit Right UnitMounting Instructions Recommended 1 Clearance from 29 7/8 Combustible Materials Mounting InstructionsW42A2, W42L2, W48A2, W48L2, W60A2, W60L2, W70A2, W70L2 Electric Heat Clearance Wall Mounting Instructions Concrete Block Wall InstallationFree AIR Flow Ducted Supply No Duct Return AT Unit Common Wall Mounting InstallationsWiring Main Power Wiring LOW Voltage WiringTAP Range Topping OFF System Charge Safety PracticesHigh Pressure Switch Important Installer NoteThree Phase Scroll Compressor Start UP Information Phase MonitorPressure Service Ports Sequence of OperationCompressor Control Module FAN Blade Setting FAN Blade Setting DimensionsFAN Blade Dimension Refrigerant ChargeDB/WB Cooling Pressure TableElectrical Specifications W**A Series Electrical Specifications W**L Series Recommended Airflow Indoor Blower PerformanceMaximum ESP of Operation Electric Heat only Electric Heat Heater Kits Circuit Breaker Wmcb & Pull Disconnect Wmpd Optional Accessories Right HandKits Optional Accessories Left HandW17, W18, W24 W30, W36 W42, W48, W60, W70 Vent & Control Options