COMPLAINT | CAUSE | REMEDY | ||
|
|
|
| |
Compressor will not run, | Thermostat | Check the position of knob If not at the coldest | ||
but fan motor runs. |
| setting, advance the knob to this setting and restart | ||
|
|
| unit. | |
|
|
| Check continuity of the thermostat. Replace | |
|
|
| thermostat if circuit is open. | |
|
|
|
| |
|
| Capacitor (Discharge | Check the capacitor. | |
|
| capacitor before servicing.) | Replace if not within ±10% of manufacturers rating. | |
|
|
| Replace if shorted, open, or damaged. | |
|
|
|
| |
|
| Compressor | Check the compressor for open circuit or ground. If | |
|
|
| open or grounded, replace the compressor. | |
|
|
|
| |
|
| Overload | Check the compressor overload, if externally | |
|
|
| mounted. Replace if open. (If the compressor | |
|
|
| temperature is high, remove the overload, cool it, | |
|
|
| and retest.) | |
|
|
|
| |
Compressor cycles on | Voltage | Check the voltage. | ||
overload. |
| If not within limits, call an electrician. | ||
|
|
|
| |
|
| Overload | Check overload, if externally mounted. | |
|
|
| Replace if open. (If the compressor temperature is | |
|
|
| high, remove the overload, cool, and retest.) | |
|
|
|
| |
Compressor cycles on | Fan motor | If not running, determine the cause. Replace if | ||
overload. |
| required. | ||
|
|
|
| |
|
| Condenser air flow | Remove the cabinet. inspect the interior surface of | |
|
| restriction | the condenser; if restricted, clean carefully with a | |
|
|
| vacuum cleaner (do not damage fins) or brush. | |
|
|
| Clean the interior base before reassembling. | |
|
|
|
| |
|
| Condenser fins (damaged) | If condenser fins are closed over a large area on the | |
|
|
| coil surface, head pressures will increase, causing | |
|
|
| the compressor to overload. Straighten the fins or | |
|
|
| replace the coil. | |
|
|
|
| |
Compressor cycles on | Capacitor | Test capacitor. | ||
|
| |||
overload. | Wiring | Check the terminals. If loose, repair or replace. | ||
|
|
|
| |
|
| Refrigeration System | Check the system for a restriction. | |
|
|
| ||
Insufficient cooling or | Air filter | If restricted, clean or replace. | ||
heating |
|
| ||
Exhaust damper door | Close if open. | |||
|
| |||
|
|
|
| |
|
| Unit undersized | Determine if the unit is properly sized for the area to | |
|
|
| be cooled. | |
|
|
| ||
Excessive noise | Blower or fan | Check the set screw or clamp. If loose or missing, | ||
|
|
| correct. If the blower or fan is hitting the air guide, | |
|
|
| rearrange the air handling parts. | |
|
|
|
| |
|
| Copper tubing | Remove the cabinet carefully and rearrange tubing | |
|
|
| so that it doesn't contact the cabinet, compressor, | |
|
|
| shroud, and barrier. | |
|
|
|
|