2.3.3 CAPACITOR

1.Remove the cabinet. (Refer to section 2.1.2)

2.Remove the screw and the clamp which fasten the capacitor.

3.Disconnect all the leads of capacitor terminals.

4.Re-install the components by referring to the removal procedure, above. (See Figure 11)

2.3.4 POWER CORD

1.Remove the cabinet. (Refer to section 2.1.2)

2.Disconnect the grounding screw from the control box.

3.Disconnect the 2 receptacles.

4.Remove a screw which fastens the cord clip. (See Figure 12)

5.Remove the power cord.

6.Re-install the component by referring to the removal procedure, above.

(Use only one ground-marked hole

for ground

connection.)

 

7.If the supply cord of this appliance is damaged, it must be replaced by the same cord that can be obtained from an authorized parts dealer.

2.3.5 THERMOSTAT

1.Remove the cabinet. (Refer to section 2.1.2)

2.Remove the 2 screws which fasten the thermostat.

3.Disconnect 2 leads of thermostat terminals.

4.Remove the thermostat.

5.Re-install the components by referring to the above removal procedure. (See Figure 13)

Tem

 

 

 

 

perat

 

 

 

 

ure

Med

 

 

 

Warmer

 

 

 

Fan

Off

 

Cooler

 

 

 

High

 

Low

 

 

Cool

 

Fan

 

 

 

 

 

Low

Cool

Med

 

 

 

 

 

 

 

Cool

Mode

Figure 11

Figure 12

Figure 13

2.3.6 ROTARY SWITCH

1. Remove the cabinet. (Refer to section 2.1.2)

2. Remove the 2 screws which fasten the rotary switch.

3. Disconnect all the leads of the rotary switch terminals.

4. Remove the rotary switch.

5. Re-install the components by referring to the above removal procedure. (See Figure 14)

Figure 14

— 8—

Image 8
Contents Room Air Conditioner Service and Parts Manual Contents PrefaceItems SpecificationsModels Cooling only Model FeaturesControl Locations Disassembly Instructions Mechanical PartsFront Grille CabinetAIR Handling Parts AIR Guide and Turbo FANCompressor Electrical PartsOverload Protector Power Cord Rotary SwitchCapacitor ThermostatEvaporator Refrigerating CycleCondenser Capillary Tube Pulling Vacuum HOW to Install the Unit Checking InstallationInstallation KIT Contents Window RequirementsTighten the nut. See Figure Casement Window Installation CurtainPiping System Troubleshooting GuideOutside Dimensions Unit runs but poor cooling Ineffective Cooling Fails to Start Complaint Cause Remedy Room AIR Conditioner Voltage LimitsName Plate Rating Minimum Maximum Complaint Cause Remedy Schematic Diagram Circuit DiagramQTY Description PER SETDescription QTY PER SET MarksExploded View W0CZZReplacement Parts List Model SV08A10A, SV10A10A, SV12A10AMemo Memo Use Factory Certified Parts