Friedrich SV08, SV10, SV12 manual Electrical Parts, Overload Protector, Compressor

Page 7

2.2.3 SHROUD

1.Remove the fan. (Refer to section 2.2.2)

2.Remove the shroud. (See Figure 8)

3.Re-install the components by referring to the removal procedure, above.

2.3 ELECTRICAL PARTS

2.3.1 OVERLOAD PROTECTOR

1.Remove the cabinet. (Refer to section 2.1.2)

2.Remove the nut which fastens the terminal cover.

3.Remove the terminal cover. (See Figure 9)

4.Remove all the leads from the overload protector.

5.Remove the overload protector.

6.Re-install the components by referring to the removal procedure, above.

2.3.2 COMPRESSOR

1.Remove the cabinet. (Refer to section 2.1.2)

2.Discharge the refrigerant system using a FreonTM Recovery System.

If there is no valve to attach the recovery system to install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

3.Remove the overload protector. (Refer to section 2.3.1)

4.After purging the unit completely, unbraze the suction and discharge tubes at the compressor connections.

5.Remove the 3 nuts and the 3 washers which fasten the compressor to the base pan.

6.Remove the compressor. (See Figure 10)

7.Re-install the components by referring to the removal procedure, above.

Figure 8

Figure 9

Figure 10

— 7—

Image 7
Contents Room Air Conditioner Service and Parts Manual Preface ContentsModels SpecificationsItems Control Locations FeaturesCooling only Model Cabinet Disassembly InstructionsMechanical Parts Front GrilleAIR Guide and Turbo FAN AIR Handling PartsOverload Protector Electrical PartsCompressor Thermostat Power CordRotary Switch CapacitorCondenser Refrigerating CycleEvaporator Capillary Tube Pulling Vacuum Checking Installation HOW to Install the UnitWindow Requirements Installation KIT ContentsTighten the nut. See Figure Curtain Casement Window InstallationOutside Dimensions Troubleshooting GuidePiping System Unit runs but poor cooling Ineffective Cooling Fails to Start Name Plate Rating Minimum Maximum Room AIR Conditioner Voltage LimitsComplaint Cause Remedy Complaint Cause Remedy PER SET Schematic DiagramCircuit Diagram QTY DescriptionPER SET Marks Description QTYW0CZZ Exploded ViewModel SV08A10A, SV10A10A, SV12A10A Replacement Parts ListMemo Memo Use Factory Certified Parts