Friedrich SV10, SV08, SV12 manual Refrigerating Cycle, Condenser, Evaporator

Page 9

2.3.7 MOTOR

1.Remove the cabinet. (Refer to section 2.1.2)

2.Remove the turbo fan. (Refer to section 2.2.1)

3.Remove the fan. (Refer to section 2.2.2)

4.Remove the 4 screws which fasten the motor from the Motor Mount. (See Figure 15)

5.Remove the motor.

6.Re-install the components by referring to the removal procedure, above.(See Figure 15)

2.4 REFRIGERATING CYCLE

2.4.1 CONDENSER

CAUTION

Discharge the refrigerant system using a FreonTM Recovery System.

If there is no valve to attach the recovery system to install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

1.Remove the cabinet. (Refer to section 2.1.2)

2.Remove the 4 screws which fasten the brace.

3.Remove the 4 screws which fasten the condenser and shroud. (See Figure 16)

4.Remove the 2 screws which fasten the condenser and base pan.

5.After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.

6.Remove the condenser.

7.Re-install the components by referring to notes on p10. (See Figure 16)

Figure 15

Figure 16

2.4.2 EVAPORATOR

1.Remove the cabinet. (Refer to section 2.1.2)

2.Remove the control box.(Refer to section 2.1.3)

3.Remove the upper air guide. (Refer to section 2.2.1)

4.Remove the 2 screws which fasten the evaporator to the lower air guide.

5.Carefully move the evaporator sideways. (Refer to section 2.2.1)

6.After discharging the refrigerant completely, unbraze the interconnecting tube at the evaporator connections.

7.Remove the evaporator.

8.Re-install the components by referring to notes on page 10. (See Figure 17)

Figure 17

— 9—

Image 9
Contents Room Air Conditioner Service and Parts Manual Preface ContentsSpecifications ModelsItems Features Control LocationsCooling only Model Mechanical Parts Disassembly InstructionsFront Grille CabinetAIR Guide and Turbo FAN AIR Handling PartsElectrical Parts Overload ProtectorCompressor Rotary Switch Power CordCapacitor ThermostatRefrigerating Cycle CondenserEvaporator Capillary Tube Pulling Vacuum Checking Installation HOW to Install the UnitWindow Requirements Installation KIT ContentsTighten the nut. See Figure Curtain Casement Window InstallationTroubleshooting Guide Outside DimensionsPiping System Unit runs but poor cooling Ineffective Cooling Fails to Start Room AIR Conditioner Voltage Limits Name Plate Rating Minimum MaximumComplaint Cause Remedy Complaint Cause Remedy Circuit Diagram Schematic DiagramQTY Description PER SETPER SET Marks Description QTYW0CZZ Exploded ViewModel SV08A10A, SV10A10A, SV12A10A Replacement Parts ListMemo Memo Use Factory Certified Parts