Lincoln Electric IM604-B manual Connection of Ranger 8 to Premises Wiring

Page 22

15

15

1.Install a double pole, double throw switch between the power company meter and the premises disconnect.

Switch rating must be the same or greater than the customer’s premises disconnect and service overcurrent protection.

2.Take necessary steps to assure load is limited to the capacity of the Ranger 8 by installing a 35 amp 230V double pole circuit breaker. Maximum rated load for the 230V auxiliary is 35 amperes. Loading above 35 amperes will reduce output voltage

below the allowable -10% of rated voltage which may damage appliances or other motor driven equipment.

3.Install a 50 amp 115/230V plug (NEMA type 14-50) to the Double Pole Circuit Breaker using No. 8,

4 conductor cable of the desired length. (The

50 amp 115/230V plug is available in the optional plug kit.)

4.Plug this cable into the 50 amp 115/230V receptacle on the Ranger 8 case front.

Figure 1

CONNECTION OF RANGER 8 TO PREMISES WIRING

230Volt

60 Hz.

3-Wire

Service

230 VOLT

POWER

115 VOLT

COMPANY

115 VOLT

METER

GROUNDED CONDUCTOR

NEUTRAL

BUS

DOUBLE POLE DOUBLE THROW

SWITCH RATING TO BE THE SAME

AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

 

 

35AMP

 

 

230 VOLT

 

 

DOUBLE

50 AMP, 115/230

 

POLE

 

CIRCUIT

VOLT PLUG

230 VOLT

BREAKER

NEMA TYPE 14-50

 

 

GND

N

N

LOAD

PREMISES

DISCONNECT AND

SERVICE

GROUNDOVERCURRENT PROTECTION

50 AMP, 115/230 VOLT

RECEPTACLENOTE: No. 8 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

WARNING

Connection of Ranger 8 to premises wiring must be done by a licensed electrician and must comply with the National Electrical Code and all other applicable electrical codes.

RANGER 8 LPG

Image 22
Contents Ranger LPG Safety California Proposition 65 WarningsElectric Shock can kill Welding Sparks can cause fire or explosion IiiPrécautions DE Sûreté Sûreté Pour Soudage a L’ArcPlease Examine Carton and Equipment For Damage Immediately Ranger 8 LPGTable of Contents Auxiliary Power Design FeaturesOther Features General DescriptionMachine SpecificationsEngine Output Optional Equipment Field Installed Remote Control Receptacle Kit K892-1 IncludesStick Wire FeedRecommended Equipment TIGSpark Arrester Installation InstructionsSafety Precautions TrailersFuel Pre-Operation ServiceLPG- fuel can cause fire or explosion OilWelding Output Cables AWGAngle of Operation Location / Ventilation High Altitude OperationOperating InstructionsIdler Switch Engine ON-OFF SwitchEngine Start Push-Button Switch Welder Controls Function and Operation Stopping the Engine Break-in Period Welding Process Stick Constant Current WeldingSummary of Welding Processes Auxiliary PowerWire Feed Welding Processes Constant Voltage 115V Duplex ReceptaclesStandby Power Connections Auxiliary Power While WeldingSimultaneous Welding and Power 115/230 Volt Dual Voltage ReceptacleConnection of Ranger 8 to Premises Wiring Table A.2 Electrical Device USE with the Ranger 8 LPG Type Common Electrical Devices Possible ConcernsCH20S MaintenanceOverspeed is Hazardous Fram CA79 Champion RC12YCTroubleshooting Trouble Cause What to doTroubleshooting Wiring Diagram CCWRanger 8 LPG Code 10937 only Onan / Kohler CSA DiagramsLPG Connection Diagrams Ranger 8 / LN-25 Across the ARC Connection DiagramDimension Print Ranger 8 LPG Kohler DimensionPrint Ranger 8 LPG Ranger 8 LPG Ranger 8 LPG Need Welding Training? How To Read Shop DrawingsNew Lessons in Arc Welding Basic CoursePrecaucion Warnung