INSTALLATION | ||
|
|
|
Figure 1
CONNECTION OF EAGLE 10,000 TO PREMISES WIRING
240Volt
60 Hz.
Service
240 VOLT
POWER
120 VOLT
COMPANY
120 VOLT
METER
GROUNDED CONDUCTOR
NEUTRAL
BUS
N
DOUBLE POLE DOUBLE THROW |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| LOAD | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
SWITCH RATING TO BE THE SAME |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
AS OR GREATER THAN PREMISES |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
SERVICE OVERCURRENT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
PROTECTION. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PREMISES | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| DISCONNECT AND | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| SERVICE | |||
|
|
|
|
|
|
|
| GROUND | |||||||||||||
|
|
|
| 40 AMP | OVERCURRENT | ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| PROTECTION | |||||||
|
|
|
| 240 VOLT |
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
| DOUBLE |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
50 AMP, 120/240 |
|
| POLE |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| CIRCUIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
VOLT PLUG | 240 VOLT |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
BREAKER |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
NEMA TYPE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
GND
|
| N |
|
50 AMP, 120/240 VOLT |
| NOTE: No. 6 COPPER CONDUCTOR CABLE SEE | |
RECEPTACLE |
| ||
|
| NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE | |
|
|
| SIZE RECOMMENDATIONS. |
WARNING
Connection of EAGLE 10,000 to premises wiring must be done by a licensed electrician and must comply with the National Electrical Code and all other applicable electrical codes.
EAGLE 10,000