INSTALLATION

A-7

 

 

 

AUXILIARY POWER RECEPTACLES

Start the engine and set the “IDLER” control switch to the “High Idle” mode. Voltage is now correct at the receptacles for auxiliary power. This must be done before a tripped GFCI receptacle can be reset proper- ly. See the MAINTENANCE section for detailed infor- mation on testing and resetting the GFCI receptacle.

The auxiliary power of the RANGER 250 LPG con- sists of two 20 Amp-120 VAC (5-20R)GFCI duplex receptacles and one 50 Amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single phase 120 VAC operation.

The auxiliary power capacity is 9,000 Watts Peak, 8000 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equiva- lent to volt-amperes at unity power factor. The max permissible current of the 240 VAC output is 33 Amps. The 240 VAC output can be split to provide two sepa- rate 120 VAC outputs with a max permissible current of 33 Amps per output to two separate 120 VAC branch circuits (these circuits cannot be paralleled). Output voltage is within ± 10% at all loads up to rated capacity. All auxiliary power is protected by circuit breakers.

The 120V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

NOTE: The 240V receptacle has two 120V circuits, but are of opposite polarities and cannot be paralleled.

STANDBY POWER CONNECTIONS

The RANGER 250 LPG is suitable for temporary, standby or emergency power using the engine manu- facturer’s recommended maintenance schedule.

The RANGER 250 LPG can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 33 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.

1.Install the double-pole, double-throw switch between the power company meter and the premis- es disconnect. Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.

2.Take necessary steps to assure load is limited to the capacity of the RANGER 250 LPG by installing a 40 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 33 amperes.

Loading above the rated output will reduce output voltage below the allowable - 10% of rated voltage which may damage appliances or other motor-dri- ven equipment and may result in overheating of the RANGER 250 LPG engine and/or alternator wind- ings.

3.Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

4.Plug this cable into the 50 Amp, 120/240 Volt receptacle on the RANGER 250 LPG case front.

RANGER 250 LPG

Image 15
Contents Ranger 250 LPG California Proposition 65 Warnings SafetyElectric Shock can kill Iii Welding Sparks can cause fire or explosionSûreté Pour Soudage a L’Arc Précautions DE SûretéThank You Table of Contents Series Section DSection E Section FTechnical Specifications Ranger 250 LPG K2336-2 InstallationMachine Specifications Ranger 250 LPG Engine K2336-2 Safety Precautions PRE-OPERATION Service FuelTighten by hand Engine Cooling System Battery ConnectionRemote Control OILElectrical Connections Standby Power Connections Auxiliary Power ReceptaclesGND Connection of Ranger 250 LPG to PremisesAcross-The-Arc Model Connection of Lincoln ELEC- Tric Wire FeedersConnection of LN-15 Wire Feeder to the Ranger 250 LPG Connection of LN-7 or LN-8 to the Ranger 250 LPGConnection of Prince Spool Gun to the Ranger 250 LPG Connection of the LN-25 to the Ranger 250 LPGGeneral Description Design FeaturesAdditional Safety Precautions OperationWeld Mode Selector Switch Welding ControlsARC Control Engine Controls Typical Ranger 250 LPG Fuel Consumption Welder OperationStopping Duty CycleWire WELDING-CV TIG WeldingTypical Current Ranges 1 for Tungsten ELECTRODES2 Auxiliary Power ARC GougingRanger 250 LPG Extension Cord Length Recommendations Accessories T12153-9 50 AMP, 120/240V Power PlugRecommended Optional Equipment Maintenance Engine Maintenance ComponentsKohler Engine Engine OIL Refill Capacities AIR Cleaner ServiceAIR PRE-CLEANER Service Engine OIL ChangeSpark Plug Service AIR Filter Paper ElementSpark Plug Charging the Battery Engine Adjustment Overspeed is HazardousBattery Maintenance Cleaning the BatteryGfci Receptacle Testing and RESET- Ting Procedure Welder / Generator MaintenanceHOW to USE Troubleshooting Guide TroubleshootingService Facility Persists,Contact your localLincoln Authorized Field Contact your local Lincoln Cause Course of ActionTroubleshooting Troubleshooting Diagrams Diagrams Diagrams Diagrams Diagrams Engine Welders /LN-8 Connection Diagram Diagrams Diagrams Diagrams Diagrams Diagrams Ranger 250 LPG Dimension PrintRanger 250 LPG Ranger 250 LPG Precaucion Warnung