Lincoln Electric IM883-A manual Electrical Connections, Machine Grounding, Welding Output Cables

Page 13

A-5

INSTALLATION

A-5

 

 

 

ELECTRICAL CONNECTIONS

MACHINE GROUNDING

Because this portable engine driven welder creates its own power, it is not necessary to connect its frame to an earth ground, unless the machine is connected to premises wiring (home, shop, etc.)

To prevent dangerous electric shock, other equipment to which this engine driven welder supplies power must:

WARNING

• Be grounded to the frame of the welder using a

grounded type plug or be double insulated.

WELDING OUTPUT CABLES

With the engine off connect the electrode and work cables to the output studs. The welding process dic- tates the polarity of the electrode cable. These con- nections should be checked periodically and tightened with a 3/4" wrench.

Table A.1 lists recommended cable sizes and lengths for rated current and duty cycle. Length refers to the distance from the welder to the work and back to the welder. Cable diameters are increased for long cable lengths to reduce voltage drops.

TABLE A.1

TOTAL COMBINED LENGTH OF ELECTRODE AND WORK CABLES

• Do not ground the machine to a pipe that carries

explosive or combustible material.

------------------------------------------------------------------------

When this welder is mounted on a truck or trailer, its frame must be electrically bonded to the metal frame of the vehicle. Use a #8 or larger copper wire connect- ed between the machine grounding stud and the frame of the vehicle. When this engine driven welder is connected to premises wiring such as that in a home or shop, its frame must be connected to the

Cable Length

0-100 Ft. (0-30 meters)

100-150 Ft. (30-46 meters)

150-200 Ft. (46-61 meters)

Cable Size for

400Amps

60% Duty Cycle

2 / 0 AWG

2 / 0 AWG

3 / 0 AWG

system earth ground. See further connection instruc- tions in the section entitled "Standby Power Connections" as well as the article on grounding in the latest National Electrical Code and the local code.

In general, if the machine is to be grounded, it should be connected with a #8 or larger copper wire to a solid earth ground such as a metal water pipe going into the ground for at least ten feet and having no insulat- ed joints, or to the metal framework of a building which has been effectively grounded.

The National Electrical Code lists a number of alter- nate means of grounding electrical equipment. A machine grounding stud marked with the symbol is provided on the front of the welder.

WELDING TERMINALS

The VANTAGE 400 is equipped with a toggle switch for selecting "hot" welding terminal when in the "WELD TERMINALS ON" position or "cold" welding terminal when in the "REMOTELY CONTROLLED" position.

CABLE INSTALLATION

Install the welding cables to your VANTAGE 400 as follows.

1.The engine must be OFF to install welding cables.

2.Remove the flanged nuts from the output terminals

.

3.Connect the electrode holder and work cables to the weld output terminals. The terminals are identi- fied on the case front.

4.Tighten the flanged nuts securely.

5.Be certain that the metal piece you are welding (the “work”) is properly connected to the work clamp and cable.

6.Check and tighten the connections periodically.

CAUTION

Loose connections will cause the output termi- nals to overheat. The terminals may eventually melt.

Do not cross the welding cables at the output ter- minal connection. Keep the cables isolated and separate from one another.

------------------------------------------------------------------------

VANTAGE® 400

Image 13
Contents Vantage California Proposition 65 Warnings SafetyElectric Shock can kill Iii Welding and Cutting Sparks can Cause fire or explosionSûreté Pour Soudage a LʼArc Précautions DE SûretéThank You Table of Contents Section E Section DSection F 528Technical Specifications Vantage 400 K2410-1 K2410-2 InstallationVRD Voltage Reduction Device Safety PrecautionsLocation and Ventilation High Temperature Operation PRE-OPERATION Engine ServiceTowing Vehicle MountingRemote Control Battery ConnectionOIL FuelMachine Grounding Electrical ConnectionsWelding Output Cables Total Combined Length of Electrode and Work CablesStandby Power Connections Auxiliary Power ReceptaclesGfci Duplex Receptacles Connection of Vantage 400 to Premises Wiring Connection of LN-15 to the Vantage Shut the welder off Connection of Lincoln Electric Wire FeedersAcross The-Arc Model Control Cable ModelConnection of Prince XL Spool GUN to the Vantage General Description OperationFigure B.1 Weld Mode Selector SwitchTable B.1 Wire Feeder Voltmeter SwitchGlow Plug Push Button Engine ControlsStarting the Engine Table B.2Welder Operation Stopping the EngineDuty Cycle Electrode InformationTypical Current Ranges 1 for Tungsten ELECTRODES2 TIG WeldingTable B.3 Auxiliary Power Wire WELDING-CVARC Gouging Field Installed Options / ACCES- Sories AccessoriesWire Feeder Options TIG OptionsRoutine Maintenance MaintenanceEngine OIL Change AIR CleanerOIL Filter Change Maintenance Tightening the FAN Belt Cooling SystemBleeding the Fuel System Battery Maintenance Engine AdjustmentServicing Optional Spark ArrestorGfci Receptacle Testing and RESET- Ting Procedure Welder / Generator MaintenanceHOW to USE Troubleshooting Guide TroubleshootingLincoln Authorized Field Service FacilityContact your local Lincoln Welding without a control cable Troubleshooting Faulty control cable. Repair or Your local Lincoln Authorized Field Service FacilityDiagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagrams Diagram Wiring400 Print DimensionPrecaucion Warnung