Friedrich SP06A10, SP10A10, SP08A10, SP12A10 service manual When the remocon is not operated

Page 19

Troubleshooting

5-2-3 When the remocon is not operated

1)Check points

(1)Is the voltage of the power source normal ? (the rating voltage ±10% range. )

(2)Is the electric wire in good contact ? (CN71, RY71)

(3)Is the assembly main PCB in good contact with the TOUCH KEY PAD(SW01-SW05)

(4)Is the battery voltage of the remocon above DC 2.7V?

Turn off the power, and then turn it on

again five seconds later.

Dose the Buzzer sound, when the power on?

Y

Check whether the "COOLING ICON" LED lamp is on

and th operation starts when pressing the

on/off button of the remocon.

N

Is the battery voltage of the remocon above

DC 2.7V?

Y

Does the X-TAL(RJ 455JB) oscillate normally?

Y

Is the collector voltage of the remocon Q1, Q2 a square wave?

N

Y

N

N

N

Go to the clause "No power".

The remocon is normally operated.

Replace the battery.

Check the X-TAL for cold soldering and a short.

Replace relevant components.

Check the micom(ICT1) Q1, and Q2 for cold soldering and a short.

Replace relevant components.

Y

Is the input voltage of the micom(IC05) No.15

N

 

pin of the assembly main PCB a aquare wave?

 

Y

Replace the assembly main PCB.

Check the R415 components.

Check the assembly main PCB micom(IC05).

5-4

FRIEDRICH AIR CONDITIONING CO.

Image 19
Contents Room AIR Conditioner Avoid Dangerous Contact PrecautionsFriedrich AIR Conditioning CO Memo Dimensions Installation Installation and Operating InstructionsSelecting Area for Installation Function Description Cooling operation modeFan operation mode Energy saver operation modeDry operation mode Sleep operation modeLED display indication in case of error detection Memo Compressor Replacement Flow Chart Disassembly and ReassemblyOil quality Checking the oilReplacing and refilling the refrigerant oil Ass’y Grille Disassembly and Reassembly ProcedureSP10A10/SP12A10Part Name Procedures Remarks Disassembly and Reassembly ProcedureSP06A10/SP08A10 Friedrich AIR Conditioning Basic Checkpoints for Troubleshooting TroubleshootingNo power Troubleshooting by SymptomTroubleshooting When the Touch Key pad and Led DisplayWhen the remocon is not operated When the compressor is not operated LOW When the fan motor does not operatedMain unit Exploded View and Parts ListExploded View and Parts List Part List Exploded view and part list Friedrich AIR Conditioning CO Basic Structure Block DiagramRefrigerating Cycle Block Diagram Micom Control DiagramRemocon Micom pin assignment KS88C4716Memo PCB Diagram Part List Part List Wiring Diagram Schematic Diagrams 10-1 PCB Friedrich AIR Conditioning CO