4-2 Checking the oil
Fill the transparent container with 10cc of oil, and then conduct the test.
4-2-1 Oil quality
Condition of |
| Oil Condition | Remarks | |
Refrigerant Cycle | Color |
| Odor | |
|
| |||
|
|
|
|
|
Normal | Straw Yellow |
| No Odor | Return with the system |
|
|
|
|
|
Brown Color |
| - | Change the oil | |
|
|
|
|
|
Compressor Damage | Dark Brown |
| Pungent oil | Change the oil |
|
|
|
|
|
4-2-2 Replacing and refilling the refrigerant oil
1.Change the compressor - DO NOT recharge the oil as the compressor itself is already charged.
2.Change the condenser .... add 50cc
3.Change the evaporator .... add 50cc
4.When the refrigerant is replaced .... add 30cc oil.
5.After vacuum is completed, the oil is filled through the high pressure side.
6.In the event of a refrigerant leak, generally it is not necessary to add oil. (Unless the oil has leaked significantly.)