3-2 Function Description

Timer indicator

Remote control sensor

Fan speed adjustment button

Temperature adjustment buttons

Temperature/Timer settings

Energy Saver indicator

Dry adjustment indicator

On/Off button

Mode selection button (Cool, Fan, Dry)

3-2-1 Cooling operation mode

The compressor is turned on and off according to the ambient temperature and set temperature.

1)Compressor on and off control

Compressor on and off control according to the ambient temperature

*The compressor is turned off when "ambient temperature = set temperature

*The compressor is turned on when "ambient temperature = set temperature +1˚C"

2)Default value after power reset set temperature = 75˚F

Fan speed = High

3) Set temperature indicating (setting) range : 1˚F interval from 64˚F to 86˚F.

3-2-2 Fan operation mode

1)If "Fan operation mode" signal is received from remocon or panel.

the compressor is immediately turned off and only fan motor is operated at set blowing speed.

it changes such as "High Med Low High"( if Fan speed is selected).

2)The initial Fan motor speed is set to "High".

3)The set temperature can not be indicated and set.

3-2-3 Energy saver operation mode

*If the compressor turn off at the cooling operation, the fan motor turn off after operation during the fixation time only, and operation that energy saver by turn off the fixation time only, and operation that energy saver by turn off the motor continuously before the condition of the compressor on.

*The fan motor is not operated at flow wind operation.

*Energy saver operation specification at the cooling operation.

1)Fan motor control in compressor on : operate with setting wind speed

2)Fan motor control in compressor off : After compressor off, the fan motor is operated breeze for 2 minutes and then it turn off.

3)After the fan motor off, the compressor and fan motor is operated normally when the compressor on.

3-2

FRIEDRICH AIR CONDITIONING CO.

Image 7
Contents Room AIR Conditioner Avoid Dangerous Contact PrecautionsFriedrich AIR Conditioning CO Memo Dimensions Installation Installation and Operating InstructionsSelecting Area for Installation Function Description Cooling operation modeFan operation mode Energy saver operation modeDry operation mode Sleep operation modeLED display indication in case of error detection Memo Compressor Replacement Flow Chart Disassembly and ReassemblyOil quality Checking the oilReplacing and refilling the refrigerant oil Ass’y Grille Disassembly and Reassembly ProcedureSP10A10/SP12A10Part Name Procedures Remarks Disassembly and Reassembly ProcedureSP06A10/SP08A10 Friedrich AIR Conditioning Basic Checkpoints for Troubleshooting TroubleshootingNo power Troubleshooting by SymptomTroubleshooting When the Touch Key pad and Led DisplayWhen the remocon is not operated When the compressor is not operated LOW When the fan motor does not operatedMain unit Exploded View and Parts ListExploded View and Parts List Part List Exploded view and part list Friedrich AIR Conditioning CO Basic Structure Block DiagramRefrigerating Cycle Block Diagram Micom Control DiagramRemocon Micom pin assignment KS88C4716Memo PCB Diagram Part List Part List Wiring Diagram Schematic Diagrams 10-1 PCB Friedrich AIR Conditioning CO