Friedrich CP06F10, CP08F10 manual Capacitor, Power Cord

Page 12

Disassembly

3 CAPACITOR

 

 

Remove the control box

 

 

Remove the screw which fasten control panel from

 

 

control box

 

 

Remove the screw which located in the front

 

 

Open the bottom side of control box

 

 

Remove the screw and the clamp which fastens

 

 

the capacitor

 

 

Disconnect all the leads of capacitor terminals

 

 

Re install the components by referring to the

Figur

10

removal procedure, above (See Figure 10)

 

 

4POWER CORD

1Remove the control box

2Open the control box

3Disconnect the grounding screw from the control box

4

Disconnect the 2 receptacles

 

 

5

Remove a screw which fastens the clip cord

 

 

(See Figure 11)

 

 

6

Remove the power cord

 

 

7

Re install the component by referring to the above

 

 

removal procedure, above

 

 

 

(Use only one ground marked hole

for ground

 

 

connection

 

Figure 11

8

the supply cord of this appliance is damaged,

 

must be replaced by the special cord

(The

 

 

special cord means the cord which has the same

 

 

specification marked on the supply cord attached at

 

 

the unit

 

 

Refrigerating Cycle

CAUTION: Discharge the refrigerant system using a Freon TM Recovery System. If there is no valve to attach the recovery system, install one (such as a WATCO A-1) before venting the FreonTM. Leave the valve in place after servicing the system.

1.CONDENSER

1.Remove the cabinet.

2.Remove the 3 screws which fasten the

brace.

3. Remove the 3 screws which fasten the condenser and shroud.

4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.

5. Remove the condenser carefully.

6. Re-install the component by referring to notes. (See Figure 12)

Figure 12

12

Room Air Conditioner

Image 12
Contents Room Air Conditioner Service and Parts Manual Table of Contents Safety Precautions Be sure not to doDo not modify power cord length Do not clean the air conditioner with water Dimensions Symbols Used in this ManualOutside Dimensions Product Specifications OperationRoom Air Conditioner Disassembly Mechanical PartsFront Grille CabinetAir Handling Parts AIR Guide and BlowerElectrical Parts MotorOverload Protector CompressorPower Cord CapacitorEvaporator Capillary TubePulling Vacuum Circuit Diagram Electronic Control Device Troubleshooting Guide Piping SystemTroubleshooting Guide Unit runs but poor coolingFails to Start Electric Parts Troubleshooting Guide Possible TroubleSet the Temp. setting to lower Temp Is the voltage No.16 CN-DISP1 on Main P.W.B Assy DC 5V? Room AIR Conditioner Voltage Limits Troubleshooting Guide Complaint Cause Remedy Exploded View Pwbpcb ASSEMBLY,DISPLAY Pwbpcb ASSEMBLY,DISPLA Use Factory Certified Parts