Troubleshooting Guide
Possible Trouble 2
• The compressor does not operate.
Is Temp.
setting set lower than Room NO
YES
• Set the Temp. setting to lower Temp.
Is the voltage No.10 | NO |
| |
of IC01M 0V? |
|
YES
•Check the
•Check the wiring Diagram.
| Is the voltage N0.7 of |
| NO | |
|
|
| ||
| IC01M DC 5V? |
|
| |
|
| YES |
|
|
|
|
|
| |
|
|
|
|
|
| • Exchange IC01M. |
|
| |
|
|
|
|
|
|
|
|
|
|
Is the Unit for 3 minutes
delay?
YES
• Wait 3 Minutes
•Exchange MAIN P.W.B Ass'y.
NO
Possible Trouble 3 | • The compressor always operate. |
|
|
Is the wire connection of
YES
• Check the
Possible Trouble 4
NO
• Fan does not operate.
•Connect LEAD Wire to
Is the voltage NO.1 or 4 | NO | |
of IC01M DC 5V? |
| |
| YES |
|
|
| |
Is the voltage NO.13 or 16 | NO | |
| ||
of IC01M 0V? |
|
YES
•Check the
•Check the wiring diagram.
• Exchange IC01M.
• Exchange IC01M.
21 Room Air Conditioner